Service guide
Solenoid valve
Types EVR 2 - EVR 22 (version 2)
NC solder NC flare NC flange NO solder
032R9605
Disassembly and assembly of 032Lxxxx only
Mounting / dismounting of top part
EVR 2 - EVR 8
4
1
2
3
Note!
Always use
cross-tightening
Note:
tube design
Mounting / dismounting of top part
EVR 10 - EVR 22
032R9605
4
1
2
3
Note!
Always use
cross-tightening
Typ e [Nm] [kpm] [ft- lbs] Torx size
EVR 2, EVR 3,
EVR 4, EVR 6, EVR 8
3.0 0.3 2.2 T15
Mounting of support washer
Typ e [Nm] [kpm] [ft-lbs] Torx size
EVR 10, EVR 15, EVR 18
10 1 7.4 T30
EVR 20, EVR 22 30 3 22.1 T45
Special for EVR 4 - EVR 8:
Dismounting gasket and supporting ring
B
Off
A
© Danfoss | DCS (az) | 2018.11
Caution!
For EVR 2 - EVR 3, and EVR 10 - EVR 22, a screwdriver might be needed
for removal of the gasket. Be careful not to scratch the gasket surface.
DKRCC.PI.BB0.2D.02 | 1
EVR 2 – EVR 3 (NC) EVR 4 – EVR 8 (NC) EVR 10 – EVR 22 (NC) EVR 4 – EVR 8 (NO) EVR 10 – EVR 20 (NO)
1
1
1
2
2
2
1
2
Pos. no. Description Dimension Material
1
O-ring ID 14.30 x H 2.40 Chloroprene
EVR 2 - EVR 3 OD 22.2 x ID 18.0 x H 2.5 Chloroprene
EVR 4 - EVR 8 OD 26.1 x ID 21.1 x H 2.5 Chloroprene
2 Gasket
EV R 10 OD 40.7 x ID 35.5 x H 2.6 Chloroprene
EVR 15 - EVR 18 OD 48.7 x ID 43.5 x H 2.6 Chloroprene
EVR 20 - EVR 22 OD 64.2 x ID 59.0 x H 2.6 Chloroprene
1
2
© Danfoss | DCS (az) | 2018.01