Danfoss ETS 5M Installation guide

Installation guide
089
90o 90o
90o 90o
Electric expansion valve Type ETS 5M
Refrigerants R410A, R22, R32, R290, R454C, R515B, R1234ze, R452B, R1234yf, R452A, R454B, R454A, R455A, R449A, R407C, R134a, R407H, R513A, R449B, R404A, R448A, R463A
034R9819
Safety notes for flammable refrigerants (R454C, R454A, R1234ze, R290, R32, R452B, R454B, R455A, R1234yf)
- This product is validated in accordance to ATEX, EN 378, ISO 5149, ASHRAE 15, IEC 60335-2-x or equivalent standards.
- Ignition risk is evaluated in accordance to ISO 5149 and IEC 60335.
- See safety note below.
Safety notes:
- The product can be applied on systems with R454C, R454A, R1234ze, R290, R32, R452B, R454B, R455A, R1234yf as the working fluid.
- For countries where safety standards are not an indispensable part of the safety system Danfoss recommend the installer to get a third party approval of the system containing flammable refrigerant.
- Note, please follow specific selection criteria stated in the datasheet for these particular refrigerants.
- The valve must only be used in closed circuit refrigeration system, where no oxygen is present acc. EN 378, ISO 5149 ASHRAE 15 or IEC 60335-2-x or equivalent standards.
Warning!
Max. working pressure
PS / MWP: 4.55 MPa / 45.5 barg / 660 psig
Refrigerant temperature
t
: -30 °C / -22 °F, t
Min.
Allowable ambient temperature
-30 °C / -22 °F - 60 °C / 140 °F
Stepper motor type
Unipolar
Nominal voltage
12 V DC
Mounting Angle
1
: 70 °C /158 °F
Max.
Phase current
240 mA
034R9819
Resistance
50 Ω
Do not connect directly to AC / DC power source. Connect valve to appropriate controller / driver only. Do not operate valve while assembling or disassembling.
Імпортер:ТОВ з іі "Данфосс ТОВ" 04080, Київ 80, п/с 168, Україна
© Danfoss | Climate Soutions | 2022.01
AN304333192445en-000601 | 1
50
50
Open position
2
1
E (2 : 1)
2 3 4
Brazing option 1
Brazing option 2
Always open valve to overdrive before brazing using manual coil.
Assembling
ETS 5M manual coil: Code no. 034G3803
Open
Connection
5
JST XHP-5 JST XHP-6
Black
Orange
Brown
2 | AN304333192445en-000601
Min
Ag 5%
3
1
H₂O
Danfoss
61L06.12
Ag 5%
Min
N
2
3
N
2
N gas from opposite side of soldering point.
Table:1 Stepper motor open and close sequence
Yellow ( A1) Orange (A2) Br own (B1) Black (B2) Red (Com)
ON OFF OFF OFF 0
ON OFF ON OFF 0
50
50
50
Red
Yellow
5
5
OFF OFF ON OFF 0
OFF ON ON OFF 0
Valve Opening
OFF ON OFF OFF 0
Valve Closing
OFF ON OFF ON 0
OFF OFF OFF ON 0
ON OFF OFF ON 0
5
5
A1
COM
x
1: Brown
A2
B1
B2
Plug Coding
JST XHP-6: 1 2 3 4 5 6 JST XHP-5: 1 2 3 4 5
Color coding
JST 5/6
5/6: RED - Common
-/5: No wire ­4/4: Yellow - Coil A1 3/3: Black - Coil B2
2/2: Orange - Coil A2 1/1: Brown - Coil B1
Red
Black
Yellow
Brown
50
50
50
5
5
5
5
Orange
© Danfoss | Climate Solutions | 2022.01