Danfoss FC 102, FC 103, FC 202, FC 301, FC 302 Installation guide

Installation Guide

VLT® Connection Kit for MCA 12x Options

1 Introduction

1.1 Purpose of the Connection Kit

Use the VLT® Connection Kit for MCA 12x Options for ensuring Ethernet cable access via the bottom of the drive. This is sometimes required for IP54 (NEMA Type 12), IP55 (NEMA Type 12), and IP66 (NEMA 4X) drives.

1.2 Compatible Drives

The VLT® Connection Kit for MCA 12x Options is compatible with the following drives:

VLT® HVAC Drive FC 102

VLT® Refrigeration Drive FC 103

VLT® AQUA Drive FC 202

VLT® AutomationDrive FC 301/FC 302

1.3 Items Supplied

The kit contains the following items:

VLT® Connection Kit for MCA 12x Options

2 x Ethernet extension cables

2 x Torx 10 screws

Installation Guide

1.4 Tools Required

The following tools are required for installing the VLT® Connection Kit for MCA 12x Option:

Torx 10 screwdriver

Flat-head screwdriver

Danfoss A/S © 2021.03

AN362449017256en-000101 / 130R0978 | 1

Danfoss FC 102, FC 103, FC 202, FC 301, FC 302 Installation guide

VLT® Connection Kit for MCA 12x Options

Installation Guide

Safety

 

 

2 Safety

2.1 Safety Instructions

W A R N I N G

DISCHARGE TIME

The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be present even when the warning indicator lights are off.

Failure to wait the specified time after power has been removed before performing service or repair work could result in death or serious injury.

-Stop the motor.

-Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and DC-link connections to other drives.

-Wait for the capacitors to discharge fully. The minimum waiting time is specified in the table Discharge time and is also visible on the nameplate on the top of the drive.

-Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors are fully discharged.

Table 1: Discharge Time

Voltage [V]

Minimum waiting time (minutes)

 

 

 

 

 

 

 

 

 

 

 

 

4

7

15

20

30

40

 

 

 

 

 

 

 

244–240

0.25–3.7 kW

5.5–37 kW

 

(0.34–5.0 hp)

 

(7.5–50 hp)

 

 

 

 

 

 

 

 

 

 

380–500

0.25–7.5 kW

11–75 kW

90–200 kW

250–500 kW

250–800 kW

 

(0.34–10 hp)

 

(15–100 hp)

(125–300 hp)

(350–650 hp)

(350–1075 hp)

 

 

 

 

 

 

315–500 kW

 

 

 

 

 

 

(450–650 hp)

 

 

 

 

 

 

 

400

90–315 kW

 

 

 

 

(125–450 hp)

 

 

 

 

 

 

 

 

 

500

110–355 kW

 

 

 

 

(150–500 hp)

 

 

 

 

 

 

 

 

 

525

55–315 kW

 

 

 

 

(75–450 hp)

 

 

 

 

 

 

 

 

 

525–600

0.75–7.5 kW

11–75 kW

 

(1.0–10 hp)

 

(15–100 hp)

 

 

 

 

 

 

 

 

 

 

525–690

1.5–7.5 kW

11–75 kW

37–315 kW

355–1200 kW

355–2000 kW

 

 

(2.0–10 hp)

(15–100 hp)

(50–450 hp)

(500–1600 hp)

(500–2700 hp)

 

 

 

 

 

 

355–710 kW

 

 

 

 

 

 

(500–950 hp)

 

 

 

 

 

 

 

690

55–315 kW

 

 

 

 

(75–450 hp)

 

 

 

 

 

 

 

 

 

2 | Danfoss A/S © 2021.03

AN362449017256en-000101 / 130R0978