Data Sheet
Solenoid valve
Type EV220BW and EV228BW
Indirect servo operated valves for drinking water
Solenoid valve range with drinking water
approvals
• For water supply
• Houses and large apartments
◦ Kitchen and bathrooms
• Commercial buildings
• Industrial buildings
• Zoning
• Laundry
• Diswashing
• Main inlet valves
• Machines and food processing
Features
• Clip-on coil
• Ambient temperature: Up to 70 °C
• Coil enclosure: Up to IP67
• Water hammer damped
• Built-in lter
• Body material in Eco brass (Lead free < 0,1 %)
or Stainless steel
• New generation EPDM sealings
recommended for drinking water
AI266333732850en-000501

Dierential pressure range [bar]
Solenoid valve, Types EV220BW and EV228BW
1 Portfolio overview
Table 1: Portfolio overview
© Danfoss | Climate Solutions | 2021.06 AI266333732850en-000501 | 2

Solenoid valve, Types EV220BW and EV228BW
2 Functions
2.1 Function, NC
Coil voltage disconnected (closed)
When the voltage is disconnected, the valve plate (3) is pressed down against the pilot orice (4) by the armature
spring (2). The pressure across the diaphragm (5) is built up via the equalizing orice (7). The diaphragm closes the
main orice (6) as soon as the pressure across the diaphragm is equivalent to the inlet pressure. The valve will be
closed for as long as the voltage to the coil is disconnected.
Coil voltage connected (open)
When voltage is applied to the coil (1), the pilot orice (4) is opened. As the pilot orice is larger than the equalizing
orice (7), the pressure across the diaphragm (5) drops and therefore it is lifted clear of the main orice (6). The valve
is now open for unimpeded ow and will be open for as long as the minimum dierential pressure across the valve
is maintained, and for as long as there is voltage to the coil.
Figure 1: Function, NC
2.2 Function, NO
Coil voltage disconnected (open)
When the voltage to the coil (1) is disconnected, the pilot orice (4) is open. As the pilot orice is larger than the
equalizing orice (7), the pressure across the diaphragm (5) drops and therefore it is lifted clear of the main orice
(6). The valve will be open for as long as the minimum dierential pressure across the valve is maintained, and for as
long as the voltage to the coil is disconnected.
Coil voltage connected (closed)
When voltage is applied to the coil, the valve plate (3) is pressed down against the pilot orice (4). The pressure
across the diaphragm (5) is built up via the equalizing orice (7). The diaphragm closes the main orice (6) as soon
as the pressure across the diaphragm is equivalent to the inlet pressure. The valve will be closed for as long as there
is voltage to the coil.
© Danfoss | Climate Solutions | 2021.06 AI266333732850en-000501 | 3

Solenoid valve, Types EV220BW and EV228BW
Figure 2: Function, NO
2.3 Function UN, latching
Figure 3: Open
When (minus) is supplied to the left terminal pin and (plus) to the right (see gure 3), the pilot orice (4) is opened.
As the pilot orice is larger than the equalizing orice (7), the pressure across the diaphragm (5) drops and therefore
it is lifted clear of the main orice (6). The valve is now open for ow and will stay open as long as the minimum
dierential pressure across the valve is maintained, until the poles are switched back (see Figure 4: closed)
Figure 4: closed
Switching poles
When (plus) is supplied to the left terminal pin and (minus) to the right (see gure 4), the valve plate is pressed
down against the pilot orice (4) by the armature spring (2). The pressure across the diaphragm (5) is built up via the
equalizing orice (7). The diaphragm closes the main orice (6) as soon as the pressure across the diaphragm is
equivalent to the inlet pressure. The valve will stay closed, until the poles are switched (see Figure 3: Open)
© Danfoss | Climate Solutions | 2021.06 AI266333732850en-000501 | 4

Solenoid valve, Types EV220BW and EV228BW
Figure 5: Function UN, latching
© Danfoss | Climate Solutions | 2021.06 AI266333732850en-000501 | 5