ERC 21X is a smart multipurpose refrigeration controller
designed to fulfill today’s requirement of commercial
refrigeration applications. This controller is suitable for high,
medium and low temperature applications with natural,
electrical and hot gas defrost compatibilities.
Typical applications include Glass door merchandisers,
commercial fridges and freezers, cold rooms and various
other commercial refrigeration applications.
1.2| General Description
ERC21X controller comes with four push buttons, a big
display, easy and intuitive menu structure and pre-defined
applications ensure ease of use. Controller is loaded
with energy efficiency features like smart evaporator fan
management, day/night mode and defrosts on demand
features.
High Effect 16 A relay enable direct connection of heavy
loads without use of intermediate relay: up to 2 hp
compressors depending on its power factor and motor
efficiency (greater than 0.65 for 230 V and greater than
0.85 for 115 V).
Safe operation of the unit is ensured through voltage
protection and high condensation temperature protection
features.
Three version of ERC 21X is available in both 230 V / 50/60 Hz and 115 V / 60 Hz.
– ERC 211: single relay output for refrigeration and heating applications.– ERC 213: three relays outputs for ventilated refrigeration applications.– ERC 214: four relays outputs for ventilated refrigeration applications.
1.3.1| ERC 211
ERC 211 has one relay output and two inputs
(1 analogue, 1 analogue/digital).
This controller can be used for either cooling or heating
applications.
Outputs:
– Relay 1: compressor/solenoid valve control or simple
heater in case of heating application Inputs.
Inputs:
– Input1: cabinet/control sensor (Sair).
– Input 2: condenser sensor or digital inputs which can
be configured for various functions as mentioned under
menu code o02.
Sair
DO1
Sc
1.3.2| ERC 213
ERC 213 has three relays outputs and four inputs
(2 analogues, 1 analogue/digital, 1 digital) for cooling
applications.
Outputs:
– Relay 1: compressor/solenoid valve control.
– Relay 2: can be configured either defrost or external alarm.
– Relay 3: fan control.
Inputs:
– Input 1: cabinet/control sensor (Sair).
– Input 2: defrost sensor (S5).
– Input 3 : condenser sensor (Sc) or digital input which can
be configured to various functions as mentioned under
menu code “o02”.
– Input 4: digital input which can be configured to various
functions as mentioned under menu code “o37”
1.3.3| ERC 214
ERC 214 has four relays outputs and four inputs (2 analogue,
1 analogue/digital, 1 digital) for cooling applications.
Outputs:
– Relay 1: compressor/solenoid valve control.
– Relay 2: defrost control.
– Relay 3: fan control.
– Relay 4 : this can be configured for either light or external
alarm.
Inputs:
– Input 1: cabinet/control sensor (Sair).
– Input 2: defrost sensor (S5).
– Input 3 : condenser sensor (Sc) or digital input which can
be configured to various functions as metioned under
menu code “o02”.
– Input4: digital input which can be configured for various
Protection against high and low voltage by limiting the
compressor operation within specified voltage limits.
Whenever the supply voltage goes beyond the defined
voltage protection limits controller will shut the compressor
OFF and flashes alarm on the display.
It will restore the operation when the voltage falls under the
operating range respecting minimum stop time.
2.2| Compressor protection
High voltage limit
Low voltage cut-in
limit (compressor start)
Low voltage cut-out
limit (alarm and
compressor stop)
Parameters for Minimum ON and OFF time, protect the
compressor by short cycling/sudden switching ON and OFF
by defining minimum ON and OFF time.
2.3| Compressor protection against
high condensing temperature
If the condenser is blocking up with dirt and thereby reaches
a too high condensing temperature, controller will give
the user early warning through condenser alarm and if
temperature rises further it will switch the compressor OFF.
If the temperature measured by the condenser sensor (Sc)
is reaching the set ”pre alarm limit” a alarm is raised, but no
further action is taken.
This is used to indicate to the user that something is wrong
with the condenser. Often the reason is that that the air flow
to the condenser is restricted (dirt) or because the condenser
fan is broken.
The alarm will reset if the condenser temperature drops back
by 5 °C. If the measured condenser temperature continues
to increase and reaches the set “Block limit” the compressor is
stopped and it is restricted from starting again until the alarm
is reset manually.
The purpose of the Predefined applications is to give the user an easy and fast way to configure the controller to a specific
application based on storage temperature (LT, MT, HT), defrost type (none, natural, electrical) and
defrost method (terminated on time or temperature).
When user select specific application based on their requirements, the controller will load a specific set of parameter values
and will hide parameters that are not relevant for the selected application.
Adjustment of the set of parameters value will be still possible at any time.
In addition to pre-defined applications, all controller versions have two standard applications, one with full list of parameters
and another with simplified list of parameters, that allows the user to make their own customized parameter settings
(AP0 and AP5 in case of ERC211 and AP0 and AP6 in case of ERC213 / ERC214).
Pre-defined application table of ERC 211 controller
AppModeDescriptionTemperatureDefrost typeDefrost end
App 0Cooling/
Heating
App 1CoolingMedium temperature without defrost (4 – 20 °C)NoneNone
App 2CoolingMedium temperature with timed natural defrost(2 – 6 °C) NaturalTime
App 3CoolingMedium temperature with natural defrost stop on
No predefined application with simplified list of
parameter
(2 – 6 °C)NaturalAir
temperature
Selection 1 covers applications where a standard cooling thermostat is needed and no defrosts are performed.
Selection 2 covers normal temperature applications with natural defrost with stop on time.
Selection 3 covers normal temperature applications with natural defrost with stop on air temperature.
Selection 4 covers applications where a simple heating thermostat is needed (no defrost).
Selection 5 covers applications where a reduced parameter list is recommended.
Pre-defined application table of ERC 213 controller
AppModeDescriptionTemperatureDefrost typeDefrost end
App 0CoolingNo predefined application
App 1Cooling
App 2Cooling
App 3Cooling
App 4Cooling
App 5Cooling
App 6Cooling
Medium temperature ventilated refrigeration units
with timed natural defrost
Medium temperature ventilated refrigeration units
with timed electrical defrost
Low temperature ventilated refrigeration units with
timed electrical defrost
Medium temperature ventilated refrigeration units
with electrical defrost (by temperature)
Low temperature ventilated refrigeration units with
electrical defrost (by temperature)
No predefined application with simplified list of
parameters
(2 – 6 °C)NaturalTime
(0 – 4 °C)ElectricalTime
(-26 – -20 °C)ElectricalTime
(0 – 4 °C)ElectricalTemperature
(-26 – -20 °C)ElectricalTemperature
Selection 1 covers normal temperature applications with natural defrost with stop on time.
Selection 2 and 3 covers respectively medium and low temperature applications with electrical defrost with stop on time.
Selection 4 and 5 covers respectively medium and low temperature applications with electrical defrost with stop on
defrost sensor “S5”.
Selection 6 covers applications where a reduced parameter list is recommended.
AppModeDescriptionTemperatureDefrost typeDefrost end
App 0CoolingNo predefined application
App 1Cooling
App 2Cooling
App 3Cooling
App 4Cooling
App 5Cooling
App 6Cooling
Medium temperature ventilated refrigeration units
with timed natural defrost
Medium temperature ventilated refrigeration units
with timed electrical defrost
Low temperature ventilated refrigeration units with
timed electrical defrost
Medium temperature ventilated refrigeration units
with electrical defrost (by temperature)
Low temperature ventilated refrigeration units with
electrical defrost (by temperature)
No predefined application with simplified list of
parameters
(2 – 6 °C)NaturalTime
(0 – 4 °C)ElectricalTime
(-26 – -20 °C)ElectricalTime
(0 – 4 °C)ElectricalTemperature
(-26 – -20 °C)ElectricalTemperature
Selection 1 covers normal temperature applications with natural defrost with stop on time.
Selection 2 and 3 covers respectively medium and low temperature applications with electrical defrost with stop on time.
Selection 4 and 5 covers respectively medium and low temperature applications with electrical defrost with stop on
defrost sensor “S5”.
Selection 6 covers applications where a reduced parameter list is recommended.
230 V AC
ERC 214 - APP 1
DI2
DO1
DO3DO4
SairDI1
230 V AC
ERC 214 - APP 2-3
DI2
DO1
DO3DO2DO4
ERC 214 - APP 4-5
SairDI1
230 V AC
DO1
DI2S5
DO3DO2DO4
SairDI1
2.5| Fan pulsating during compressor OFF cycle
This is an energy saving feature. During compressor OFF cycle controller will run the fan with defined duty cycle to maintain
uniform temperature and delay the need of compressor switching ON
This feature records and averages the evaporator temperature recorded during the first three cut out of compressor
immediately after defrost. The controller will constantly follow the evaporator temperature and compare with the above
recorded average temperature. In between two defrosts, If the evaporator temperature goes below the previously recorded
average temperature by “defrost on demand” value “d30”, defrost will be triggered.
– This function can only be used in 1:1 systems.
– This function is disabled when the parameter “defrost on demand” is set to 20.
– Defrost on demand is triggered only if the time since the last defrost session has ended is greater than ¼ of the defrost
interval or 2 hours whichever is lesser.
– Defrost doesn’t start by this method during the following scenarios.
– Pull down mode.
– Night mode.
– Main switch in DI or main switch in Menu is in OFF position.
– Manual control mode.
– Evaporator sensor senses a temperature which is greater than 0 °C.
Power supply115 V AC / 230 V AC 50/60 Hz, galvanic isolated low voltage regulated power supply
Rated powerLess than 0.7 W
Inputs
Allowed sensor types
Sensors included in Kit Solution NTC 10000 Ohm at 25 °C, cable length: 1.5 m
Accuracy
Type of action1B (relay)
Output
DisplayLED display, 3 digits, decimal point and multi-function icons, °C + °F scale
Operating conditions-10 – 55 °C (14 – 131 °F), 90% Rh
Storage conditions-40 – 70 °C (-40 – 158 °F), 90% Rh
Protection
EnvironmentalPollution degree II, non-condensing
Overvoltage category
Resistance to heat and fire
EMC categoryCategory I
Approvals
Operating temperature sensing control suitable for incorporation into commercial air-conditioning
and refrigeration applications
Sensor inputs, Digital inputs, Programming key
Connected to SELV limited energy <15 W
NTC 5000 Ohm at 25 °C, (Beta value=3980 at 25/100 °C - e.g. EKS 211)
NTC 10000 Ohm at 25 °C, (Beta value=3435 at 25/85 °C - e.g. EKS 221)
PTC 990 Ohm at 25 °C, (e.g. EKS 111)
Pt1000, (e.g. AKS 11, AKS 12, AKS 21)
Measuring range:
-40 – 105 °C (-40 – 221 °F)
Controller accuracy:
±1 K below -35 °C, ±0.5 K between -35 – 25 °C,
±1 K above 25 °C
DO1 Compressor relay:
16 A, 16 (16) A, EN 60730-1
10 FLA / 60 LRA at 230 V, UL60730-1
16 FLA / 72 LRA at 115 V, UL60730-1
DO2 Defrost relay:
8 A, 2 FLA / 12 LRA, UL60730-1
8 A, 2 (2 A), EN60730-1
DO3 Fan relay:
3 A, 2 FLA / 12 LRA, UL60730-1
3 A, 2 (2 A), EN60730-1
DO4 Alarm/Light relay:
2 A
Front : IP65 (Gasket integrated)
Rear: IP00
II - 230 V supply version - (ENEC, UL recognized)
III - 115 V supply version - (UL recognized)
Category D (UL94-V0)
Temperature for ball pressure test statement “According to Annex G”
(EN 60730-1)
UL recognition (US & Canada) (UL 60730-1)
ENEC (EN 60730-1)
CQC
CE (LVD & EMC Directive)
EAC (GHOST)
NSF
ROHS2.0
HACCP temperature monitoring in compliance with EN134785 Class I,
when used with AKS 12 sensor
– Place the wired controller in the slot and ensure rubber sealing is resting properly on the mounting surface.
– Slide the mounting clips along the rails of the rear plastic from the rear side of the panel.
– Slide the clips towards mounting surface until controller is firmly fixed.
– To remove the controller, one needs to skillfully unlatch the snapping tab and pull the clips backwards.
115 V AC / 230 V AC / 50/60 Hz (Refer to the controller label).
4.6| Sensors
– Sair Control sensor.– S5 Defrost (evaporator) sensor.– Sc Condenser sensor.– Di1 Digital input - configurable to the functions listed under menu code o02.– Di2 Digital input - configurable to the functions listed under menu code o37.
–
4.7| Electric noise
Cables for sensors and DI inputs must be kept separate from other electric cables:
– Use separate cable trays.
– Keep a distance between cables of at least 10 cm.
– Long cables at the DI input should be avoided.
5| Menu Navigation and overview
5.1| Key functions and display Icons
Key Function
Press for one second: UP
Press and hold at power up:
FACTORY RESET (“FAC ” is displayed)
Press for one second: BACK
Press and hold: PULL-DOWN
Display Icons
Press and hold: ON/OFF
Press for one second: DOWN
Press and hold: DEFROST
Press for one second: TEMPERATURE SETPOINT/OK
Press and hold: MENU
Night mode (Energy saving)Fan running
Compressor running (Flashes in pull-down mode)Active alarm
DefrostUnit (°C or °F)
5.2| Quick Configuration at power up
– STEP 1: power on– STEP 2: select the quick configuration menu
Within 30 seconds of power on, press “<” BACK for 3 seconds. The main switch “r12” is automatically set to OFF.
– STEP 3: select pre-installed application “o61”
The display automatically shows the application selection parameter “o61”.
Press SET to select the pre-installed application.
The display shows the default value (eg. “AP0” flashing).
Choose the application type by pressing UP/DOWN and press SET to confirm.
The controller presets parameter values according to the selected application and does not hide relevant parameters.
Tip: you can easily move from AP0 to AP6, and thus select the simplified list of parameters, by pressing the UP key (circular list).
AppDescription (e.g. for ERC 213 and ERC 214)
App 0None (no preset application)
App 1Medium temperature (2 – 6 °C), ventilated ref. units with timed natural defrost
App 2Medium temperature (0 – 4 °C), ventilated ref. units with timed electrical defrost
App 3Low temperature (-26 – -20 °C), ventilated ref. units with timed electrical defrost
App 4Medium temperature (0 – 4 °C), ventilated ref. units with electrical defrost (by temperature)
App 5Low temperature (-26 – -20 °C), ventilated ref. units with electrical defrost (by temperature)
App 6None (no preset application) with simplified parameter list
Note: refer to chapter 2.4 - “Pre-defined Applications” for a complete description of the available applications.
The display automatically shows sensor selection parameter “o06”.
Press SET to select the sensor type.
The display shows the default value (eg. “n10” flashing).
Choose sensor type by pressing UP/DOWN (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) and press SET to confirm.
NOTE: all sensors must be the same type.
– STEP 5: configure DO4 output “o36”
The display automatically shows the “o36” parameter to configure “DO4” output. (Available only in 4 relays model).
Select light “Lig” or alarm “ALA” as per the application and press SET to confirm.
The display returns to normal display mode and the control is started.
5.3| Menu Structure
SET: press for 3 seconds to access
status, setup and service
– Press SET for three seconds to access the parameters groups.
– Select “CFg” menu and press SET to enter. The first menu “r12” (main switch) is displayed.
– Switch OFF main switch (r12=0) for changing the pre-installed application.
– Press UP/DOWN to scroll through the parameter list.
– Configure the “o61” parameter to select a pre-installed application:
– Press SET to access the “o61” parameter.
– Press UP/DOWN to select an application.
– Press SET to confirm, “o61” is displayed.
– Continue to set the next parameters (“o06” sensor type and “o36” DO4 configuration) in the “cFg” menu.
5.5| Adjust set point temperature
(short press) SET: adjust setpoint temperature.
UP/DOWN: change the temperature setpoint (in setting mode the setpoint flashes).
SET: save the temperature setpoint.
5.6| Initiate a manual defrost
DEFROST: press for 3 seconds to initiate a defsost.
DEFROST: press for 3 seconds to stop manual defrost.
The DEFROST icon is shown during defrost.
5.7| Initiate a pull down
PULL DOWN: press for 3 seconds to initiate pull down.
“Pud”: is shown for 3 seconds to indicate pull down.
The PULL DOWN icon flashes during pull down.
PULL DOWN: press for 3 seconds to stop pull down.
5.8| View active alarm
Temperature and alarm codes
alternate flashes until the alarm
is resolved. The alarm bell is shown.
5.9| Unlock keyboard
- After 5 minutes of no activity, the keypad is locked (if P76=yes).
- When the keypad is locked any button press shows “LoC” in the display.
- Press UP and DOWN buttons simultaneously for 3 seconds
to unlock the keyboard. “unl” is displayed for 3 seconds.
With this setting refrigeration can be started, stopped or a manual override of the outputs can be allowed.
Stopped refrigeration will give a ”OFF” signal on the display.
-1=service (manual control of outputs allowed)
0=OFF
1=ON
o61Predefined applications
Predefined applications is to give the user an easy and fast way to configure the controller refer to a specific
application based on storage temperature, defrost type and defrost method.
Users can set appropriate application that meets their requirements under this menu (please refer predefined
applications table under section 2.4 for more details). Predefined application is protected by main switch.
o06Sensor type selection
This parameter is for defining type of temperature sensors connected to the controller.
User can configure NTC 5 K, NTC 10 K, PTC and PT1000 sensors in this controller.
All the mounted sensors (Sair, S5 and Sc) must be of same type.
o36DO4 configuration
This parameter is to configure 4th relay as light or Alarm in case of four relay controller (ERC 214).
Lig=light
ALA=alarm
r--Reference
r00Temperature setpoint
This parameter defines the desired cabinet temperature at which compressor cuts out.
The set value can be locked or limited to a range with the settings in “r02” and “r03”.
r01Differential
This defines the difference between the cut-out and the cut-in of compressor relay.
Compressor relay will cut-in when the cabinet temperature reaches the set point+differetial.
In case of heating application, heater will cut-in when the temperature reaches the set point-differential.
r02Minimum set point limitation
The minimum allowable setpoint value can be configured here to avoid setting too low values by
accident/mistake.
r03Maximum set point limitation
The maximum allowable setpoint value can be configured here to avoid setting too high values by
accident/mistake.
r04Display offset
Correction value in display temperature. If the temperature at the products and the temperature received by
the controller are not identical, an offset adjustment of the display temperature can be carried out under this
menu code.
r05Display temperature unit
Set here if the controller is to show temperature values in °C or in °F. Switching from one to the other will cause
all temperature settings to be automatically updated to respective unit.
r09Calibration of Sair
Offset for air temperature calibration.
Compensation possibility due to long sensor cable.
r12Main switch
With this setting refrigeration can be started, stopped or a manual override of the outputs can be allowed.
Stopped refrigeration will give a ”OFF” signal on the display.
-1=service (manual control of outputs allowed)
0=OFF
1=ON
r13Night setback value
The thermostat’s reference will be the setpoint plus this value when the controller changes over to night
operation. (Select a negative value if there is to be cold accumulation).
Activation can take place via digital input.
r40Thermostat reference displacement offset temperature
The thermostat reference and the alarm values are shifted the following number of degrees when the
reference displacement is activated. Activation can take place via digital input.
A safety feature; the lowest temperature allowed during pull-down.
A--Alarm
A03Delay for temperature alarm during normal conditions
If the upper or the lower alarm limit values are exceeded, a timer function will commence.
The alarm will not become active until the set time delay has been passed.
A12Delay for temperature alarm during pull-down/start-up/defrost
This time delay is used during start-up, during defrost, during pull-down. There will be change-over to the
normal alarm time delay “A03” when the temperature falls within the alarm limits.
A13High temperature alarm limit
If the cabinet temperature stays above this limit for the time mentioned by the alarm delay, high temperature
alarm is raised.
A14Low temperature alarm limit
If the cabinet temperature stays below this limit for the time mentioned by the alarm delay, low temperature
alarm is raised.
A27DI1 delay
If “DI1” is configured as a door open alarm or as an external alarm, this delay is used to raise the respective
alarm.
A28DI2 delay
If “DI2” is configured as a door open alarm or as an external alarm, this delay is used to raise the respective
alarm.
A37Condenser high alarm limit
If the condenser temperature reaches above this limit, condenser alarm is raised immediately and no action is
taken. The alarm is zeroset if temperature falls 5 K below the set temperature.
A54Condenser high block limit
If the condenser temperature continues to increase above the “A37” limit and reaches this temperature limit,
condenser block alarm is raised and compressor is stopped. It is restricted to starting again until alarm is reset
manually. Manual reset of condenser block alarm can be performed in two ways:
- Power controller OFF and power ON controller again.
- Switch controller OFF and ON again via main switch or front button.
A72Voltage protection enable
This parameter is to enable and disable the voltage protection feature, which protects compressor from
adverse line voltage conditions.
A73Minimum cut-in voltage
When the compressor is due to start, the voltage of the power supply will be checked and the compressor will
only be allowed to start if it is at least the value given in this parameter.
A74Minimum cut-out voltage
When the compressor is running, it will be switched OFF if the voltage goes below that given in this parameter.
A75Maximum voltage
When the compressor is running, it will be switched OFF if the voltage exceeds that given in this parameter.
If the compressor is already stopped, it will remain switched OFF.
d--Defrost
d01Defrost method
Here you set whether defrost is to be accomplished by electric, Hot gas or natural method.
no=none
nAt=natural
EL=electrical
gAS=gas
d02Defrost stop temperature
This parameter defines at what temperature the defrost cycle will stop.
The temperature is given by the evaporator sensor or by the cabinet temperature sensor as defined in menu
code “d10”.
d03Defrost interval
Defines the time period between the start of two defrost cycles. In case of power failure elapsed time is stored
in the memory and next defrost will happen after completing the defined time interval.
d04Maximum defrost time
This parameter defines the defrost time when it is time based defrost. In case of temperature based defrost this
is treated as safety time to stop the defrost if it is not terminated based on the temperature.
This parameter decides the time offset when the defrost is triggered by digital inputs or during power up.
This function is only relevant if you have several refrigeration appliances or groups where you want the defrost
to be staggered in relation to one another.
d06Drip-OFF time
This parameter defines the time delay to start the compressor after defrost heater being switched OFF.
This delay is generally provided to ensure all water droplets on the evaporator drips off before starting the
refrigeration cycle.
d07Fan delay after defrost
Defines how long the delay is between the start of the compressor and the fan after defrost cycle.
d08Fan start temperature after defrost
This only applies if an evaporator temperature sensor is fitted.
This parameter determines at what evaporator temperature the fan will start after a defrost cycle is complete.
If the time set in “d07” occurs before the temperature set in “d08”, the fan will start in line with “d07”.
If the temperature set in “d08” occurs first, then the fan will start in line with “d08”.
d09Fan during defrost
This parameter is to define whether fan is to operate during defrost or not.
d10Defrost stop sensor
This parameter is to define which sensor has to be used to exit/terminate the defrost.
non=none, defrost is based on time
Air=Sair sensor
dEF=S5 (defrost) sensor
d18Compressor accumulated runtime to start defrost
When the accumulated compressor runtime is equal to the value set in this Parameter, defrost will be triggered.
If the compressor runtime is less than the set value during the define defrost interval “d03”, defrost will be
triggered based on the defrost interval “d03”. This feature is disabled when this parameter is set to zero.
d19Defrost on demand
The controller will constantly monitor the “S5” temperature to estimate the ice buildup.
In between two defrosts, if the “S5” temperature become lower than the value defined here controller will
initiate the defrost on demand.
This feature is disabled when this parameter is set to 20. This function can only be used in 1:1 systems.
d30Defrost delay after pull down
This parameter defines the time delay to start the defrost after pull down cycle.
This has to ensure defrost doesn’t happen immediately after pull down cycle.
F--Fan control
F01Fan at compressor cut-out
This parameter define the fan operation during compressor OFF cycle.
FAo=fan always ON
FFC=fan follow compressor
FPL=fan Pulsating
F04Fan stop evaporating temperature
This parameter defines the maximum evaporator temperature at which the Fan must switch OFF.
If the defrost sensor registers a higher temperature than the one set here, the fans will be stopped to avoid the
warm air circulation in the cabinet.
F07Fan ON cycle
This parameter is applicable only when the Fan at Compressor cut out “F01” is set to Fan Pulsating mode.
The Fan pulsating ON time will be as per the time set in this parameter.
F08Fan OFF cycle
This parameter is applicable only when the Fan at Compressor cut out “F01” is set to Fan Pulsating mode.
The Fan pulsating OFF time will be as per the time set in this parameter.
c--Compressor
C01Compressor minimum ON time
This parameter determines the minimum number of minutes the compressor must run before a cut-out can
take effect based on temperature. This is to avoid sudden switching ON and OFF of the compressor.
C02Compressor minimum OFF time
This parameter determines the minimum number of minutes the compressor must switched OFF before a
cut-in can take effect based on temperature. This is to avoid sudden switching OFF and ON of the compressor.
This parameter sets the delay in minutes before the compressor stops when the door is opened.
If set to zero, the function is disabled.
C70Zero crossing selection
This feature will increase the relay life time, reduce the contact welding and switching noise by switching ON
at Zero crossing. Disable zero crossing when external relay is used.
o--Others
o01Delay of outputs at startup
After start-up the controller functions can be delayed by the time delay defined here so that overloading of the
electricity supply network is avoided.
o02DI1 configuration
Here you can configure the DI1 to one of the functions listed below.
oFF=not used
Sdc=status display output
doo=door alarm with resumption (door function). When the input is open it signals that the door is open.
Compressor/heater and fan are stopped after “C04 Compressor door open delay”. After the time mentioned by
“DI1 Delay” from the time door is opened, an alarm will be given and refrigeration will be resumed.
doA=door alarm without resumption (door alarm). When the input is open it signals that the door is open.
Compressor/heater and fan are stopped after “C04 Compressor door open delay” and will stay off until the door
is closed. After the time mentioned by “DI1 Delay” from the time door is opened, an alarm will be given
(and refrigeration will not be resumed).
SCH=main switch. Regulation is carried out when the input is short-circuited, and regulation is stopped when
the input is put in position OFF.
nig=day/night mode. When the input is short-circuited, there will be regulation for night operation.
rFd=reference displacement. Value in “r40” is added to the reference “r00” when the input is short-circuited
EAL=external alarm. Alarm will be given when the input is short-circuited.
dEF=defrost. Defrost is initiated when the input is short-circuited. Edge triggering is used. Defrost exit can take
place by time, temperature or by manually pressing defrost push button on the front panel.
Pud=pull down. Pull down is initiated when the input is short-circuited. Edge triggering is used.
It will come out of pull down based on time and temperature defined under parameter “r96” and “r97” or can be
stopped manually by pressing pull down push button on front panel.
Sc=condenser sensor
o03Serial address
Data communication is possible through external TTL to RS485 gateway.
o05Password
If the settings in the controller are to be protected with an access code you can set a numerical value between
0 and 999. You can cancel the function by setting to 0.
o06Sensor type selection
This parameter is for defining type of temperature sensors connected to the controller.
User can configure NTC 5 K, NTC 10 K, PTC and PT1000 sensors in this controller.
All the mounted sensors (Sair, S5 and Sc)must be of same type.
o07Cooling/heating
This parameter is applicable only for single relay controller (ERC 211) for selecting cooling or heating
application.
o15Display resolution
This parameter defines the steps in which the temperature must be displayed by 0.1 or 0.5 or 1.
o23Relay 1 counter
The number of cycles for the “DO1” relay can be read in this menu.
The read value is multiplied by 100 to obtain the number of cycles.
On reaching 999x100 cycles the counts stops and is reset to 0.
o24Relay 2 counter
The number of cycles for the “DO2” relay can be read in this menu.
The read value is multiplied by 100 to obtain the number of cycles.
On reaching 999x100 cycles the counts stops and is reset to 0.
o25Relay 3 counter
The number of cycles for the DO3 relay can be read in this menu.
The read value is multiplied by 100 to obtain the number of cycles.
On reaching 999x100 cycles the counts stops and is reset to 0.
The number of cycles for the DO4 relay can be read in this menu.
The read value is multiplied by 100 to obtain the number of cycles.
On reaching 999x100 cycles the counts stops and is reset to 0.
o36DO4 configuration
This parameter is to configure 4th relay as light or Alarm in case of 4 relay controller (ERC 214).
Lig=light
ALA=alarm
o37DI2 configuration
Here you can configure the DI1 to one of the functions listed below
oFF=not used
Sdc=status display output
doo=door alarm with resumption (door function). When the input is open it signals that the door is open.
Compressor/heater and fan are stopped after “C04 Compressor door open delay”. After the time mentioned by
“DI1 Delay” from the time door is opened, an alarm will be given and refrigeration will be resumed.
doA=door alarm without resumption (door alarm). When the input is open it signals that the door is open.
Compressor/heater and fan are stopped after “C04 Compressor door open delay” and will stay off until the door
is closed. After the time mentioned by “DI1 Delay” from the time door is opened, an alarm will be given
(and refrigeration will not be resumed).
SCH=main switch. Regulation is carried out when the input is short-circuited, and regulation is stopped when
the input is put in position OFF.
nig=day/ night mode. When the input is short-circuited, there will be regulation for night operation.
rFd=reference displacement. Value in “r40” is added to the reference “r00” when the input is short-circuited.
EAL=external alarm. Alarm will be given when the input is short-circuited.
dEF=defrost. Defrost is initiated when the input is short-circuited. Edge triggering is used. Defrost exit can take
place by time, temperature or by manually pressing defrost push button on the front panel
Pud=pull down. Pull down is initiated when the input is short-circuited. Edge triggering is used.
It will come out of pull down based on time and temperature defined under parameter “r96” and “r97” or can be
stopped manually by pressing pull down push button on front panel.
o38Light control
This parameter defines the way the light must be controlled. Below are the three light control modes available.
on=always on
dAn=day/night
doo=based on door action
o61Predefined applications
Predefined applications is to give the user an easy and fast way to configure the controller to a specific
application based on storage temperature, defrost type and defrost method.
Users can set appropriate application that meets their requirements under this menu (please refer predefined
applications table under section 2.4 for more details). Predefined application is protected by main switch.
o67Save settings as factory
This parameter when set to YES. The current controller Parameter settings are stored as Factory default.
WARNING: original factory settings are overwritten.
o71DO2 configuration
Here you can configure the second relay as defrost or alarm in case of three relay controller (ERC213).
dEF=defrost
ALA=alarm
o91Display at defrost
You can set what is to be displayed during defrost here.
Air=actual air temperature
FrE=freezed temperature( display the temperature just before starting defrost)
no (normally open)=associated functionality is activated when “DI1” port is short circuit.
The associated function is deactivated when “DI1” port is open circuit.
nc (normally closed)=associated functionality is activated when “DI1” port is open circuit and deactivated
when “DI1” port is short circuit.
P74DI2 input polarity
no (normally open)=associated functionality is activated when “DI2” port is short circuit.
The associated function is deactivated when “DI2” port is open circuit.
nc (normally closed)=associated functionality is activated when “DI2” port is open circuit and deactivated
when “DI2” port is short circuit.
P75Invert alarm relay
Alarm relay operation can be inverted here
0=normal
1=invert relay action
P76Key board lock enable
YES=enable keyboard lock functionality after 5 minutes of no activity on the keypad.
Temperature setpointr00-100.0200.0C/F2.08.04.04.040.02.0
Differentialr010.120.0K2.02.02.02.02.02.0
Min set point limitationr02-100.0200.0C/F-35.04.02.02.020.0-35.0
Max set point limitationr03-100.0200.0C/F50.020.06.06.060.050.0
Display offset
(correction value in display
temperature)
Display unit (°C/°F)r05-C-F-C-C-C-C-C-C
Calibration of Sair
(offset for air temperature
calibration)
Main switch
-1=service, 0=OFF, 1=ON
Night set back
(offset temperature during night
mode)
WARNING: the earlier factory
settings are overwritten
Display at defrost
Air=actual air temperature,
FrE=freezed temperature,
-d-="-d-" is displayed
PolarityP--
DI1 input polarity
nc=normally closed,
no=normally open
Keyboard lock enableP76noyESnonononono-
Readoutsu--
Controller status
S0=cooling ON/Heating ON,
S2=wait for compressor ON time
to elapse,
S3=wait for compressor OFF time
to elapse-restart time,
S4=drip OFF delay after defrost,
S10=cooling stop
S11=cooling stopped by
thermostat/heating OFF,
S14=defrosting state,
S15=fan delay state after defrost,
S17=door open (DI input),
S20=emergency cooling,
S25=manual control of outputs,
S30=continous cycle/Pull-down,
S32=delay of outputs at power up
Air temperature (Sair)
Read the present regulation
reference
DI1 inputu10oFFon---
Status of night operationu13oFFon---
Condenser temperature (Sc)U09-100.0200.0C/F---
Compressor relay statusu58oFFon---
Firmware version readoutu80000999---
Temperature setpointr00-100.0200.0C/F2.04.02.0-24.02.0-24.02.0
Differentialr010.120.0K2.02.02.02.02.02.02.0
Min set point limitationr02-100.0200.0C/F-35.02.00.0-26.00.0-26.0-35.0
Max set point limitationr03-100.0200.0C/F50.06.04.0-20.04.0-20.050.0
Display offset
(correction value in display
temperature)
Display Unit (°C/°F)r05-C-F-C-C-C-C-C-C-C
Calibration of Sair
(offset for air temperature
calibration)
Main switch
-1=service, 0=OFF, 1=ON
Night set back
(offset temperature during night
mode)
during normal conditions
Delay for temperature alarm
during pull-down/start-up/
defrost
High temperature alarm limit
(Cabinet/Room)
Low temperature alarm limitA14-100.0200.0C/F-30.00.0-2.0-30.0-2.0-30.0-30.0
DI1 delay
(time delay for selected DI1
function)
DI2 delay
(time delay for selected DI2
function)
Condenser high alarm limitA370200C/F808080808080-
Condenser high block limitA540200C/F858585858585-
Voltage protection enableA72noyESnonononononono
Minimum cut-in voltageA730270V0000000
Minimum cut-out voltageA740270V0000000
Maximum voltageA750270V270270270270270270270
no=no defrost, nAt=natural,
EL=electrical, gAS=hot gas
Defrost stop temperatured020.050.0C/F6.0---6.06.06.0
Defrost intervald030240hours868128128
Max defrost timed040480min30451515303030
Defrost delay at power up
(or DI signal)
Drip delayd06060min0000005
Fan delay after defrostd07060min0000005
Fan start temperature
after defrost
Fan during defrostd09oFFonononononononon
Defrost stop sensor
S0=cooling ON/Heating ON,
S2=wait for compressor ON time
to elapse,
S3=wait for compressor OFF time
to elapse-restart time,
S4=drip OFF delay after defrost,
S10=cooling stop
S11=cooling stopped by
thermostat/heating OFF,
S14=defrosting state,
S15=fan delay state after defrost,
S17=door open (DI input),
S20=emergency cooling,
S25=manual control of outputs,
S30=continous cycle/Pull-down,
S32=delay of outputs at power up
Air temperature (Sair)u01-100.0200.0C/F---
Read the present regulation
reference
Defrost temperature (S5)u09-100.0200.0C/F------
DI1 inputu10oFFon---
Status of night operationu13oFFon---
DI2 inputu37oFFon---
Condenser temperature (Sc)U09-100.0200.0C/F---
Compressor relay statusu58oFFon---
Fan relay statusu59oFFon---
Defrost relay statusu60oFFon---
Light relay statusu63oFFon---
Firmware version readoutu80000999---
Temperature setpointr00-100.0200.0C/F2.04.02.0-24.02.0-24.02.0
Differentialr010.120.0K2.02.02.02.02.02.02.0
Min set point limitationr02-100.0200.0C/F-35.02.00.0-26.00.0-26.0-35.0
Max set point limitationr03-100.0200.0C/F50.06.04.0-20.04.0-20.050.0
Display offset
(correction value in display
temperature)
Display Unit (°C/°F)r05-C-F-C-C-C-C-C-C-C
Calibration of Sair
(offset for air temperature
calibration)
Main switch
-1=service, 0=OFF, 1=ON
Night set back
(offset temperature during night
mode)
Low temperature alarm limitA14-100.0200.0C/F-30.00.0-2.0-30.0-2.0-30.0-30.0
DI1 delay
(time delay for selected DI1
function)
DI2 delay
(time delay for selected DI2
function)
Condenser high alarm limitA370200C/F808080808080-
Condenser high block limitA540200C/F858585858585-
Voltage protection enableA72noyESnonononononono
Minimum cut-in voltageA730270V0000000
Minimum cut-out voltageA740270V0000000
Maximum voltageA750270V270270270270270270270
Defrostd--
Defrost method
no=no defrost, nAt=natural,
EL=electrical, gAS=hot gas
Defrost stop temperatured020.050.0C/F6.0---6.06.06.0
Defrost intervald030240hours868128128
Max defrost timed040480min30451515303030
Defrost delay at power up
(or DI signal)
Drip delayd06060min0000005
Fan delay after defrostd07060min0000005
Fan start temperature
after defrost
Fan during defrostd09oFFonononononononon
Defrost stop sensor
S0=cooling ON/Heating ON,
S2=wait for compressor ON time
to elapse,
S3=wait for compressor OFF time
to elapse-restart time,
S4=drip OFF delay after defrost,
S10=cooling stop
S11=cooling stopped by
thermostat/heating OFF,
S14=defrosting state,
S15=fan delay state after defrost,
S17=door open (DI input),
S20=emergency cooling,
S25=manual control of outputs,
S30=continous cycle/Pull-down,
S32=delay of outputs at power up
Air temperature (Sair)u01-100.0200.0C/F---
Read the present regulation
reference
Defrost temperature (S5)u09-100.0200.0C/F------
DI1 inputu10oFFon---
Status of night operationu13oFFon---
DI2 inputu37oFFon---
Condenser temperature (Sc)U09-100.0200.0C/F---
Compressor relay statusu58oFFon---
Fan relay statusu59oFFon---
Defrost relay statusu60oFFon---
Alarm relay statusu62oFFon---
Light relay statusu63oFFon---
Firmware version readoutu80000999---
Air temperature sensor (Sair) errorE29
Defrost sensor (S5) errorE27
Condenser sensor (Sc) errorE30
High temperature alarmA01
Low temperature alarmA02
High voltage alarmA99
Low voltage alarmAA1
High condenser temperature alarmA61
Door alarmA04
Standby alarmA45
DI external alarmA15
7.5| Troubleshooting
ProblemProbable causeRemedy
Waiting for compressor delay timer
Defrost in progress
Compressor does not start
Line voltage to compressor too low or
too high
Defrost does not startController in pull down mode
Pull-down does not start
Wrong temperature displayedWrong type of sensor selected
Pull-down max duration is 0
Pull-down limit temperature too high