Danfoss Everis 4250, Everis 4270 Installation guide

INSTRUCTIONS
Thermostatic sensor type RTS-K EverisTM 4250 &4270
Application
Operation
013R9391
Setting the temperature
Thermostatic sensor type RTS-K EverisTM 4250 and 4270 can be fitted without adapter on valve radiators
The thermostatic sensor with a liquid-filled bellows system provides proportional regulation. The sensor is actuated by ambient temperature. The calibrated pressure in the bellows corresponds to the tempera­ture of the charge. This pressure is balanced by the force of a regulating spring. On a rise in ambient temperature the liquid pressure
The required room temperature is set by turning the setting dial. The temperature scales show the correlation between scale values and the room temperature. The temperature values stated are for guidance only as the obtained room temperature will often be influenced by installation conditions.
Room
temporarily
not in use
Cellar Corridor,
(compact radiators) from the manufacturers: Diatherm, Kermi, Korado, Purmo, Rettig, Radson.
rises in the bellows, moving the valve cone towards the closed position until equilibrium exists between the bellows and the spring. On a drop in ambient temperature the liquid pressure falls, allowing the bellows to contract and the valve cone to move towards the open position until a state of equilibrium is re-established.
The temperature scales are stated according to European standards at Xp = 2 °C. This means that the radiator thermostats close at a sensor temperature which is 2 °C higher than stated on the temperature scales.
Different temperatures are recommended depending on the purpose of the room. The illustration shows the most frequently used.
bedroom
Living room,
kitchen
Bath room
013R9391
Mounting
Adjusting temperature control range
The sensor is supplied to connect valves with M 30 x 1.5 connection. During mounting the setting dial should be in position 5. The nut should be tightened with an open-end 32 mm spanner.
Setting the upper limit
e.g. 3 as the highest possible temperature selection:
1. Turn the handle to max. position.
2. Keep the limiter tab to the right of the scale pointer pressed down with a small screwdriver.
3. Turn the handle to 3 on scale and release the tab.
2)1)
Setting the lower limit
e.g. 2 as the lowest possible temperature selection:
1. Turn the head to. min. position.
2. Keep the limiter tab to the left of the scale pointer pressed down with a small screwdriver.
3. Turn the head to 2 and release the tab.
DKCD VIVFK102 03/2004
Loading...