Danfoss ERC 214 Installation guide

DI1
Installation guide
ERC 214
Digital regulator for refrigeration and defrosting, 4 relays.
The ERC 214 is a smart, multipurpose integrated refrigeration controller with temperature
520 H110 6 8
Dimensions (mm)
and defrost management, available with 4 relays. This controller is for Operating temperature sensing control, suitable for refrigeration and heating applications. Incorporated control has been designed to fulfil today’s requirements for commercial refrigeration applications.
71
36
28
29
Danfoss
80G8101.01
520 H110 6 8
Assembly
Wiring diagram
Sair
S5
DO1
83
DI2 DO4
DO2
DO3
61.2 66
Rear mount (clip fixing)
Assembly Removal
Quick programming tool: EKA 183B
DO1
Sc
DO2 DO3 DO4
Drilling template
Danfoss
80G8102.01
Danfoss
80G8103.02
12
3L 4N 567891011121314
~~~~
Electrical input
(on the basis of product code)
GND GND
Connectors: Max. Torque = 0.4 Nm
DKRCE.PI.RL0.N4.02 | 1© Copyright Danfoss | Published by ADAP-KOOL | 2018.10 Installation guide | ERC 214
Installation guide - ERC 214
1 - Technical features
• Easy to use: the four buttons, the easy-to-read menu structure and the preinstalled application solutions guarantee optimal usability.
• Simple installation: the 16 A relay means heavy loads can be connected directly without having to use an intermediate relay: compressors up to 2 HP on the basis of the power factor and efficiency of the motor (over 0.65 at 230 V and over 0.85 at 115 V). A vast range of compatible sensor types and screw terminals guarantee highly flexible installation.
• Unit protection: special software functions, protecting the compressor from voltage fluctuations or high condensation temperature, to guarantee optimal unit performance.
• Energy efficiency: defrosting on request, day/night mode and intelligent evaporator fan management guarantee maximum energy efficiency.
2 - User interface
Button function
Press and hold down on startup RESET FACTORY SETTINGS (“FAC” is displayed)
Press for one second: BACK Press and hold down: PULL-DOWN
Press for one second: TEMPERATURE SETPOINT/OK Press and hold down: MENU
Display icons
Night mode (energy saving) Fan on Defrosting
Compressor on Blinks in pull-down mode
Alarm activated Units (°C or °F)
Press for one second: UP Press and hold down: ON/OFF
Press for one second: DOWN Press and hold down: DEFROSTING
3 - Quick-start configuration
• STEP 1: Startup
• STEP 2: Select quick-start configuration menu
Within 30 seconds of startup, press “<” BACK for 3 seconds. The main switch “r12 ” is automatically set to OFF.
• STEP 3: Select the preinstalled application “o 61
The display automatically shows the application selection parameter “o61”. Press SET to select the preinstalled application. The display shows the default value (for example “AP0”, blinking). Select the type of application by pressing UP/DOWN and then SET to confirm. The regulator presets the parameter values on the basis of the application selected and hides any irrelevant parameters.
Tip: you can easily switch from AP0 to AP6 and therefore select the simplified parameters list by pressing the UP button (circular list).
App Description App 0 None (no preset application) App 1 Medium temperature ventilated ref. units (2 – 6 °C), with timed natural defrosting App 2 Medium temperature ventilated ref. units (0 – 4 °C), with timed electric defrosting App 3 Low temperature ventilated ref. units (-26 – -20 °C), with timed electric defrosting App 4 App 5 App 6 None (no preset application) with simplified parameters list
Medium temperature ventilated ref. units (0 – 4 °C), with timed electric defrosting (on the basis of the temperature) Low temperature ventilated ref. units (-26 – -20 °C), with timed electric defrosting (on the basis of the temperature)
• STEP 4: Select the sensor type “o06
The display automatically shows the sensor selection parameter “o06”. Press SET to select the type of sensor. The display shows the default value (for example “n10 ”, blinking). Select the type of sensor by pressing UP/DOWN (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) then SET to confirm.
NOTE: all the sensors must by the same type.
• STEP 5: Configure output DO4 “o36
The display automatically shows the parameter “o36” to configure the output “DO4”. Select light (“Lig”) or alarm (“ALA”) on the basis of the application and press SET to confirm. The display is reset in normal display mode with the control on.
DKRCE.PI.RL0.N4.02 | 2© Copyright Danfoss | Published by ADAP-KOOL | 2018.10 Installation guide | ERC 214
Installation guide - ERC 214
4 - Menu structure
1) Parameters group
Password (if enabled)
Input states
Configuration
SET: press for 3 seconds for state, settings and service
2) Parameter names
SET
Main switch
Application
Sensor type
To scroll the
parameter names
DO4 configuration
SET
3) Value
Application
1-2-3- 4 -5-6
Application 0
Application
6-5 - 4 -3 -2-1
Danfoss
80G114.01
To scroll the
parameter groups
5 - Quick configuration with “cFg” menu
• Press SET for three seconds to open the parameter groups.
• Select the “cFg” menu and press SET to open. The first menu “r12 ” (main switch) is displayed.
• Set the main switch to OFF (r12=0) to change the preinstalled application.
• Press UP/DOWN to scroll through the parameters list.
• Configure the parameter “o61” to select a preinstalled application:
- Press SET to open the parameter “o61”.
- Press UP/DOWN to select an application (AP0= no application).
- Press SET to confirm; “o61” is displayed.
• Continue to set the following parameters (sensor type “o06” and configuration “O36” DO4) in the “cFg” menu.
DKRCE.PI.RL0.N4.02 | 3© Copyright Danfoss | Published by ADAP-KOOL | 2018.10 Installation guide | ERC 214