ContentsVLT AQUA 12-Pulse High Power Instruction Manual
Contents
1 How to Read the Instruction Manual
1.1.1 Copyright, Limitation of Liability and Revision Rights1-1
1.1.3 Approvals1-1
2 Safety
2.1.1 High Voltage2-1
2.1.2 Safety Instructions2-1
2.1.5 Avoid Unintended Start2-2
2.1.6 Safe Stop2-2
2.1.8 IT Line Power2-3
3 Mechanical Installation
3.1 Pre-installation
3.1.1 Planning the Installation Site3-1
3.1.2 Receiving the Adjustable Frequency Drive3-1
3.1.3 Transportation and Unpacking3-1
3.1.4 Lifting3-1
3.1.5 Mechanical Dimensions3-3
1-1
2-1
3-1
3-1
3.2 Mechanical Installation
3.2.3 Terminal Locations, F8-F133-8
3.2.4 Cooling and Airflow3-14
3.3 Frame size F Panel Options
4 How to Install
4.1 Electrical Installation
4.1.1 Power Connections4-1
4.1.6 Shielded Cables4-9
4.1.9 AC line input connections4-11
4.1.11 Fuses4-12
4.1.13 Motor Bearing Currents4-14
4.1.14 Control Cable Routing4-14
4.1.16 Electrical Installation, Control Terminals4-15
4.2 Connection Examples
4.2.1 Start/Stop4-17
4.2.2 Pulse Start/Stop4-17
4.3 Electrical Installation - additional
3-7
3-17
4-1
4-1
4-17
4-19
4.3.1 Electrical Installation, Control Cables4-19
4.3.2 Switches S201, S202, and S8014-22
MG.20.Y1.22 - VLT® is a registered Danfoss trademark
ContentsVLT AQUA 12-Pulse High Power Instruction Manual
4.4 Final Set-up and Test
4.5 Additional Connections
5 How to operate the adjustable frequency drive
5.1.2 How to operate the Graphical LCP (GLCP)5-1
5.1.8 Tips and tricks5-6
6 How to program the adjustable frequency drive
6.1 How to program
6.2 Commonly Used Parameters - Explanations
6.2.1 Main Menu6-7
6.3 Parameter Options
6.3.1 Default settings6-34
6.3.2 Operation/Display 0-**6-35
6.3.3 Load/Motor 1-**6-37
6.3.4 Brakes 2-**6-39
6.3.5 Reference / Ramps 3-**6-40
6.3.6 Limits / Warnings 4-**6-41
4-22
4-23
5-1
6-1
6-1
6-7
6-34
6.3.7 Digital In/Out 5-**6-42
6.3.8 Analog In/Out 6-**6-44
6.3.9 Comm. and Options 8-**6-46
6.3.10 Profibus 9-**6-47
6.3.11 CAN Fieldbus 10-**6-48
6.3.12 Smart Logic 13-**6-49
6.3.13 Special Functions 14-**6-50
6.3.14 Adj. Freq. Drive Information 15-**6-51
6.3.15 Data Readouts 16-**6-53
6.3.16 Data Readouts 2 18-**6-55
6.3.17 Adj. Freq. Drive Closed-loop 20-**6-56
6.3.18 Ext. Closed-loop 21-**6-57
6.3.19 Application Functions 22-**6-59
6.3.20 Timed Actions 23-**6-61
6.3.21 Cascade Controller 25-**6-62
6.3.22 Analog I/O Option MCB 109 26-**6-64
6.3.24 Water Application Functions 29-**6-67
6.3.25 Bypass Option 31-**6-67
7 General Specifications
8 Troubleshooting
MG.20.Y1.22 - VLT® is a registered Danfoss trademark
7-1
8-1
ContentsVLT AQUA 12-Pulse High Power Instruction Manual
9 Index
9-1
MG.20.Y1.22 - VLT® is a registered Danfoss trademark
ContentsVLT AQUA 12-Pulse High Power Instruction Manual
MG.20.Y1.22 - VLT® is a registered Danfoss trademark
How to Read the Instruction...VLT AQUA 12-Pulse High Power Instruction Manual
1 How to Read the Instruction Manual
11
1.1.1 Copyright, Limitation of Liability and
Revision Rights
This publication contains information proprietary to
Danfoss. By accepting and using this manual, the user
agrees that the information contained herein will be used
solely for operating equipment from Danfoss or equipment
from other vendors provided that such equipment is
intended for communication with Danfoss equipment over
a serial communication link. This publication is protected
under the copyright laws of Denmark and most other
countries.
Danfoss does not warrant that a software program
produced according to the guidelines provided in this
manual will function properly in every physical, hardware
or software environment.
Although Danfoss has tested and reviewed the documentation within this manual, Danfoss makes no warranty or
representation, neither expressed nor implied, with respect
to this documentation, including its quality, performance,
or fitness for a particular purpose.
NOTE!
Indicates something to be noted by the reader.
CAUTION
Indicates a general warning.
WARNING
Indicates a high-voltage warning.
Indicates default setting
✮
1.1.3 Approvals
In no event shall Danfoss be liable for direct, indirect,
special, incidental, or consequential damages arising out of
the use, or the inability to use information contained in
this manual, even if advised of the possibility of such
damages. In particular, Danfoss is not responsible for any
costs, including but not limited to those incurred as a
result of lost profits or revenue, loss or damage of
equipment, loss of computer programs, loss of data, the
costs to substitute these, or any claims by third parties.
Danfoss reserves the right to revise this publication at any
time and to make changes to its contents without prior
notice or any obligation to notify former or present users
of such revisions or changes.
It has been assumed that all devices will be sitting behind
a firewall that does packet filtering and the environment
has well-implemented restrictions on the software that can
run inside the firewall. All nodes are assumed to be
"trusted" nodes.
1.1.2
Symbols
Symbols used in this manual
1.1.4
Available literature for VLT® AQUA
Drive FC 200
-
VLT® AQUA Drive Instruction Manual MG.20.Mx.yy
provides the neccessary information for getting
the drive up and running.
-
VLT® AQUA Drive High Power Instruction Manual
MG.20.Px.yy provides the neccessary information
for getting the HP drive up and running.
-
VLT® AQUA Drive Design Guide MG.20.Nx.yy
contains all the technical information about the
drive and customer design and applications.
-
VLT® AQUA Drive Programming Guide MN.
20.Ox.yy provides information on how to program
and includes complete parameter descriptions.
1-2MG.20.Y1.22 - VLT® is a registered Danfoss trademark
Torque limit
How to Read the Instruction...VLT AQUA 12-Pulse High Power Instruction Manual
1.1.6 Disposal Instructions
Equipment containing electrical components
may not be disposed of together with domestic
waste.
It must be separately collected with electrical
and electronic waste according to local and
currently valid legislation.
11
MG.20.Y1.22 - VLT® is a registered Danfoss trademark1-3
How to Read the Instruction...VLT AQUA 12-Pulse High Power Instruction Manual
11
1-4MG.20.Y1.22 - VLT® is a registered Danfoss trademark
SafetyVLT AQUA 12-Pulse High Power Instruction Manual
2 Safety
Caution
The adjustable frequency drive DC link capacitors remain
charged after power has been disconnected. To avoid the
electrical shock hazard, disconnect the adjustable frequency
drive from line power before carrying out maintenance. Before
servicing the adjustable frequency drive, wait the minimum
amount of time indicated below:
380– V425–1350 hp
[315–1000 kW]
525–690 V535–1875 hp
[400–1400 kW]
VLT AQUA Drive
FC 200 Series
Software version: 1.6x
This guide can be used with all
40 minutes
30 minutes
WARNING
Installation at high altitudes
380–480V: At altitudes above 9,843 feet [3 km], please
contact Danfoss regarding PELV.
525–690V: At altitudes above 6561 ft [2 km], please contact
Danfoss regarding PELV.
2.1.2 Safety Instructions
Make sure the adjustable frequency drive is
•
properly grounded.
Protect users against supply voltage.
•
Protect the motor against overloading according
•
to national and local regulations.
Motor overload protection is not included in the
•
default settings. To add this function, set
1-90 Motor Thermal Protection to value Elec. OL
trip or Elec. OL warning. For the North American
market: Electronic Thermal Overload functions
provide class 20 motor overload protection in
accordance with NEC.
The ground leakage current exceeds 3.5mA.
•
The [OFF] key is not a safety switch. It does not
•
disconnect the adjustable frequency drive from
line power.
22
adjustable frequency drives with
software
version 1.6x or later.
The actual software version
number can be read from
15-43 Software Version.
2.1.1 High Voltage
WARNING
The voltage of the adjustable frequency drive is dangerous
whenever the adjustable frequency drive is connected to
line power. Incorrect installation or operation of the motor
or adjustable frequency drive may cause damage to the
equipment, serious personal injury or death. The
instructions in this manual must therefore be observed, in
addition to applicable local and national rules and safety
regulations.
General Warning
2.1.3
WARNING
Warning:
Touching the electrical parts may be fatal - even after the
equipment has been disconnected from line power.
Make sure that other voltage inputs have been disconnected, such as load sharing (linkage of DC intermediate
circuit), as well as the motor connection for kinetic backup.
When using the adjustable frequency drive: wait at least 40
minutes.
Shorter time is allowed only if indicated on the nameplate
for the specific unit.
MG.20.Y1.22 - VLT® is a registered Danfoss trademark2-1
37
12
130BT314.10
SafetyVLT AQUA 12-Pulse High Power Instruction Manual
2.1.6
22
Leakage Current
The ground leakage current from the adjustable frequency
drive exceeds 3.5 mA. To ensure that the ground cable has
a good mechanical connection to the ground connection
(terminal 95), the cable cross-section must be at least 0.016
in2 [10 mm2] or 2 rated ground wires terminated
separately. For proper grounding for EMC, see section
Grounding in the How to Install chapter.
Residual Current Device
The drive can cause DC current in the protective
conductor. Where a residual current device (RCD) is used
for extra protection, only an RCD of Type B (time delayed)
shall be used on the supply side of this product.
Protective grounding of the adjustable frequency drive and
the use of RCDs must always follow national and local
regulations.
Before Commencing Repair Work
2.1.4
1.Disconnect the adjustable frequency drive from
line power.
2.Disconnect DC bus terminals 88 and 89 from load
share applications
3.Wait for the discharge of the DC link. See period
of time on the warning label.
4.Remove motor cable
Avoid Unintended Start
2.1.5
While the adjustable frequency drive is connected to line
power, the motor can be started/stopped using digital
commands, bus commands, references or via the keypad::
Disconnect the adjustable frequency drive from
•
line power whenever personal safety considerations make it necessary to avoid an unintended
start.
To avoid unintended start, always activate the
•
[OFF] key before changing parameters.
An electronic fault, temporary overload, a fault in
•
the line power supply, or lost motor connection
may cause a stopped motor to start. The
adjustable frequency drive with safe stop
provides protection against unintended start, if
Safe Stop Terminal 37 is deactivated or disconnected.
CAUTION
Safe Stop
The can perform the safety function Safe Torque Off (As
defined by draft CD IEC 61800-5-2) or Stop Category 0 (as
defined in EN 60204-1).
It is designed and approved suitable for the requirements
of Safety Category 3 in EN 954-1. This functionality is called
Safe Stop. Prior to integration and use of Safe Stop in an
installation, a thorough risk analysis on the installation
must be carried out in order to determine whether the
Safe Stop functionality and safety category are appropriate
and sufficient. In order to install and use the Safe Stop
function in accordance with the requirements of Safety
Category 3 in EN 954-1, the related information and
instructions of the Design Guide must be followed! The
information and instructions of the Instruction Manual are
not sufficient for a correct and safe use of the safe stop
functionality!
Safe Stop Installation
2.1.7
To carry out an installation of a Category 0 Stop
(EN60204) in conformity with Safety Category 3 (EN954-1),
follow these instructions:
1.The bridge (jumper) between Terminal 37 and
24V DC must be removed. Cutting or breaking
the jumper is not sufficient. Remove it entirely to
avoid short-circuiting. See jumper on Figure 2.1.
2.Connect terminal 37 to 24 V DC by a short
circuit-protected cable. The 24 V DC voltage
supply must be interruptible by an EN954-1
category 3 circuit interrupt device. If the interrupt
device and the are placed in the same installation
panel, you can use an non-shielded cable instead
of a shielded one.
Figure 2.1 Bridge jumper between terminal 37 and 24 VDC
Figure 2.2 shows a Stopping Category 0 (EN 60204-1) with
safety Category 3 (EN 954-1). The circuit interrupt is caused
2-2MG.20.Y1.22 - VLT® is a registered Danfoss trademark
Control
board
Rectier
Inverter
Safe
channel
Safety device Cat.3 (Circuit interrupt
device, possibly with release input)
Coast
Short-circuit protected cable
(if not inside installation cabinet)
Door contact
Mains
Frequency
Converter
M
37
5Vdc
12
R
1
R
2
6 phase
130BB566.10
SafetyVLT AQUA 12-Pulse High Power Instruction Manual
by an opening door contact. The illustration also shows
how to connect a non-safety related hardware coast.
22
Figure 2.2 Essential aspects of an installation to achieve a Stopping Category 0 (EN 60204-1) with safety Category 3 (EN 954-1).
IT Line Power
2.1.8
14-50 RFI 1 can be used to disable the factory installed
A1/B1 RFI filter option. If this is done, it will reduce the RFI
performance to A2 level. For the 525–690V adjustable
frequency drives, 14-50 RFI 1 is not available as there is no
A1/B1 Factory Installed RFI Filter option.
MG.20.Y1.22 - VLT® is a registered Danfoss trademark2-3
SafetyVLT AQUA 12-Pulse High Power Instruction Manual
22
2-4MG.20.Y1.22 - VLT® is a registered Danfoss trademark
130BB753.10
Mechanical InstallationVLT AQUA 12-Pulse High Power Instruction Manual
3 Mechanical Installation
3.1.4
Lifting
3.1 Pre-installation
3.1.1 Planning the Installation Site
NOTE!
Before performing the installation, it is important to plan
the installation of the adjustable frequency drive.
Neglecting this may result in extra work during and after
installation.
Select the best possible operation site by considering the
following (see details on the following pages and in the
respective Design Guides):
Ambient operating temperature
•
Installation method
•
How to cool the unit
•
Position of the adjustable frequency drive.
•
Cable routing
•
Ensure the power source supplies the correct
•
voltage and necessary current.
Ensure that the motor current rating is within the
•
maximum current from the adjustable frequency
drive.
Ensure that the drive is properly protected per
•
local regulations.
Always lift the adjustable frequency drive using the
dedicated lifting holes. For all 4X unit size and 52 unit size
(IP00) Units, use a bar to avoid bending the lifting holes of
the adjustable frequency drive.
Figure 3.1 Recommended lifting method, Unit Size .
3
3
Receiving the Adjustable Frequency
3.1.2
Drive
When receiving the adjustable frequency drive, make sure
that the packaging is intact, and look for any damage that
might have occurred to the unit during transport. If
damage has occurred, immediately contact the shipping
company to make a damage claim.
Transportation and Unpacking
3.1.3
Before unpacking the adjustable frequency drive, it is
recommended to unload it as close as possible to the final
installation site.
Remove the box and handle the adjustable frequency drive
on the pallet, as long as possible.
MG.20.Y1.22 - VLT® is a registered Danfoss trademark3-1
130BB688.10
130BB689.10
3
Mechanical InstallationVLT AQUA 12-Pulse High Power Instruction Manual
NOTE!
Note the plinth is provided in the same packaging as the
adjustable frequency drive but is not attached during
shipment. The plinth is required to allow airflow to the
drive to provide proper cooling. The unit sizes6X should be
positioned on top of the plinth in the final installation
location. The angle from the top of the drive to the lifting
cable should be 140°F [60°C] or greater.
In addition to the drawings above a spreader bar is an
acceptable way to lift the unit sizes 6X.
3-2MG.20.Y1.22 - VLT® is a registered Danfoss trademark
130BB754.10
800
607
IP/21
NEMA 1
IP/54
NEMA 12
1400
m3/Hr
824
CFM
618
CFM
1050
m3/Hr
1160
CFM
1970
m3/Hr
2280
2205
1497
130BB568.10
1400
607
IP/21
NEMA 1
IP/54
NEMA 12
2100
m3/Hr
1236
CFM
927
CFM
1575
m3/Hr
1160
CFM
1970
m3/Hr
2280
2205
1497
Mechanical InstallationVLT AQUA 12-Pulse High Power Instruction Manual
3.1.5 Mechanical Dimensions
3
3
Unit size 61IP 21/54 - NEMA 1/12Unit size 63IP 21/54 - NEMA 1/12
All dimensions in mm
MG.20.Y1.22 - VLT® is a registered Danfoss trademark3-3
130BB569.10
1600
607
IP/21
NEMA 1
IP/54
NEMA 12
2800
m3/Hr
1648
CFM
1236
CFM
2100
m3/Hr
2320
CFM
3940
m3/Hr
2280
2205
1497
130BB570.10
2400
607
IP/21
NEMA 1
IP/54
NEMA 12
4200
m3/Hr
2472
CFM
1854
CFM
3150
m3/Hr
2320
CFM
3940
m3/Hr
2280
2205
1497
3
Mechanical InstallationVLT AQUA 12-Pulse High Power Instruction Manual
Unit size 62IP 21/54 - NEMA 1/12Unit size 64IP 21/54 - NEMA 1/12
All dimensions in mm
3-4MG.20.Y1.22 - VLT® is a registered Danfoss trademark
130BB571.10
2000
607
IP/21
NEMA 1
IP/54
NEMA 12
2800
m3/Hr
2472
CFM
1854
CFM
3150
m3/Hr
2900
CFM
4925
m3/Hr
2280
2205
1497
130BB572.10
2800
607
IP/21
NEMA 1
IP/54
NEMA 12
4200
m3/Hr
2472
CFM
1854
CFM
3150
m3/Hr
2900
CFM
4925
m3/Hr
2280
2205
1497
Mechanical InstallationVLT AQUA 12-Pulse High Power Instruction Manual
3
3
Unit size 62IP 21/54 - NEMA 1/12Unit size 64IP 21/54 - NEMA 1/12
All dimensions in mm
MG.20.Y1.22 - VLT® is a registered Danfoss trademark3-5
F9
F8
130BB690.10
F11
F10
130BB691.10
F13
F12
130BB692.10
3
Mechanical InstallationVLT AQUA 12-Pulse High Power Instruction Manual
Mechanical dimensions, Unit Sizes 4 and 5
Unit size5161626364
Heavy-duty rated power
- 160% overload torque
IP
NEMA
Shipping
dimensions
Drive
dimensions
Height
Width38.2 in [970 mm]61.7 in [1568 mm]69.3 in [1760 mm]
Depth44.49 in [1130 mm] 44.49 in [1130 mm] 44.49 in [1130 mm] 44.49 in [1130 mm] 44.49 in [1130 mm] 44.49 in [1130 mm]
Height86.8 in [2204 mm]86.8 in [2204 mm]86.8 in [2204 mm]86.8 in [2204 mm]86.8 in [2204 mm]86.8 in [2204 mm]
Width31.50 in [800 mm]55.1 in [1400 mm]63 in [1600 mm]86.6 in [2200 mm] 78.74 in [2000 mm] 102.4 in [2600 mm]
Depth28.86 in [606 mm]28.86 in [606 mm]28.86 in [606 mm]28.86 in [606 mm]28.86 in [606 mm]28.86 in [606 mm]
Max
weight
425–600 hp [315–450 kW]
(380–480 V)
535–850 hp [400–630 kW]
(525–690 V)
21, 54
Type 12
91.5 in [2324 mm]91.5 in [2324 mm]91.5 in [2324 mm]91.5 in [2324 mm]91.5 in [2324 mm]91.5 in [2324 mm]
3-6MG.20.Y1.22 - VLT® is a registered Danfoss trademark
776
(30.6)
130BB531.10
130BB003.13
578
(22.8)
776
(30.6)
776
(30.6)
776
(30.6)
130BB574.10
776
(30.6)
(2x)
130BB575.10
624
(24.6)
579
(22.8)
130BB576.10
776
(30.6)
624
(24.6)
579
(22.8)
776
(30.6)
776
(30.6)
130BB577.10
Mechanical InstallationVLT AQUA 12-Pulse High Power Instruction Manual
3.2 Mechanical Installation
Preparation of the mechanical installation of the adjustable
frequency drive must be done carefully to ensure proper
results and to avoid additional work during installation.
Start by taking a close look at the mechanical drawings at
Figure 3.6 Space in front of
the end of this instruction manual to become familiar with
the space demands.
3.2.1 Tools Needed
3
3
To perform the mechanical installation, the following tools
are needed:
Drill with 0.39 or 0.47 in [10 or 12 mm] drill.
•
Tape measure
•
Wrench with relevant metric sockets (7–17mm)
•
Extensions to wrench
•
Sheet metal punch for conduits or cable
•
connectors in IP 21/Nema 1 and IP 54/Nema 12
drive types.
Lifting bar to lift the unit (rod or tube max. Ø
•
25mm (1 inch), able to lift minimum 400kg
(880lbs)).
Crane or other lifting aid to place the adjustable
•
frequency drive in position
A Torx T50 tool is needed to install the Unit Size
•
51IP 21/Nema 1 and IP 54/Nema 12 drive types.
General Considerations
3.2.2
Space
Ensure proper space above and below the adjustable
frequency drive to allow airflow and cable access. In
addition, space in front of the unit must be considered to
allow the panel door to be opened.
Figure 3.7 Space in front of
Figure 3.8 Space in front of
Figure 3.9 Space in front of
Wire access
Ensure that proper cable access is present including the
necessary bending allowance.
NOTE!
All cable lugs/shoes must mount within the width of the
terminal bus bar.
Figure 3.4 Space in front of
Figure 3.5 Space in front of
MG.20.Y1.22 - VLT® is a registered Danfoss trademark3-7
1
239.6 [ 9.43 ]
0.0 [ 0.00 ]
0.0 [ 0.00 ]
160.0 [ 6.30 ]
56.6 [ 2.23 ]
39.8 [ 1.57 ]
91.8 [ 3.61 ]
174.1 [ 6.85 ]
226.1 [ 8.90 ]
130BB534.10
R2/L12
R1/L11
91-1
91
S2/L22
S1/L21
92-1
T2/L32 93-1
92
T1/L3193
U/T1 96V/T2 97W/T3 98
0.0 [ 0.00 ]
57.6 [ 2.27 ]
74.0 [ 2.91 ]
100.4 [ 3.95 ]
139.4 [ 5.49 ]
172.6 [ 6.80 ]
189.0 [ 7.44 ]
199.4 [ 7.85 ]
287.6 [ 11.32 ]
304.0 [ 11.97 ]
407.3 [ 16.04 ]
464.4 [ 18.28 ]
522.3 [ 20.56 ]
524.4 [ 20.65 ]
629.7 [ 24.79 ]
637.3 [ 25.09 ]
Mechanical InstallationVLT AQUA 12-Pulse High Power Instruction Manual
3.2.3 Terminal Locations, F8-F13
3
The F enclosures have six different sizes, 61, 62, 63, F11,
F12 and 64 The , F1061 and 62 consist of an inverter
cabinet on the right and rectifier cabinet on the left. The ,
F1163 and 64 have an additional options cabinet left of
the rectifier cabinet. The 63 is an 61 with an additional
Terminal locations - Unit Sizes 61 and 63
options cabinet. The F11 is an 62 with an additional
options cabinet. The F13 is an 62 with an additional
options cabinet.
Figure 3.10 Terminal locations - Inverter and Rectifier Cabinet - and (front, left and right side view). The connector plate is 1.65 in [42
mm] below .0 level.
1) Ground bar
3-8MG.20.Y1.22 - VLT® is a registered Danfoss trademark
.0 [.0]
54.4[2.1]
169.4 [6.7]
284.4 [11.2]
407.3 [16.0]
522.3 [20.6]
637.3 [25.1]
287.4 [11.3]
253.1 [10.0]
.0 [.0]
.0 [.0]
339.4 [13.4]
287.4 [11.3]
.0 [.0]
339.4 [13.4]
308.3 [12.1]
465.6 [18.3]
465.6 [18.3]
198.1[7.8]
234.1 [9.2]
282.1 [11.1]
318.1 [12.5]
551.0 [21.7]
587.0 [23.1]
635.0 [25.0]
671.0 [26.4]
44.40 [1.75]
244.40 [9.62]
204.1 [8.0]
497.1 [19.6]
572.1 [22.5]
180.3 [7.1]
129.1 [5.1]
130BA849.10
2
2
1
3
3
3
Mechanical InstallationVLT AQUA 12-Pulse High Power Instruction Manual
Terminal locations - Unit Sizes 61 and 63
3
3
Figure 3.11 Terminal locations - Inverter Cabinet (front, left and right side view). The connector plate is 1.65 in [42 mm] below .0 level.
1) Ground bar
2) Motor terminals
3) Brake terminals
MG.20.Y1.22 - VLT® is a registered Danfoss trademark3-9
287.4 [11.32]
0.0 [0.00]
339.4 [13.36]
253.1 [9.96]
0.0 [0.00]
287.4 [11.32]
0.0 [0.00]
339.4 [13.36]
465.6 [18.33]
465.6 [18.33]
308.3 [12.14]
180.3 [7.10]
210.1 [8.27]
0.0 [0.00]
66.4 [2.61]
181.4 [7.14]
296.4 [11.67]
431.0 [16.97]
546.0 [21.50]
661.0 [26.03]
795.7 [31.33]
910.7 [35.85]
1025.7 [40.38]
246.1 [9.69]
294.1 [11.58]
330.1 [13.00]
574.7 [22.63]
610.7 [24.04]
658.7 [25.93]
694.7 [27.35]
939.4 [36.98]
975.4 [38.40]
1023.4 [40.29]
1059.4 [41.71]
144.3 [5.68]
219.3 [8.63]
512.3 [20.17]
587.3 [23.12]
880.3 [34.66]
955.3 [37.61]
TERMINAL LOCATIONSFRONT VIEW
TERMINAL LOCATIONSRIGHT VIEW
TERMINAL LOCATIONSLEFT VIEW
1
2
3
2
3
130BA850.10
146x91
A
A
A
A
A
A
A
A
A
A
FASTENER TORQUE: MIO 19 Nm (14 FT -LB)
U/T1 96 V/T2 97 W/T3 98
FASTENER TORQUE: MIO 19 Nm (14 FT -LB)
U/T1 96 V/T2 97 W/T3 98
FASTENER TORQUE: MIO 19 Nm (14 FT -LB)
U/T1 96 V/T2 97 W/T3 98
3
Mechanical InstallationVLT AQUA 12-Pulse High Power Instruction Manual
Terminal locations - Unit Sizes 62/64
Figure 3.12 Terminal locations - Inverter Cabinet (front, left and right side view). The connector plate is 1.65 in [42 mm] below .0 level.
1) Ground bar
3-10MG.20.Y1.22 - VLT® is a registered Danfoss trademark
1
239.6 [ 9.43 ]
0.0 [ 0.00 ]
0.0 [ 0.00 ]
160.0 [ 6.30 ]
56.6 [ 2.23 ]
39.8 [ 1.57 ]
91.8 [ 3.61 ]
174.1 [ 6.85 ]
226.1 [ 8.90 ]
130BB534.10
R2/L12
R1/L11
91-1
91
S2/L22
S1/L21
92-1
T2/L32 93-1
92
T1/L3193
U/T1 96V/T2 97W/T3 98
0.0 [ 0.00 ]
57.6 [ 2.27 ]
74.0 [ 2.91 ]
100.4 [ 3.95 ]
139.4 [ 5.49 ]
172.6 [ 6.80 ]
189.0 [ 7.44 ]
199.4 [ 7.85 ]
287.6 [ 11.32 ]
304.0 [ 11.97 ]
407.3 [ 16.04 ]
464.4 [ 18.28 ]
522.3 [ 20.56 ]
524.4 [ 20.65 ]
629.7 [ 24.79 ]
637.3 [ 25.09 ]
Mechanical InstallationVLT AQUA 12-Pulse High Power Instruction Manual
Terminal locations - Rectifier ()
3
3
Figure 3.13 Terminal locations - Rectifier (left side, front and right side view). The connector plate is 1.65 in [42 mm] below .0 level.
1) Load share Terminal (-)
2) Ground bar
3) Load share Terminal (+)
MG.20.Y1.22 - VLT® is a registered Danfoss trademark3-11
336.4
291.2
142.0
92.0
.0
.0
73.0
128.5
129.3
184.0
218.3
249.0
314.0
307.3
369.5
448.0
493.0
425.0
244.4
151.3
386.7
443.8
628.8
830.3
887.4
.0
130BB756.10
3
Mechanical InstallationVLT AQUA 12-Pulse High Power Instruction Manual
Figure 3.15 Terminal locations - Options cabinet (left side, front and right side view).
MG.20.Y1.22 - VLT® is a registered Danfoss trademark3-13
90
80
70
60
50
40
30
20
10
0
(%)
Drive Derating
0255075100125 150175225
130BB190.10
200
Pressure Change
130BB073.10
3
Mechanical InstallationVLT AQUA 12-Pulse High Power Instruction Manual
3.2.4 Cooling and Airflow
Cooling
Cooling can be obtained in different ways, by using the
cooling ducts in the bottom and the top of the unit, by
taking air in and out the back of the unit or by combining
the cooling possibilities.
Duct cooling
A dedicated option has been developed to optimize installation of drive types in Rittal TS8 Units utilizing the fan of
the adjustable frequency drive for forced air cooling of the
backchannel. Please consult GE for more details.
The air out the top of the Unit could but ducted outside a
facility so the heat loses from the backchannel are not
dissipated within the control room reducing airconditioning requirements of the facility.
Back cooling
The backchannel air can also be ventilated in and out the
back of a Rittal TS8 Unit. This offers a solution where the
backchannel could take air from outside the facility and
return the heat losses outside the facility thus reducing airconditioning requirements.
Airflow
The necessary airflow over the heatsink must be ensured.
The flow rate is shown below.
Unit Size
protection
IP21 / NEMA 1
IP54 / NEMA 12
Table 3.1 Heatsink Air Flow
* Airflow per fan. Unit Sizes 5X contain multiple fans.
Figure 3.16 Unit Size 61, 62, 63 and 64 Derating vs. Pressure
Change
Drive air flow: 985 m3/h (580 cfm)
Connector/Conduit Entry - IP21
3.2.5
(NEMA 1) and IP54 (NEMA12)
Cables are connected through the connector plate from
the bottom. Remove the plate and plan where to place the
entry for the connectors or conduits. Prepare holes in the
marked area on the drawing.
NOTE!
The connector plate must be fitted to the adjustable
frequency drive to ensure the specified protection degree,
as well as ensuring proper cooling of the unit. If the
connector plate is not mounted, the adjustable frequency
drive may trip on Alarm 69, Pwr. Card Temp
External ducts
If additional duct work is added externally to the Rittal
cabinet, the pressure drop in the ducting must be
calculated. Use the charts below to derate the adjustable
frequency drive according to the pressure drop.
3-14MG.20.Y1.22 - VLT® is a registered Danfoss trademark
Figure 3.17 Example of proper installation of the connector
plate.
Loading...
+ 128 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.