Danfoss EV220B, EV220BW Data sheet

Data Sheet
Solenoid valve Type EV220B and EV220BW
EV220B 6-22 and EV220BW 12 NO:
General purpose valves for water, brine, air and oil applications
EV220B 6 - EV220B 22 and EV220BW 12 NO is a direct servo-operated 2/2-way solenoid valve program with connections from 1/4” to 1”. This program is especially for OEM applications demanding a robust solution and moderate ow rates.
Features
• For water, oil, compressed air and similar neutral media
• Clip on coil
• Ambient temperature: Up to 80 °C
• Coil enclosure: Up to IP67
AI236986441887en-001203
Features
EV220B 6 - 22
EV220B 6-10
EV220B 6-12
EV220BW 12
Body material
Brass
DZR Brass
Brass
DZR brass
DN [mm]
6 - 22
6 - 10
6 - 12
12
Connection
G1/4'' - G1''
G3/8'' - G1/2''
G3/8'' - G1/2''
G1/2''
Sealing material
EPDM, FKM
EPDM
EPDM, FKM
EPDM
Function
NCNCNO
NO
Kv [m3/h]
0.7 - 6
0.7 - 1.5
0.7 - 2.5
2.5
Dierential pressure range [bar]
0.1 - 20
0.1 - 20
0.1 - 10
0.3 - 10
Temperature range [°C]
-30 - 100
-30 - 100
-30 - 100
-30 - 100
Solenoid valve, Type EV220B and EV220BW
1 Portfolio overview
Table 1: Portfolio overview
© Danfoss | Climate Solutions | 2022.03 AI236986441887en-001203 | 2
1.2.3.4.5.6.7.8.Armature spring
Armature
Valve plate
Equalizing orice
Main orice
Pilot orice
Diaphragm
Coil
Solenoid valve, Type EV220B and EV220BW
2 Function
2.1 Function NC
Coil voltage disconnected (closed)
When the supply voltage to the coil (8) is disconnected, the valve plate (3) is pressed down against the pilot orice (6) by the armature spring (1). The pressure across the diaphragm (7) is built up via the equalizing orice (4). The diaphragm closes the main orice (5) as soon as the pressure across the diaphragm is equivalent to the inlet pressure. The valve will be closed for as long as the voltage to the coil is disconnected.
Coil voltage connected (open)
When voltage is applied to the coil, the pilot orice (6) is opened. As the pilot orice is larger than the equalizing orice (4), the pressure across the diaphragm (7) drops and therefore it is lifted clear of the main orice (5). The valve
is now open and will be open for as long as the minimum dierential pressure across the valve is maintained, and for as long as there is voltage to the coil.
Figure 1: Function NC
2.2 Function NO
Coil voltage disconnected (open)
When the voltage to the coil (8) is disconnected, the pilot orice (6) is open. As the pilot orice is larger than the equalizing orice (4), the pressure across the diaphragm (7) drops and therefore it is lifted clear of the main orice (5). The valve will be open for as long as the minimum dierential pressure across the valve is maintained, and for as long as the voltage to the coil is disconnected.
Coil voltage connected (closed)
When voltage is applied to the coil, the valve plate (3) is pressed down against the pilot orice (6). The pressure across the diaphragm (7) is built up via the equalizing orice (4). The diaphragm closes the main orice (5) as soon as the pressure across the diaphragm is equivalent to the inlet pressure. The valve will be closed for as long as there is voltage to the coil.
© Danfoss | Climate Solutions | 2022.03 AI236986441887en-001203 | 3
1 2
3 4
5
8
6 7
1.2.3.4.5.6.7.8.Armature
Opening spring
Valve plate
Equalizing orice
Main orice
Pilot orice
Diaphragm
Coil
Solenoid valve, Type EV220B and EV220BW
Figure 2: Function NO
© Danfoss | Climate Solutions | 2022.03 AI236986441887en-001203 | 4
Loading...