Fact sheet
EvoFlatTM FSS fully insulated
Flat station with integrated water heater for apartments, single- and multi-family houses
FEATURES AND BENEFITS
• Flat station for direct heating and DHW
heating based on flow principle
• Innovative, energy-saving controller
TCP-M in combination with high
performance heat exchanger for ondemand water heating
• Capacity: 15 kW HE, 55 kW DHW
• Minimum space required for installation
• Built-in or wall-mounted variant
• Pipes and plate heat exchanger made of
stainless steel
• No retightening of internal connections
required, due to newly designed click
connection,
• Constant DHW temperature even at
fluctuating flow temperatures or
differential pressures
• Minimized risk of lime scale and bacteria
formation
Application
Die EvoFlatTM FSS is a compact and simple
to operate flat station. Especially suitable
for two-pipe systems in residential buildings, which are supplied from a secondary connected district heating system, a
block heating system, a centrally located
boiler system (oil, gas or biomass, as well
as for CHP systems. The EvoFlat FSS
TM
is
available as built-in variant with a recess
box or as mount-on-wall variant with
cover.
Primary side (DH)
The flat station is prefabricated with interconnecting components such as a differential pressure controller (integrated
in main temperature controller TPC-M),
strainer, sensor pockets and fitting piece
for insertion of a heat meter.
Heating (HE)
The self-acting temperature controller
TPC - M with integrated differential pressure controller sets the optimum operating conditions for heating and DHW. In
order to enable a time dependent temperature control program, a zone valve
with actuator is included and can be
connected to a room thermostat as an
option.
Domestic hot water (DHW)
The domestic hot water is prepared in
the heat exchanger based on the flow
principle and the temperature is regulated by the self-acting controller with
integrated differential pressure controller - the TPC-M.
Supreme ease of operation is obtained via the combined hydraulic and
thermostatic regulation of the TPC-M
controller. The flow-controlled part
allows primary and secondary side
flow through the heat exchanger, only
when hot water is tapped and blocks
the flow immediately after completion
of the tapping process.
The thermostatic part controls the domestic hot water temperature.
The TPC - M controller with integrated
differential pressure controller also
compensates for flunctuating flow
temperatures and differential pressures and thereby ensures a constant
domestic hot water temperature at all
times.
For registration of the cold water consumption the EvoFlat
TM
FSS flat station
is equipped with a fitting piece for
mounting of a cold water meter in the
DCW inlet.
Construction
All pipes are made of stainless steel.
The connections are made by a newly
designed click connection.
Compared to conventional stations
with screw connections, this new
connection technology does not require retightening during assembly.
Insulation
The EvoFlatTM FSS flat station is built
up on an EPP insulated back plate
as well as a front insulation cabinet,
enabling the customer to have a fully
insulated substation, thus ensuring
reduced heat losses and excellent
operating economy.
www.danfoss.com

44
105,4
D
C
B
A
87
6
5
4
3
2
CIRCUIT DIAGRAM - EXAMPLE
DHW
DCW
Outlet
DCW
Inlet
DH
Supply
DH
Return
38
59
24
27
Design specifications:
Nominal pressure: PN 10
Max. supply temperature: 95 °C
DCW static pressure: P
Brazing material (HEX): Copper / Stainless steel
= 1,5 bar
min
Weight excl. cover: 10 kg
Insulation: EPP λ 0,039
2
575
23 5
2 Plate heat exchanger Danfoss XB06H -1
5 Strainer 3/4” N/ N mv=0,6 mm
23 Sensor pocket
M10×1
24 Fitting piece for energy meter 3/4” x 110 mm
27 Temperature sensor DHW
38 Hot Water Controller TPC-M
40 Summer-Bypass
59 Fitting piece for DCW meter: 3/4” × 110 mm
40
HE
Supply
HE
Return
Connections:
1. Domestic cold water (DCW) inlet
2. Domestic hot water (DHW)
3. Domestic cold water (DCW) outlet
4. District heating (DH) supply
5. District heating (DH) return
6. Heating (HE) supply
7. Heating (HE) return
Electrical supply: 230 V AC
Dimensions (mm):
With connections: H 575 × W 545 × D 150*
* Depth incl. mounting plate
Connections sizes:
G ¾“ IT (int. thread)
DHW: CAPACITY EXAMPLES 10/50°C
Temperature
primary
Supply/Return
[°C]
Pressure loss
37 65/21 23 730 13.3
43 65/22 40 850 15.3
45 65/20 22 867 16.1
49 65/21 30 950 17.5
55 65/16 27 950 19.4
38 55/21 27 950 13.6
51 65/19 28 950 18.3
34 55/24 28 950 12.5
Unit typ e
HEX
XB06H-1 26 Cu/E (Type 1)
XB06H-1 40 Cu/E (Type 2)
XB06H+ 60 Cu (Type 3)
XB06H-1 56 E (Type 3)
* Energy meter not incl.
DHW
capacity
[[kW]
Primary
[*kp a]
112 65 65 65 65 65 65
545
Flow rate
Primary*
[l/h]
Tap load
[l/min.]
* * Energy meter and DHW heating not incl.
Optionen:
• Room thermostat
• Actuator for zone valve
• Mounting rail for wall mounted variant
• Recess box for built-in variant incl.
mounting rail
HEATING: CAPACITY EXAMPLES
Heating
capacity
[kW]
10 20 3 430
10 30 1 287
10 40 1 215
15 20 8 645
15 30 3 430
15 40 2 323
Heating
circuit Δt
[°C]
Total pressure loss
primary* *
[kPa]
Flow rate
primary
[l/h]
© Danfoss | DHS-SMDT/PL | 2021 .02
AM180986466241en-020302