Danfoss ERC 214 Installation guide

DI1
Installation guide
ERC 214
Digital regulator for refrigeration and defrosting, 4 relays.
The ERC 214 is a smart, multipurpose integrated refrigeration controller with temperature
520 H110 6 8
Dimensions (mm)
and defrost management, available with 4 relays. This controller is for Operating temperature sensing control, suitable for refrigeration and heating applications. Incorporated control has been designed to fulfil today’s requirements for commercial refrigeration applications.
71
36
28
29
Danfoss
80G8101.01
520 H110 6 8
Assembly
Wiring diagram
Sair
S5
DO1
83
DI2 DO4
DO2
DO3
61.2 66
Rear mount (clip fixing)
Assembly Removal
Quick programming tool: EKA 183B
DO1
Sc
DO2 DO3 DO4
Drilling template
Danfoss
80G8102.01
Danfoss
80G8103.02
12
3L 4N 567891011121314
~~~~
Electrical input
(on the basis of product code)
GND GND
Connectors: Max. Torque = 0.4 Nm
DKRCE.PI.RL0.N4.02 | 1© Copyright Danfoss | Published by ADAP-KOOL | 2018.10 Installation guide | ERC 214
Installation guide - ERC 214
1 - Technical features
• Easy to use: the four buttons, the easy-to-read menu structure and the preinstalled application solutions guarantee optimal usability.
• Simple installation: the 16 A relay means heavy loads can be connected directly without having to use an intermediate relay: compressors up to 2 HP on the basis of the power factor and efficiency of the motor (over 0.65 at 230 V and over 0.85 at 115 V). A vast range of compatible sensor types and screw terminals guarantee highly flexible installation.
• Unit protection: special software functions, protecting the compressor from voltage fluctuations or high condensation temperature, to guarantee optimal unit performance.
• Energy efficiency: defrosting on request, day/night mode and intelligent evaporator fan management guarantee maximum energy efficiency.
2 - User interface
Button function
Press and hold down on startup RESET FACTORY SETTINGS (“FAC” is displayed)
Press for one second: BACK Press and hold down: PULL-DOWN
Press for one second: TEMPERATURE SETPOINT/OK Press and hold down: MENU
Display icons
Night mode (energy saving) Fan on Defrosting
Compressor on Blinks in pull-down mode
Alarm activated Units (°C or °F)
Press for one second: UP Press and hold down: ON/OFF
Press for one second: DOWN Press and hold down: DEFROSTING
3 - Quick-start configuration
• STEP 1: Startup
• STEP 2: Select quick-start configuration menu
Within 30 seconds of startup, press “<” BACK for 3 seconds. The main switch “r12 ” is automatically set to OFF.
• STEP 3: Select the preinstalled application “o 61
The display automatically shows the application selection parameter “o61”. Press SET to select the preinstalled application. The display shows the default value (for example “AP0”, blinking). Select the type of application by pressing UP/DOWN and then SET to confirm. The regulator presets the parameter values on the basis of the application selected and hides any irrelevant parameters.
Tip: you can easily switch from AP0 to AP6 and therefore select the simplified parameters list by pressing the UP button (circular list).
App Description App 0 None (no preset application) App 1 Medium temperature ventilated ref. units (2 – 6 °C), with timed natural defrosting App 2 Medium temperature ventilated ref. units (0 – 4 °C), with timed electric defrosting App 3 Low temperature ventilated ref. units (-26 – -20 °C), with timed electric defrosting App 4 App 5 App 6 None (no preset application) with simplified parameters list
Medium temperature ventilated ref. units (0 – 4 °C), with timed electric defrosting (on the basis of the temperature) Low temperature ventilated ref. units (-26 – -20 °C), with timed electric defrosting (on the basis of the temperature)
• STEP 4: Select the sensor type “o06
The display automatically shows the sensor selection parameter “o06”. Press SET to select the type of sensor. The display shows the default value (for example “n10 ”, blinking). Select the type of sensor by pressing UP/DOWN (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) then SET to confirm.
NOTE: all the sensors must by the same type.
• STEP 5: Configure output DO4 “o36
The display automatically shows the parameter “o36” to configure the output “DO4”. Select light (“Lig”) or alarm (“ALA”) on the basis of the application and press SET to confirm. The display is reset in normal display mode with the control on.
DKRCE.PI.RL0.N4.02 | 2© Copyright Danfoss | Published by ADAP-KOOL | 2018.10 Installation guide | ERC 214
Installation guide - ERC 214
4 - Menu structure
1) Parameters group
Password (if enabled)
Input states
Configuration
SET: press for 3 seconds for state, settings and service
2) Parameter names
SET
Main switch
Application
Sensor type
To scroll the
parameter names
DO4 configuration
SET
3) Value
Application
1-2-3- 4 -5-6
Application 0
Application
6-5 - 4 -3 -2-1
Danfoss
80G114.01
To scroll the
parameter groups
5 - Quick configuration with “cFg” menu
• Press SET for three seconds to open the parameter groups.
• Select the “cFg” menu and press SET to open. The first menu “r12 ” (main switch) is displayed.
• Set the main switch to OFF (r12=0) to change the preinstalled application.
• Press UP/DOWN to scroll through the parameters list.
• Configure the parameter “o61” to select a preinstalled application:
- Press SET to open the parameter “o61”.
- Press UP/DOWN to select an application (AP0= no application).
- Press SET to confirm; “o61” is displayed.
• Continue to set the following parameters (sensor type “o06” and configuration “O36” DO4) in the “cFg” menu.
DKRCE.PI.RL0.N4.02 | 3© Copyright Danfoss | Published by ADAP-KOOL | 2018.10 Installation guide | ERC 214
Installation guide - ERC 214
6 - Basic functions
Adjusting the setpoint temperature
(short press) SET: adjust the setpoint temperature.
UP/DOWN: change the temperature setpoint (in setting mode the setpoint flashes).
SET: saves the temperature setpoint.
Initiate a manual defrost
DEFROST: press for 3 seconds to initiate a defsost.
DEFROST: press for 3 seconds to stop manual defrost.
The DEFROST icon is shown during defrost.
Initiate a pull down
PULL DOWN: press for 3 seconds to initiate pull down.
Danfoss
80G115.01
Pud”: is shown for 3 seconds to indicate pull down. The PULL DOWN icon flashes during pull down.
PULL DOWN: press for 3 seconds to stop pull down.
View an active alarm
Temperature and alarm codes alternate flashes until the alarm is resolved. The alarm bell is shown.
Unlock keyboard
- After 5 minutes of inactivity, the keypad will be locked (if P76 = YES).
- When the keypad is locked, if any key is selected, “LoC” appears on the display.
- Press UP and DOWN buttons simultaneously for 3 seconds to unlock the keyboard. “unl” is displayed for 3 seconds.
7 - Default application settings
App Mode Description Temp. Def. type Def. end App 0 Cooling None (no preset application) App 1 Cooling Medium temperature ventilated refrigeration units with timed natural defrost (2 – 6 °C) Natural Time App 2 Cooling Medium temperature ventilated refrigeration units with timed electrical defrost (0 – 4 °C) Electrical Time App 3 Cooling Low temperature ventilated refrigeration units with timed electrical defrost (-26 – -20 °C) Electrical Time
App 4 Cooling
App 5 Cooling
App 6 Cooling None (no preset application) with simplified parameter list
Medium temperature ventilated refrigeration units with electrical defrost (by temperature)
Low temperature ventilated refrigeration units with electrical defrost (by temperature)
(0 – 4 °C) Electrical Temperature
(-26 – -20 °C) Electrical Temperature
APP 1 APP 2/3 APP 4/5
SairDI1 DI2 SairDI1 DI2 SairDI1 DI2 S5
230 V AC 230 V AC 230 V AC
DO1 DO3 DO4
DO1 DO3DO2 DO4 DO1 DO3DO2 DO4
Danfoss
80G116.01
DKRCE.PI.RL0.N4.02 | 4© Copyright Danfoss | Published by ADAP-KOOL | 2018.10 Installation guide | ERC 214
Installation guide - ERC 214
8 - Technical Data
FEATURES DESCRIPTION
Purpose of control
Construction of control Incorporated control
Power supply Low voltage, regulated, galvanically isolated, 115 V AC or 230 V AC, 50/60 Hz input Rated power Less than 0.7 W
Inputs
Types of sensors allowed
Sensors in “Kit Solution” NTC 10000 Ohms at 25 °C, 1.5 m cable
Precision
Type of action 1B (relay)
Output
Display LED 3-figure display, decimal point and multifunction icons, °C + °F scale Operating Conditions -10 – 55 °C (14 – 131 °F), 90% Rh Storage conditions -40 – 70 °C (-40 – 158 °F), 90% Rh
Protection
Environmental data Pollution degree II, condensate free
Overvoltage category
Heat and fire resistant
EMC category Category I
Certifications
Operating temperature sensing control suitable for incorporation into commercial air­conditioning and refrigeration applications
Sensor inputs, Digital inputs, Programming key Connected to SELV limited energy <15 W
NTC 5000 Ohms at 25 °C (beta = 3,980 at 25/100 °C - EKS 211 for example) NTC 10000 Ohms at 25 °C (beta = 3,435 at 25/85 °C - EKS 221 for example) PTC 990 Ohms at 25 °C (EKS 111 for example) Pt1000 (AKS 11, AKS 12, AKS 21 for example)
Measuring range:
-40 – 105 °C (-40 – 221 °F) Regulator precision:
+/-1 K below -35 °C, +/-0.5 K between -35 – 25 °C, +/-1 K above 25 °C
Compressor relay DO1: 16 A, 16 (16) A, EN 60730-1 10 FLA / 60 LRA at 230 V, UL60730-1 16 FLA / 72 LRA at 115 V, UL60730-1
Defrosting relay DO2: 8 A, 2 FLA / 12 LRA, UL60730-1 8 A, 2 (2 A), EN60730-1
Fan relay DO3: 3 A, 2 FLA / 12 LRA, UL60730-1 3 A, 2 (2 A), EN60730-1
Alarm / light relay DO4: 2:00 AM
Front: IP65 (with seal) Rear: IP00
II - 230 V supply version - (ENEC, UL recognized) III - 115 V supply version - (UL recognized)
Category D (UL94-V0) Temperature for ball pressure test statement “According to Annex G” (EN 60730-1)
UL acknowledgement (USA and Canada) (UL 60730-1) ENEC (EN 60730-1) CQC EC (LVD and EMC Directives) EAC (GHOST) NSF ROHS2.0 HACCP temperature monitoring in compliance with EN134785 Class I if used with sensor AKS 12
DKRCE.PI.RL0.N4.02 | 5© Copyright Danfoss | Published by ADAP-KOOL | 2018.10 Installation guide | ERC 214
Installation guide - ERC 214
9 - Parameters
Parameter name - ERC 214 Code Min. Max. Unit
Configuration cFg
Main switch
-1=service, 0=OFF, 1=ON
Predefined applications
AP0, AP1, AP2, AP3, AP4, AP5, AP6
Sensor type selection
n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000
DO4 configuration
Lig=light, ALA=alarm
Reference / thermostat r--
Temperature setpoint r00 -100 200 C/F 2 4 2 -24 2 -24 2 Differential r01 0.1 20 K 2 2 2 2 2 2 2 Min set point limitation r02 -100 200 C/F -35 2 0 -26 0 -26 -35 Max set point limitation r03 -100 200 C/F 50 6 4 -20 4 -20 50 Offset display
(temperature correction shown on display)
Display units (°C / °F) r05 -C -F -C -C -C -C -C -C -C Sair calibration
(offset for air temperature calibration)
Main switch
-1=service, 0=OFF, 1=ON
Night setback
(offset temperature during night mode)
Thermostat reference displacement
(temperature offset)
Pull-down duration r96 0 960 min. 0 0 0 0 0 0 - Pull-down temperature limit r97 -100 200 C/F 0 0 0 0 0 0 -
Alarm A--
Delay for temperature alarm
during normal conditions
Temperature alarm delay
pull-down / startup / defrosting duration
High temperature alarm limit
(Cabinet / Ambient)
Low temperature alarm limit A14 -100 200 C/F -30 0 -2 -30 -2 -30 -30 DI1 delay
(delay for selected function DI1)
DI2 delay
(delay for selected function DI2)
Condenser high alarm limit A37 0 200 C/F 80 80 80 80 80 80 - Condenser high block limit A54 0 200 C/F 85 85 85 85 85 85 - Voltage protection enable A72 no yes no no no no no no no Minimum cut-in voltage A73 0 270 V 0 0 0 0 0 0 0 Minimum cut-out voltage A74 0 270 V 0 0 0 0 0 0 0 Maximum voltage A75 0 270 V 270 270 270 270 270 270 270
Defrost d--
Defrosting method
no=no defrost, nAt=natural, EL=electric, gAS=hot gas
Defrost stop temperature d02 0 50 C/F 6 - - - 6 6 6 Defrost interval d03 0 240 hours 8 6 8 12 8 12 8
N.B.: hidden parameters are greyed out
r12 -1 1 1 1 1 1 1 1 1
o61 AP0 AP6 AP0 AP1 AP2 AP3 AP4 AP5 AP6
o06 n5 Pt1 n10 n10 n10 n10 n10 n10 n10
o36 Lig ALA Lig Lig Lig Lig Lig Lig Lig
r04 -10 10 K 0 0 0 0 0 0 0
r09 -20 20 K 0 0 0 0 0 0 -
r12 -1 1 1 1 1 1 1 1 -
r13 -50 50 K 0 0 0 0 0 0 0
r40 -50 50 K 0 0 0 0 0 0 -
A03 0 240 min 30 45 30 30 30 30 30
A12 0 240 min 60 90 60 60 60 60 60
A13 -100 200 C/F 8 10 8 -15 8 -15 8
A27 0 240 min 30 30 30 30 30 30 30
A28 0 240 min 30 30 30 30 30 30 30
d01 no gAS EL nAt EL EL EL EL EL
App. 0
(Def.)
App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
DKRCE.PI.RL0.N4.02 | 6© Copyright Danfoss | Published by ADAP-KOOL | 2018.10 Installation guide | ERC 214
Installation guide - ERC 214
Parameter name - ERC 214 Code Min. Max. Unit
App. 0
(Def.)
App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
Max. defrost time d04 0 480 min 30 45 15 15 30 30 30 Defrost delay at power up
(or DI signal)
d05 0 240.0 min 0 0 0 0 0 0 -
Drip delay d06 0 60 min 0 0 0 0 0 0 5 Fan delay after defrost d07 0 60 min 0 0 0 0 0 0 5 Fan start temperature after defrost d08 -50 0 C/F -5 - - - -5 -5 - Fan during defrost d09 oFF on on on on on on on on Defrost stop sensor
non=timed, Air=Sair (air temperature),
d10 non dEF non non non non dEF dEF non
dEF=S5 (defrost sensor)
Compressor accumulated
runtime to start defrost
d18 0 96 hours 0 0 0 0 0 0 -
0=OFF
Defrost on demand
20.0=OFF
Defrost delay after pull-down
0=OFF
d19 0 20 K 20 - - - 20 20 -
d30 0 960 min 0 0 0 0 0 0 -
Fan control F--
Fan at compressor cutout
FFc=fan follow compressor, FAo=fan always ON,
F01 FFc FPL FAo FAo FAo FA o FAo FA o FAo
FPL= fan pulsation
Fan stop evaporator temperature
50.0=OFF
F04 -50 50 C/F 50 - - - 50 50 -
Fan cycle ON F07 0 15 min 2 2 2 2 2 2 2 Fan cycle OFF F08 0 15 min 2 2 2 2 2 2 2
Compressor c--
Compressor minimum ON time C01 0 30 min 0 0 0 0 0 0 0 Compressor minimum OFF time C02 0 30 min 2 2 2 2 2 2 2 Compressor OFF delay
with door open
C04 0 15 min 0 0 0 0 0 0 1
Zero crossing selection C70 no yes yes yes yes yes yes yes yes
Others o--
Delay of outputs at startup o01 0 600 min 5 5 5 5 5 5 5 DI1 configuration
oFF=not used, Sdc=status display output, doo=door alarm with resumption, doA=door alarm without resumption, SCH = main switch, nig=day / night mode,
o02 oFF Sc oFF oFF oFF oFF oFF oFF oFF
rFd=reference displacement, EAL=external alarm, dEF=defrost, Pud=pull-down, Sc=condenser sensor
Serial address o03 0 247 0 0 0 0 0 0 - Password o05 no 999 no no no no no no 0 Select sensor type
n5=NTC 5 K, n10=NTC 10 K,
o06 n5 Pt1 n10 n10 n10 n10 n10 n10 -
Ptc=PTC, Pt1=Pt1000
Display resolution
0.1=steps of 0.1 °C,
0.5=steps of 0.5 °C,
o15 0.1 1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
1.0=steps of 1.0 °C
Relay 1 counter
(1 count = 100 operating cycles)
o23 0 999 0 0 0 0 0 0 -
N.B.: hidden parameters are greyed out
DKRCE.PI.RL0.N4.02 | 7© Copyright Danfoss | Published by ADAP-KOOL | 2018.10 Installation guide | ERC 214
Installation guide - ERC 214
Parameter name - ERC 214 Code Min. Max. Unit
Relay 2 counter
(1 count = 100 operating cycles)
Relay 3 counter
(1 count = 100 operating cycles)
Relay 4 counter
(1 count = 100 operating cycles)
DO4 configuration
ALA=alarm, Lig=light
o24 0 999 0 0 0 0 0 0 -
o25 0 999 0 0 0 0 0 0 -
o26 0 999 0 0 0 0 0 0 -
o36 ALA Lig Lig Lig Lig Lig Lig Lig -
App. 0
(Def.)
App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
DI2 configuration
oFF=not used, Sdc=status display output, doo=door alarm with resumption, doA=door alarm without resumption, SCH=main switch, nig=day / night mode,
o37 oFF Pud oFF oFF oFF oFF oFF oFF oFF
rFd=reference displacement, EAL=external alarm, dEF=defrost, Pud=pull-down
Lights control
on=always on, dAn=day / night,
o38 on doo on on on on on on on
doo=on basis of door action
Predefined applications o61 AP0 AP6 AP0 AP1 AP2 AP3 AP4 AP5 - Save settings as default
WARNING: previous default settings
o67 no yes no no no no no no -
will be overwritten
Display at defrost
Air=effective air temperature, FrE=freezing temperature,
o91 Air -d- -d- -d- -d- -d- -d- -d- -d-
-d-="-d-" is displayed
Polarity P--
DI1 input polarity
nc=normally closed,
P73 nc no no no no no no no no
no=normally open
DI2 input polarity
nc=normally closed,
P74 nc no no no no no no no no
no=normally open
Invert alarm relay
0=normal, 1=relay action inversion
P75 0 1 0 0 0 0 0 0 -
Keyboard lock enable P76 no yes no no no no no no -
Readouts u--
Controller status
S0=cooling ON/Heating ON, S2=wait for compressor ON time to elapse, S3=wait for compressor OFF time to elapse-restart time, S4=drip OFF delay after defrost, S10=cooling stop, S11=cooling stopped by thermostat / heating OFF, S14=defrosting state,
u00 S0 S32 --
S15=fan delay state after defrost, S17=door open (DI input), S20=emergency cooling, S25=manual control of outputs, S30=continous cycle/Pull-down, S32=delay of outputs at power up
Air temperature (Sair) U01 -100 200 C/F --- Read the present regulation
reference
u02 -100 200 C/F ---
Defrost temperature (S5) u09 -100 200 C/F --- - - -
N.B.: hidden parameters are greyed out
DKRCE.PI.RL0.N4.02 | 8© Copyright Danfoss | Published by ADAP-KOOL | 2018.10 Installation guide | ERC 214
Danf already on order pro All trademarks in this material are property of the respec
Installation guide - ERC 214
Parameter name - ERC 214 Code Min. Max. Unit
App. 0
(Def.)
DI1 input u10 oFF on --- Status of night operation u13 oFF on --- DI2 input u37 oFF on --- Condenser temperature (Sc) U09 -100 200 C/F --- Compressor relay status u58 oFF on --- Fan relay status u59 oFF on --- Defrost relay status u60 oFF on --- Alarm relay status u62 oFF on --- Light relay status u63 oFF on --- Firmware version readout u80 0 999 ---
Alarm status
Sair air temperature sensor error E29 S5 defrost sensor error E27 Sc condenser sensor error E30 High temperature alarm A01 Low temperature alarm A02 High voltage alarm A99 Low voltage alarm AA1 Condenser alarm A61 Door alarm A04 Standby alarm A45 DI external alarm A15
N.B.: hidden parameters are greyed out
App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
Safety standards
Check the input voltage is correct before connecting the instrument. Do not expose to water or damp: only use the regulator within the design operating limits, avoiding sudden temperature changes with high atmospheric humidity to prevent condensate forming.
Product disposal
The device (or product) must be disposed of in compliance with local waste disposal legislation.
EU design registration
002566703-0001
Contact info.: www.danfoss.com/erc
oss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
vided that such alterations can be made without subsequential changes being necessary eady agreed.
tive companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
DKRCE.PI.RL0.N4.02 | 9© Copyright Danfoss | Published by ADAP-KOOL | 2018.10 Installation guide | ERC 214