Danfoss EvoFlat FSS Fact sheet

Fact sheet
EvoFlatTM FSS fully insulated
Flat station with integrated water heater for apartments, single- and multi-family houses
FEATURES AND BENEFITS
• Flat station for direct heating and DHW heating based on flow principle
• Innovative, energy-saving controller TCP-M in combination with high performance heat exchanger for on­demand water heating
• Capacity: 15 kW HE, 55 kW DHW
• Minimum space required for installation
• Built-in or wall-mounted variant
• Pipes and plate heat exchanger made of stainless steel
• No retightening of internal connections required, due to newly designed click connection,
• Constant DHW temperature even at fluctuating flow temperatures or differential pressures
• Minimized risk of lime scale and bacteria formation
Application
Die EvoFlatTM FSS is a compact and simple to operate flat station. Especially suitable for two-pipe systems in residential build­ings, which are supplied from a secon­dary connected district heating system, a block heating system, a centrally located boiler system (oil, gas or biomass, as well as for CHP systems. The EvoFlat FSS
TM
is available as built-in variant with a recess box or as mount-on-wall variant with cover.
Primary side (DH)
The flat station is prefabricated with in­terconnecting components such as a dif­ferential pressure controller (integrated in main temperature controller TPC-M), strainer, sensor pockets and fitting piece for insertion of a heat meter.
Heating (HE)
The self-acting temperature controller TPC - M with integrated differential pres­sure controller sets the optimum operat­ing conditions for heating and DHW. In order to enable a time dependent tem­perature control program, a zone valve with actuator is included and can be connected to a room thermostat as an option.
Domestic hot water (DHW)
The domestic hot water is prepared in the heat exchanger based on the flow principle and the temperature is regu­lated by the self-acting controller with integrated differential pressure con­troller - the TPC-M. Supreme ease of operation is ob­tained via the combined hydraulic and thermostatic regulation of the TPC-M controller. The flow-controlled part allows primary and secondary side flow through the heat exchanger, only when hot water is tapped and blocks the flow immediately after completion of the tapping process. The thermostatic part controls the do­mestic hot water temperature. The TPC - M controller with integrated differential pressure controller also compensates for flunctuating flow temperatures and differential pres­sures and thereby ensures a constant domestic hot water temperature at all times. For registration of the cold water con­sumption the EvoFlat
TM
FSS flat station is equipped with a fitting piece for mounting of a cold water meter in the DCW inlet.
Construction
All pipes are made of stainless steel. The connections are made by a newly designed click connection. Compared to conventional stations with screw connections, this new connection technology does not re­quire retightening during assembly.
Insulation
The EvoFlatTM FSS flat station is built up on an EPP insulated back plate as well as a front insulation cabinet, enabling the customer to have a fully insulated substation, thus ensuring reduced heat losses and excellent operating economy.
www.danfoss.com
44
105,4
D
C
B
A
87
6
5
4
3
2
CIRCUIT DIAGRAM - EXAMPLE
DHW
DCW
Outlet
DCW
Inlet
DH
Supply
DH
Return
38
59
24
27
Design specifications:
Nominal pressure: PN 10 Max. supply temperature: 95 °C DCW static pressure: P Brazing material (HEX): Copper / Stainless steel
= 1,5 bar
min
Weight excl. cover: 10 kg
Insulation: EPP λ 0,039
2
575
23 5
2 Plate heat exchanger Danfoss XB06H -1 5 Strainer 3/4” N/ N mv=0,6 mm 23 Sensor pocket
M10×1
24 Fitting piece for energy meter 3/4” x 110 mm 27 Temperature sensor DHW 38 Hot Water Controller TPC-M 40 Summer-Bypass 59 Fitting piece for DCW meter: 3/4” × 110 mm
40
HE Supply
HE Return
Connections:
1. Domestic cold water (DCW) inlet
2. Domestic hot water (DHW)
3. Domestic cold water (DCW) outlet
4. District heating (DH) supply
5. District heating (DH) return
6. Heating (HE) supply
7. Heating (HE) return
Electrical supply: 230 V AC
Dimensions (mm):
With connections: H 575 × W 545 × D 150* * Depth incl. mounting plate
Connections sizes:
G ¾“ IT (int. thread)
DHW: CAPACITY EXAMPLES 10/50°C
Temperature
primary
Supply/Return
[°C]
Pressure loss
37 65/21 23 730 13.3 43 65/22 40 850 15.3 45 65/20 22 867 16.1 49 65/21 30 950 17.5 55 65/16 27 950 19.4 38 55/21 27 950 13.6 51 65/19 28 950 18.3 34 55/24 28 950 12.5
Unit typ e
HEX
XB06H-1 26 Cu/E (Type 1)
XB06H-1 40 Cu/E (Type 2)
XB06H+ 60 Cu (Type 3)
XB06H-1 56 E (Type 3)
* Energy meter not incl.
DHW
capacity
[[kW]
Primary
[*kp a]
112 65 65 65 65 65 65
545
Flow rate Primary*
[l/h]
Tap load
[l/min.]
* * Energy meter and DHW heating not incl.
Optionen:
• Room thermostat
• Actuator for zone valve
• Mounting rail for wall mounted variant
• Recess box for built-in variant incl. mounting rail
HEATING: CAPACITY EXAMPLES
Heating capacity
[kW]
10 20 3 430 10 30 1 287 10 40 1 215 15 20 8 645 15 30 3 430 15 40 2 323
Heating
circuit Δt
[°C]
Total pressure loss
primary* *
[kPa]
Flow rate
primary
[l/h]
© Danfoss | DHS-SMDT/PL | 2021 .02
AM180986466241en-020302