Data sheet |
ESBE Series VTA 572 |
|
|
Thermostatic Diverting Valve |
|
|
|
|
Technical Data:
Ordering
Information:
Flow Pattern:
Applications and Features:
The VTA 572 is a 3-way thermostatic valve for either mixing or diverting applications within hydronic closed loop systems. This particular non-electric thermostatic controller has a low temperature range providing an ideal control for a thermostatic changeover application, while providing a cost effective means to meet application demands. The VTA572 is available in two temperature ranges:
• 50 - 86°F (0 - 30°C)
• 68 - 109°F (20 - 43°C)
Working Pressure |
|
|
|
|
|
145 psi (10 bar) |
||
Maximum Differential Pressure |
|
|
14.5 psi (1 bar) |
|||||
|
|
|
|
|
|
|
|
|
Minimum flow rate |
|
|
|
|
2.4 gpm |
|||
|
|
|
|
|
|
|||
Allowable Anti-freeze Additive |
|
Glycol ≤50% mixture |
||||||
Maximum Fluid Temperature |
|
|
|
(100C) |
||||
|
|
|
|
|
|
|
||
Outlet Temperature Variation |
|
|
±4.5°F (±2.5°C) |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Code no. |
|
Cv |
|
|
Description |
|
Connection |
|
|
|
|
|
|
|
|
||
31700100 |
|
5.2 |
|
3/4” Union valve body, 50-86°F (0-30°C) |
|
G1 external thread |
||
|
|
|
|
|
|
|
||
31700200 |
|
5.2 |
|
3/4” Union valve body, 68-109°F (20-43°C) |
|
G1 external thread |
||
|
|
|
|
|
|
|
|
|
Required Tailpieces Kit |
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
Code no. |
|
|
|
|
Description |
|
|
|
|
|
|
|
|
|
|||
065B8892 |
|
3/4” Union x 3/4” Female Solder |
|
|
|
|||
065B8899 |
|
3/4” Union x 1” Female Solder |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
As a mixing valve supply through the VTA572 |
||
|
|
|
|
|
|
will enter from the left, mix with return water |
||
|
|
|
|
|
|
entering from the bottom and leave as mixed |
||
|
|
|
|
|
|
water from the right. |
||
Supply |
|
|
|
Mixed |
In a diverting application, water will enter from |
|||
|
|
|
|
|
||||
|
|
|
|
|
|
the right (Mixed) and depending on the set and |
||
|
|
|
|
|
|
sensed temperature will exit the valve as follows: |
||
|
|
|
|
|
|
1) Water temperature higher than set, flow will |
||
|
|
|
|
|
|
exit the Return port |
||
|
|
|
|
|
|
2) Water temperature is lower than set, flow will |
||
|
|
Return |
|
|
exit Supply port |
VD.KI.P1.22 © Danfoss 3/2013 |
1 |