Data Sheet
Solenoid valve
Type EV210B and EV210BW
Direct-operated 2/2-way solenoid valves for universal use.
EV210B and EV210BW covers a wide range of direct-operated 2/2-way solenoid valves for universal use.
EV210B and EV210BW are a very robust valves program with high performance and can be used in all kind of tough working conditions in demanding industrial applications such as control and closage.
Features and versions:
• For water, oil, compressed air and similar neutral media
• Clip on coil
• Ambient temperature: up to 80 °C
• Coil enclosure : up to IP67
• The valves can be used for vacuum
• EV210B brass version for water, oil, compressed air and similar neutral media
• EV210B stainless steel version for neutral and aggressive liquids and gasses
• EV210BW brass and Stainless steel versions, EPDM seal and WRAS approved for drinking water
AI200686429133en-001101
Solenoid valve, type EV210B and EV210BW
1 Portfolio overview
Table 1: Portfolio overview
Features |
EV210B |
EV210BW |
EV210B |
EV210BW |
|
|
|
|
|
Body material |
Brass |
Brass |
Stainless steel |
Stainless steel |
|
|
|
|
|
DN [mm] |
1.5 – 25 |
1.5-4.5 |
2-3 |
1.5-4.5 |
|
|
|
|
|
Connection |
G 1⁄8 – G 1 |
G1⁄8-G3⁄8 |
G1⁄8-G1⁄4 |
G1⁄4 |
Sealing material |
EPDM, FKM |
EPDM |
EPDM |
EPDM |
|
|
|
|
|
Function |
NC, NO |
NC |
NC |
NC |
|
|
|
|
|
Kv [m3/h] |
0.08-8.00 |
0.08-0.55 |
0.15-0.30 |
0.08-0.55 |
Di€erential pressure range [bar] |
0 – 30 |
0-16 |
0-30 |
0-16 |
|
|
|
|
|
Temperature range [°C] |
-30 – 120 |
-30-90 |
-30-120 |
-30-90 |
|
|
|
|
|
© Danfoss | Climate Solutions | 2021.06 |
AI200686429133en-001101 | 2 |
Solenoid valve, type EV210B and EV210BW
2 Functions
2.1 Function NC
Coil voltage disconnected (closed):
When the voltage to the coil (5) is disconnected, the armature (2) with the valve plate (3) is pressed down against the valve orifice (4) by the closing spring (1) and the medium,s pressure.
The valve will be closed for as long as the voltage to the coil is disconnected.
Coil voltage connected (open):
When voltage is applied to the coil(5), the armature (2) with the valve plate (3) is lifted clear of the valve orifice (4).
The valve is now open for unimpeded flow and will be open for as long as there is voltage to the coil.
Figure 1: Function NC
|
1 |
|
2 |
5 |
3 |
|
|
4 |
|
2.2 Function NO |
|
1Closing spring
2Armature
3Valve plate
4Valve orifice
5Coil
Coil voltage connected (open):
When the voltage to the coil(8) is disconnected, the valve orifice (5) is open, the opening spring (2) lifting the spindle (3) with the valve plate (4) clear of the orifice.
The valve will be open for as long as the supply voltage to the coil is disconnected.
Coil voltage disconnected (closed):
When voltage is applied to the coil (8), the magnetic field draws the valve,s armature (1) down to touch the fixed base(7). The spindle (3) with the valve plate (4) is now pressed down against the valve orifice (5) by the closing spring (6).
The valve will be closed for as long as there is voltage to the coil.
© Danfoss | Climate Solutions | 2021.06 |
AI200686429133en-001101 | 3 |
Solenoid valve, type EV210B and EV210BW
Figure 2: Function NO
|
1 |
|
2 |
|
3 |
|
4 |
8 |
5 |
|
|
7 |
|
6 |
|
1Armature
2Opening spring
3Spindle
4Valve plate
5Valve orifice
6Closing spring
7Fixed base
8Coil
© Danfoss | Climate Solutions | 2021.06 |
AI200686429133en-001101 | 4 |
Solenoid valve, type EV210B and EV210BW
3 Applications
It is recommended to use a filter in front of the valve. Recommended filter 50 mesh (297 microns).
Figure 3: Filter
In water applications, exercise the valves at least once every 24 hours, meaning change the state of the valve. The valve exercise will minimize the risk of the valve sticking due to calcium carbonate, zinc or iron oxide build-up.
Figure 4: Exercise: Valve on/off
ON
OFF
24h
To minimize scaling, and corrosion attack it is recommended that the water passing the valve have the following values:
•Hardness 6 - 18 °dH to avoid scaling (chalk / lime stone build up)
•Conductivity 50 – 800 µS/cm to avoid brass dezincification and corrosion
•Above 25 °C media temperature avoid stagnant water inside the valve to avoid dezincification and corrosion attack
© Danfoss | Climate Solutions | 2021.06 |
AI200686429133en-001101 | 5 |