Installation guide
Solenoid valve
Type EV220B 65 - 100
016R9522
016R9522
© Danfoss | DCS (sb) | 2020.04
AN335627203023en-000101 | 1
The product contains
1
2
3
4
EV220B 65 EV220B 80 & 10 0
8 pcs 2 pcs 1 pcs 1 pcs
*Only in ca se of water hammer r isk, change the eq ualizing orifice . See page 6 for inst allation guide.
Accessories
Cable plug
Coil BB/BE/BG/BY
Flange set
Identification
Example:
Week 06 / year : 2020
EV220B 65 - 100
Small box
Manual override kit
1 pcs*
NO. Part
1 Water supply
2 Filter
3 Bal l valve, water suppl y
4 Solenoid valve
5 Ball , test reservio r
6 Test reservior
7 Ball valve, application
8 Application
Type
EV220B 65
EV220B 80
EV220B 100
L
[mm]
320 224 300 46 66 185 85 185 24 65
370 265 350 46 66 200 93 2 15 34 80
430 315 400 46 66 220 103 240 44 100
L
1
[mm]
Required
min. L2*
(mm)
B1 [mm] Coil type
BB/BE BG
70
øD
[mm]
7
8
5
6
H1
[mm]
H2
[mm]
Weight
without
coil
[kg]
Required min.
inside tube
diameter
d** (mm)
100
min. L2min. L2
2
H
Recommendations
Water quality
Hardness 6 - 18 °dH
OFF
≥ 50 mesh (≤ 297 microns)
Conduct ivity 50 - 800 µS/cm t
Media tem p. < 25°C
© Danfoss | DCS (sb) | 2020.04 © Danfoss | DCS (sb) | 2020.04
Maintenance
every 6 to 12 months
* Avoid closin g problems cause d by turbulent flow i t is required to have a st raight tube on bot h sides of the valve.
** Requi red to keep same tub e size for entire app lication, same o r bigger inside di ameter as valve ori fice 65 / 80 / 100 mm.
AN335627203023en-000101 | 2 AN335627203023en-000101 | 3
d
D
1
H
L1
L