Fact sheet
Termix BV
Instantaneous water heater for large apartment houses, sports arenas and schools
Application
The Termix BV substation is an
instantaneous water heater featuring superb heat extraction
and high performance. The substation is delivered with thermostatic or automatic controls.
The Termix BV is suitable for large
apartment houses, sports arenas and
schools, where large amounts of hot
water are needed. The hot water systems are available in 7 different sizes
with an output from 77-265 kW. The
Termix BV unit is supplied with PU insulated heat exchangers.
Domestic hot water (DHW)
The domestic hot water is prepared
in a plate heat exchanger and the
temperature is regulated with thermostatic or automatic controls.
The thermostatic solution is regulated with self-acting thermostatic
control valves. The substations with
high output are controlled with two
valves connected in cascade in order
to control both small and
large demands for hot water in an efficient manner.
The Termix BV can also be mounted
with automatic controls. There is no
additional pressure loss on the secondary side of the heat exchanger
with a thermostatic or automatic
control valve. Therefore this type of
regulation can be used by low pressure in the cold water mains.
Domestic hot water circulation
The Termix BV substation is supplied
with connections for DHW circulation including circulation pump and
a non-return valve as a standard.
Options
The substation can be supplied with
a safety valve and a thermostatic circulation valve.
Construction
All pipes are made of stainless
steel. The connections are made
by nuts and gaskets. The Termix BV
substation can be delivered with a
white-lacquered steel cover in modern design.
FEATURES AND BENEFITS
• Instantaneous water heater
• DHW regulation with thermostatic
or automatic controls
• Capacity: 77-265 kW DHW
• DHW in sufficient quantity
• Operates independent of differential
pressure and flow temperature
• Minimum space required
for installation
• Pipes and plate heat exchanger
made of stainless steel
• Minimized risk of lime scale
and bacteria formation
www.danfoss.com
CIRCUIT DIAGRAM - EXAMPLE
DH
supply
DH
return
Diagram for Termix BV type 4-8
Technical parameters:
Nominal pressure: PN 16
DH supply temperature: Tmax= 120 °C
DCW static pressure: Pmin = 0,5 bar
Brazing material (HEX): Copper
Weight incl. cover: 20-40 kg (incl. packing)
Cover: White-lacquered steel sheet
Dimensions (mm):
Without cover:
H 660 x W 510 x D 240 (type 2-5)
H 1000 x W 800 x D 340 (type 6-8)
With cover:
H 800 x W 540 x D 360 (type 2-5)
H 1000 x W 950 x D 525 (type 6-8)
Connections:
1. District heating (DH) supply
2. District heating (DH) return
3. Circulation
4. Domestic hot water (DHW)
5. Domestic cold water (DCW)
Type 2-5
Type 6-8
DHW
B Heat exchanger DHW
2 Non-return valve
7 Thermostatic valve
11 Domestic hot water pump
18 Thermometer
DCW
Circ.
Connections sizes:
DH + DCW + DHW: G 1” (int. thread)
Circulation: G ¾” (int. thread)
Options:
• White-lacquered steel cover
• Safety valve and non-return valve (10 bar)
• Thermostatic circulation set
Wall
Wall
Seen from above
DHW: CAPACITY EXAMPLES
Substation
type
BL-2E-CP 70 200 10
BL-3E-CP 82 300 15
BL-4E-CP 113 600 25
BL-5E-CP 126 800 30
BL-6E-CP 157 800 35
BL-7E-CP 186 1000 40
BL-8E-CP 222 1000 45
* Flow per shower: 10 l/min - DHW temp. at tap: 40 °C
Charging
capacity
[kW]
Recommended
size of tank
[litre]
Number of showers*
Danfoss Randall Ltd . • Unit A4, Centre Point Business Park, Oak Road • Dublin 12 • Ireland
Tel.: +353 1800 930 243 • Fax: +353 1800 556 691 • districtheating@danfoss.com • www.dh.danfoss.com
© Danfoss | DHS-SRMT/ PL | 2016. 02