Intended use of the user guide................................................................................................................................................... 5
Conformity according to standards........................................................................................................................................ 11
Terms and abbreviations.............................................................................................................................................................12
Responsibility of the manufacturer.........................................................................................................................................13
General safety statement............................................................................................................................................................14
Safety message signal words.....................................................................................................................................................14
Personal protective equipment................................................................................................................................................15
Intended use of the electric machine.....................................................................................................................................19
Used technology............................................................................................................................................................................ 20
System introduction..................................................................................................................................................................... 21
Connections and interfaces........................................................................................................................................................22
System design.................................................................................................................................................................................26
Cooling and temperature measurement ........................................................................................................................26
Shaft alignment and load...................................................................................................................................................... 29
Receiving and unpacking............................................................................................................................................................32
Mounting the electric machine........................................................................................................................................... 39
Power connections.................................................................................................................................................................. 42
High voltage connection..................................................................................................................................................42
Cable gland assembly and power line connection.................................................................................................46
Low voltage connections.......................................................................................................................................................50
Condition monitoring during operation...............................................................................................................................59
Bearings and lubrication............................................................................................................................................................. 63
Cooling system maintenance....................................................................................................................................................67
Dismounting
Troubleshooting
Aftersales
Service policy...................................................................................................................................................................................70
Service parts.....................................................................................................................................................................................70
Disposal
Storage, installation and maintenance checklists
This user guide is the installation, operation and maintenance user guide for the EM-PMI375-T200, EMPMI375-T500, EM-PMI375-T800 and EM-PMI375-T1100 electric machines.
This user guide contains instructions necessary to safely and properly handle, install, operate and
maintain the electric machine. They should be brought to the attention of anyone who installs, operates
or maintains the machine or associated equipment.
All of the safety warnings and instructions in this user guide must be followed to prevent injury to
personnel or damage to property. Only qualified and authorized personnel, familiar with health and
safety requirements and national legislation, shall be permitted to handle, install, operate and maintain
the device.
This user guide must be kept for future reference during installation, operation and maintenance.
This user guide uses illustrations as examples only. Illustrations in this user guide may not necessarily
reflect all system features.
Frame model indicates dimensions and electrical characteristics of the electric machine. The following
naming convention is used to refer to the electric machine frame model:
EM-PMI375-T200-XXXX+XX
•
EM-PMI375-T500-XXXX+XX
•
EM-PMI375-T800-XXXX+XX
•
EM-PMI375-T1100-XXXX+XX
•
The naming codes of the electric machine
Part of the nameMeaning
EMElectric Machine
PMIXXX or PMEXXXPermanent Magnet Internal and a number relative to
the diameter of the electric machine, or Permanent
Magnet External and a number relative to diameter of the
electric machine
TXXXXAverage continuous torque of the motor range, relative
to the lenght of the machine
XXXXRated rotation speed
+XXOptions, see option table below. Standard options are
indicated by a star (*).
The power input of the machine may require one or several three phase power systems. This is indicated
by a power connection option marking, for example: DUAL or QUAD in the machine model code. One
three phases power system can include one or three connection boxes in the machine. The most usual
case is when an electric machine has a single connection box, but this is not shown in the machine
model code.
Example: EM-PMI375-T800-1300-DUAL
•
The electric machine can include some of the options available. The options of the electric machine are
shown also in the rating plate, following the frame model code. Note! Only options that differ from the
standard delivery are indicated. Following options are used, see Table below. For detailed information of
the models, options and characteristics, see product data sheets.
+RES1ResolverIn-built non contacting resolver, 6-pole
pair
+RES2Double resolver2 x In-built non contacting resolver, 6-pole
pair
Side mounting*NoneNo side mounting holes available. In case
+SM1Side mounting12 x side mounting threaded holes
Winding temperature
sensor
Bearing temperature sensor *None
Anti-condensation heaters *None
Marine classification*No marine classification
*Temperature surveillance3 x PT100 in the windings
+TEMP4Redundant temperature
surveillance
+TEMP5Redundant temperature
surveillance
+BTMP1PT100 in bearingsPlug-in connector
+HEAT1One anti-condensation
heater
+CL1ABS American Bureau of Shipping
+CL2BV Bureau Veritas
+CL3DNV
+CL4LR Lloyd’s Register
+CL5RINA
+CL6CCS China Classification Society
side mounting holes are present, they are
plugged by default.
M10x1.5. Plugged by default with M10x10,
DIN 913, (ISO 4026), SET SCREW
6 x PT100 in the windings
12 x PT100 (two wire) in windings (Not
available with +LVB1 option)
230VAC/130W
Conformity according to standards
The electric machine has been designed to be in conformity with the following directives and to meet the
requirements specified in the following standards:
Applicable Directives and standards
StandardExplanation
Low Voltage Directive
2006/95/EC (until 19.4.2016)
and Low Voltage Directive
2014/35/EU (from 20.4.2016
onwards)
IEC 60034-1:2010Rotating electrical machines - Part 1: Rating and performance
IEC 60034-5:2001/A1:2007Rotating electrical machines - Part 5: Degrees of protection provided by the
IEC 60034-6:1991Rotating electrical machines - Part 6: Methods of cooling
IEC 60034-7:1992/A1:2001Rotating electrical machines - Part 7: Classification of types of construction,
Electrical equipment means any equipment designed for use with a voltage
rating of between 50 and 1000 V for alternating current. This electric
machine is subject to the Low Voltage Directive 2006/95/EC or 2014/35/EC.
integral design of rotating electrical machines (IP code) - Classification
mounting arrangements and connection box position (IM Code)
User Guide
EM-PMI375
General information
Warranty
Applicable Directives and standards (continued)
StandardExplanation
IEC 60034-8:2007/A1:2014Rotating electrical machines - Part 8: Terminal markings and direction of rotation
IEC 60034-14:2004/A1:2008Amendment 1 - Rotating electrical machines - Part 14: Mechanical vibration of
certain machines with shaft heights 56 mm and higher - Measurement, evaluation
and limits of vibration severity.
Danfoss offers warranty against defects in workmanship and materials for its products for a period of
twelve (12) months from commissioning or eighteen months (18) from delivery (Incoterms-EXW),
whichever occurs first.
In order for the warranty to be valid, the customer must follow the requirements of this and all related
documents, especially those set out in the product installation and maintenance, as well as the applicable
standards and regulations in force in each country.
Defects arising from the improper or negligent use, operation, and/or installation of the equipment, nonexecution of regular preventive maintenance, as well as defects resulting from external factors or
equipment and components not supplied/recommended by Danfoss, will not be covered by the
warranty.
The warranty will not apply if the customer at its own discretion makes repairs and/or modifications to
the equipment without prior written consent from Danfoss.
Terms and abbreviations
The symbols, terms and abbreviations in the Tables below are possibly used in this manual.
Symbols
SymbolVariableUnit
URated voltage (phase-to-phase AC)V
IRated current (AC)A
PRated Power (S1)kW
TRated torque (S1) at rated speedNm
T
max
nRated speedrpm
Max nMaximum speedrpm
fRated supply frequency at nominal speedHz
PFPower factor (cosφ)
Q
c
T
c
T
amb
RES_COSCosine signal received from the resolverdeg
RES_SINSinusoidal signal received from the machine resolverdeg
GNDGround in electrical connections
Ω (Ohm)ResistanceΩ
ResolverRotation meter in electric machines, used for measuring degrees of rotation
ACAlternating current
DCDirect current
PMSMPermanent Magnet Synchronous Machine
SRPMSynchronous Reluctance assisted Permanent Magnet
S1Duty type according to the IEC60034; Continuous running duty
S9Duty type according to the IEC60034; Duty with non-periodic load and speed variations
Responsibility of the manufacturer
Danfoss is responsible for the safety, reliability and performance of the electric machine only if:
•
Handling, mounting, installation, operation and maintenance are done by qualified and authorized
personnel.
•
The installation of the system complies with the requirements of the appropriate regulations.
•
The electric machine is used in accordance with the instructions in this user guide.
•
The electric machine is installed, maintained and serviced in accordance with the instructions in this
user guide.
The electric machine is intended for use as a component for industrial and commercial installations.
The end product containing the electric machine must conform with all related regulations.
•
The use of the electric machine is prohibited in hazardous areas unless it is expressly designed for
such use.
•
The electric machine is intended for installation, use and maintenance by qualified personnel, familiar
with health and safety requirements and national legislation. Ignoring these instructions may
invalidate all applicable warranties.
•
These instructions must be followed to make sure of safe and correct installation, operation and
maintenance of the electric machine. They should be brought to the attention of anyone who installs,
operates or maintains the electric machine or associated equipment.
•
High voltage and rotating parts can cause serious or fatal injuries. For electric machine covered by
this user guide, it is important to observe safety precautions to protect personnel from possible
injury.
Safety message signal words indicate the severity of a potential hazard.
DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious
injury.
WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury.
CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury. CAUTION may also alert against unsafe practices.
NOTICE Indicates a potentially hazardous situation which, if not avoided, could result in property
damage.
Safety symbols
The following safety and information related symbols appear in this user guide and on the electric
machine.
Danger
This symbol is identified by a yellow background, red octagonal band and a black STOP text.
It indicates a hazardous situation that causes severe injury or death. Action indicated by this
symbol may not be executed.
General warning
This symbol is identified by a yellow background, black triangular band, and a black
exclamation point symbol. It indicates a general potentially hazardous situation.
Electric shock warning
The symbol is identified by a yellow background, black triangular band, and a black
arrowhead symbol. It indicates dangerous electrical voltage that could cause an electric shock
to a person.
Burn warning
The symbol is identified by a yellow background, black triangular band, and a black wavy
lines symbol. It indicates a hot device that could cause burns to a person.
The symbol also indicates that the device should be placed and installed so that contact with
its potentially hot surface is not possible.
Magnet warning
The symbol is identified by a yellow background, black triangular band, and a black magnet
symbol. It indicates strong magnetic field that could cause harm to a person or property.
Rotating shaft warning
The symbol is identified by a yellow background, black triangular band, and a black rotating
shaft symbol. It indicates strong rotating shaft that could cause harm to a person or property.
General Information.
Read the instructions in the user guide.
Personal protective equipment
Personal protective equipment shall be used when necessary during handling, installation and
maintenance of the electric machine to avoid injury.
Use eye protective equipment like safety goggles or mask when you work with the electric
machine. Permanent damage to the eye could be caused if bearing grease, melted nitrile
rubber (radial lip seal), glycol or other fluids splash.
Use hearing protective equipment when you work on the electric machine. Hearing injuries
can be caused by too loud noise (noise in excess of 85 dBA).
Use head protective equipment like helmet when you lift the electric machine! Head injuries
can be caused by object impact.
Use cut resistant gloves when you handle and maintain the electric machine. There is a risk of
cut injuries.
Use protective footwear when you lift or move the electric machine! Foot injuries could be
caused if lifting system or lifting brackets fail.
Security features
The electric machine has at least one PT100 temperature sensor in the windings. The amount of the
sensors depend on the options chosen. The temperature signal(s) can be read out from the measurement
connector of the electric machine. You can connect the temperature signal to the temperature
surveillance pin in the inverter (EC-C) and make sure that the inverter has the machine temperature
protection feature activated.
Electromagnetic compatibility (EMC)
EMC stands for Electromagnetic compatibility. It is the ability of electric equipment to operate without
problems within an electromagnetic environment. Likewise, the equipment must not disturb or interfere
with any other product or system within its locality. This is a legal requirement for all equipment taken
into service within the European Economic Area (EEA).
Our products are designed with high standards of EMC in mind. Connect the power lines and groundings
along the instructions in this user guide to achieve the required level of EMI protection.
It is the responsibility of the installer to make sure that the equipment or system into which the product is
incorporated complies with the EMC legislation of the country of use. Within the European Union,
equipment into which this product is incorporated must comply with the EMC Directive 2014/30/EU.
When interfacing other equipment, connect only equipment that are specified as part of the
system and that are compatible.
Magnetic and electromagnetic fields generated near the current-carrying conductors and
permanent magnets in electric machines represent a health danger to persons with heart
pacemakers, metal implants and hearing aids. Persons with a heart pacemaker, metal
implants or hearing aids must consult a doctor before they enter the following areas:
•
Areas in which electric equipment and parts are operated
•
Areas in which electric equipment with permanent magnets are stored, mounted,
operated or repaired
If necessary, perform a special electromagnetic compatibility (EMC) test on the installation.
This product manual is about four electric machines:
•
EM-PMI375-T200
•
EM-PMI375-T500
•
EM-PMI375-T800
•
EM-PMI375-T1100
For harsh conditions, like salty air in marine applications, it is recommended to check the
surface treatment possibilities with the factory.
The electric machines have been developed especially for heavy duty, marine and transportation
applications. They are more reliable, smaller, lighter and more efficient than conventional products on
the market.
Typical applications of the electric machines are:
Motor (electric propulsion) and generator for hybrid marine vessels or mobile work machine and bus
•
parallel hybrid applications.
Traction motor and generator for electrical or hybrid electrical mobile work machines or buses.
•
The electric machines feature Synchronous Reluctance assisted Permanent Magnet (SRPM) motor
technology, having several advanced features:
Extremely compact and robust structure.
•
High efficiency throughout the operation range.
•
Liquid cooling with water/glycol mixture.
•
Low coolant flow required.
•
High allowed coolant temperature.
•
IP65 enclosure class to maximize reliability.
•
Multiple mounting possibilities.
•
Extended speed and torque capabilities compared to standard PM machines.
•
Machine structure designed to be able to produce high starting torques (instant torque to non-
•
moving wheel).
Optimized speed range to meet most common gear ratios used in heavy mobile machinery.
The electric machines have several frame models (sizes) to be the optimal solutions for several
applications. They also have options for shaft type, attachment interface, bearings, connection box
attachment, rotation sensors and temperature sensors.
Intended use of the electric machine
This electric machine is intended to be used as a motor or generator and as a part of a machinery, for
example in:
Power train of a marine vessel, transportation vehicle or a heavy duty work machine.
•
Power generation equipment.
•
The electric machine is intended to be powered and controlled with an inverter or inverters capable of
supplying three-phase alternating current and that is capable of controlling the electric machine. The
electric machine is not suitable for direct online use.
In a power generation equipment the electric machines are intended to be powered by a prime mover,
for example, an internal combustion engine and controlled by the above mentioned electric power
inverter.
The electric machine is solely intended for professional use, and may be operated only by trained
professionals. The maintenance of the electric machine may be done only by trained professionals.
Forbidden use of the electric machine
It is forbidden to use, handle and maintain the machine in following ways (including but not limited to):
•
Using the electric machine for other purposes than defined in this user guide.
•
Disregarding the obligation to comply with the user guide, safety signs and rating plate of the electric
machine.
•
Using the electric machine, making adjustments and maintenance without first reading this user
guide.
•
Exceeding the designed limits during the electric machine operation.
•
Using non-original service parts of wrong material causing corrosion problems and mechanical
failures in time.
•
Operating and performing maintenance for the electric machine without appropriate personal
protective equipment.
•
Using electric machine parts like frame, shaft end or terminal box for climbing or for support for other
structures.
Causing any kind of impact forces to the electric machine (for example hitting or hammering or
dropping objects).
•
Operating the electric machine with electric connections other than defined in the user guide and/or
other documents.
•
Operating the electric machine with insufficiently tightened connections or cable glands.
•
Operating the electric machine with power cables routed against the instructions.
•
Operating the electric machine without properly dimensioned and operating cooling system.
•
Operating the electric machine without following the bearing lubrication instructions.
•
Touching the connection terminal of the electric machine or doing maintenance or adjustment
operations on the electric machine with the electricity connected.
•
Accessing the connection box(es) if the shaft can be turned by an external prime mover.
•
Lifting the electric machine from wrong lifting points and without correct lifting equipment.
•
Lifting additional load with the machine.
•
Storing the electric machine outdoors in wet or dusty conditions.
•
Storing the electric machine without correct support to prevent rolling or falling of the machines.
•
Using the electric machine in potentially explosive environment.
•
Allowing dirt or liquid to enter into the electric machine or connection box.
•
Using cables that cannot withstand the maximum currents of the electric machine.
Used technology
The electric machine is a Synchronous Reluctance assisted Permanent Magnet (SRPM) machine. This
technology has several benefits compared to standard permanent magnet (PM) technology and
traditional induction machine (IM) technology. The SRPM technology combines the benefits of PM and
Synchronous Reluctance technology, having increased torque capability over wide speed range and
ability to produce torque to higher speeds. The electric machine efficiency at lower speeds is also good.
The supply current to the machine stator windings create rotating magnetic field, which in turn rotates
the rotor containing permanent magnets. In the synchronous permanent magnet machine, the rotation
of the rotor (shaft) is synchronized with the frequency of the power supply current. The reluctance
technology maximizes the pull-out torque of the machine.
The permanent magnets of the rotor are of salient-pole design, having embedded permanent magnets in
the rotor structure. This structure makes the electric machine mechanically more stable and capable of
higher speed operations. See Figure below illustrating the magnet topology of the electric machine. The
Figure shows the principle only, and is not an exact illustration of the structure.
Machine topology
1Electric machine stator and stator windings
2Electric machine rotor
Danfoss provides electric drive trains for applications in heavy mobile work machines, marine vessels and
buses. The drive trains include all essential components for converting from traditional to hybrid electric
(HEV) or electric vehicle (EV) solutions. Danfoss technology saves fuel and lowers emission and noise
levels.
Overview of the Danfoss drive train system
The electric machines are liquid cooled with water/glycol mixture. For more information, see
Chapter Cooling connections.
A low voltage measurement signal connector is attached to the electric machines. Different temperature
and resolver signals can be read, depending on the machine options chosen. For more information about
the connection, see Chapter Low voltage connections.
The electric machines (some models) can be equipped with one or two anti-condensations heater(s),
depending on the machine type and the option chosen. The heater is used to prevent any water
condensing inside the machine enclosure.
2 Bearing temperature sensors (Option +BTMP1).
3 Air ventilation plug.
There can also be a male shaft or male shaft + flange connection in the N-end of the machine, depending on the
option (+NE1 or +NE2).
User Guide
EM-PMI375
Product overview
Rating plate
4 Connection box containing the power connections.
5 Flange mountings, D-end and N-end.
6 Grease fill connections (+BHS option dependent).
7 Cooling system connections (bores G3/4).
8 Low voltage connector (measurement connector), including low voltage grounding connector.
9 Grease escape connection, D-end and N-end (+BHS option dependent).
10 Lifting points.
11 Additional attachment points.
Each electric machine has a rating plate which can be found on the machine frame. The rating plate
contains machine rating and identification. The rating values in the Figure below are not correct for this
machine. See the rating plate on the machine and data sheets for the correct values.
Rating plate
Rating plate fields
FieldExplanationUnit
1Electric machine product family: EM-PMI or EM-PME
2Electric machine type code and options
Serial No.Serial number
URated voltage
(phase-to-phase AC)
IRated current (AC)I
PRated power (S9) according to IEC60034-1kW
nRated speedrpm
TRated torque (S9) at rated speedNm
PFPower factor
fRated supply frequency at nominal speedHz
Q
c
Pole pairsNumber of magnetic pole pairs of the machine
T
c
MountingAllowed mounting position according to IEC60034-7
MassMass of the electric machinekg
DutyDefined rotating electric machine duty cycles by IEC60034-1 standard
T
amb
IP ratingEnclosure class according to IEC60034-5
CoolingCooling method according to IEC60034-6
RotationDirection of rotor rotation with default phase order. Observed facing the D-end.
Max nMaximum rotation speedrpm
Insul. classTemperature rating (class) of insulation of the electric machine according to IEC60034-1
Temp. classTemperature rating (class) of individual insulation materials of the insulation according to
Bear. / D-end Bearing type (types) in the D-end of the electric machine
Bear. / N-end Bearing type in the N-end of the electric machine
Max. pressure Cooling liquid max pressure
CEDepending on the details of the delivery, the rating plate might not have CE-marking
Rated coolant liquid flowl/min
Rated coolant liquid input temperature°C
Rated ambient temperature°C
IEC60034-1
Tightening torques
Tightening torque tolerance is +/- 5% of the specified tightening torque.
Use threadlocking adhesive for RST bolts.
Do not install dry screws or other fastening equipment.
Add suitable lubrication, for example Wuerth HSP 1400, to prevent excess friction.
ConnectionTorque
Mounting bolts for D-end attachment40 Nm
Mounting bolts for N-end attachment (support or auxiliary components)30 Nm
Connection box mounting screws7 Nm
Connection box cover plate screws4 Nm
Cable lug15 Nm
This Chapter describes design principles that must be taken into account when designing the system
using the electric machine.
Cooling and temperature measurement
Do not operate the electric machine without correctly dimensioned and operating cooling
system.
Mount the electric machine in correct position, see Chapter Allowed mounting position.
When you connect the cooling system make sure that the cooling medium flows freely in and
out from the electric machine with the cooling medium flow equal or higher than rated.
The cooling medium temperature at the inlet of the electric machine must be lower or equal
to the rated temperature.
The electric machines are liquid-cooled using max. 50 % water-glycol coolant. The used cooling method
is IC 9S7Y7 (IEC 60034-6 classification), requiring an external heat exchanger. See also
Chapter Recommended coolants.
See more detailed information about coolant connection bore specifications, required coolant liquid flow
and other specifications in the product data sheet. Rated values can be found from the electric machine
rating plate.
The electric machine has at least one PT100 temperature sensor in the windings. The amount of the
sensors depend on the options chosen. The temperature signal(s) can be read out from the measurement
connector of the machine.
You can connect one temperature signal to the temperature surveillance pin in the inverter (EC-C1200)
and make sure that the inverter has the machine temperature protection feature activated.
The maximum allowed winding temperature of the electric machine is shown in the rating plate and in
the data sheet.
The PT100 temperature sensor characteristics are: resistance 100 Ω at 0 ºC temperature, and the
resistance increases 0.385 Ω per each 1 ºC increase of temperature.
Insulation lifetime
Heat cycles, environment, moisture, vibrations and similar variables have an effect on the
lifetime expectancy of the insulation of the electric machine. The value of the insulation
lifetime expectancy is a calculated value and it is not tested in practice.
The insulation of the electric machine has the following lifetime expectancy.
The electric machine is intended to be powered and controlled with an inverter capable of supplying
three-phase alternating current and that is capable of controlling the electric machine. The electric
machine is not suitable for direct online use.
If the electric machine is driven with an inverter from a supplier other than Danfoss Editron, the electric
machine performance may differ from rated values. The optimum performance of the electric machine is
obtained with Danfoss Editron inverters. These inverters are:
•
Compact and light.
•
Liquid cooled.
•
Tolerant to high mechanical vibration (10 G) and shock (50 G).
•
Efficient, efficiency > 98 %.
•
Reliable, no moving components.
100 000 h if driven with maximum winding temperature of 150°C
EC-C1200
Do not exceed the maximum rotation speed of the electric machine.
The main machine power driving parameters are shown in the machine rating plate. For more
information, contact Danfoss representative.
You can connect one of the temperature signals (from the low voltage connector) to the temperature
surveillance pin in the inverter and make sure that the inverter has the machine temperature protection
feature activated.
Supporting structure requirements
Do not install the electric machine near or in direct contact with easily flammable materials.
The surface of the electric machine can be hot.
The mating housing arrangement of the electric machine must be secure and sufficiently rigid to prevent
vibrations and mechanical failures. Necessary actions should be taken to avoid corrosion on the mating
housing arrangement.
The supporting structure for the electric machine must be such that the electric machine can be
mounted using its allowed mounting positions, see Chapter Allowed mounting positions.
The mounting space must be adequate for the electric machine mounting and possible auxiliary
components. See the length and the diameter data of the electric machine from the product drawing.
Main dimensions of the electric machine are shown in the Figure below (the illustration may differ from
the actual electric machine).
The electric machine has a SAE 3 D-end flange (IM 3001). A SAE 3 flywheel housing is required as mating
flange. The machine's N-end flange (SAE 4 flywheel housing) can be used for auxiliary components or
support.
Length of the electric machine frame (including the connection box(es).
Length of the shaft (from the end of the shaft to the electric machine D-end mounting shoulder).
Diameter of the flange mounting bore circle.
Diameter of the mounting shoulder.
Shaft alignment and load
Improper alignment (misalignment) may result in bearing overloads, premature bearing
failures, vibrations and shaft failures. Flexible coupling does not compensate for excessive
misalignment.
The type of the electric machine shaft is W50x2x24x8f. Recommended female connection counterpart is
of type N50x2x24x9H. The flange type is SAE3.
Alignment between the shaft and mating structure must be accurate.
The misalignment can be parallel or angular misalignment, or combination of those. With parallel
misalignment, the center lines of both shafts are parallel but they are offset. With angular misalignment,
the shafts are at an angle to each other. Figures below illustrate the parallel and angular misalignment.
Parallel alignment of the shaft and mating structure
* The values given might differ between coupling types.
The maximum external force directed to the shaft axially and radially may not exceed
machine specific values. For more information, see document DOC-000454. Calculate the
relevant values with the help of the document.
Contact Danfoss service at https://danfosseditron.zendesk.com/hc/en-gb or send email to
editron.service@danfoss.com to obtain the document.
Heavy equipment. Handle with care during transportation.
Electric machine is shipped in first class condition. It has been inspected and packed correctly to prevent
damage from ordinary handling during shipment. During transportation, shocks, fails and humidity
should be avoided. Protect the cooling holes for transportation.
The weight of the electric machine can be found on the machine rating plate, and in the product data
sheet.
Do not touch the electric machine during the insulation resistance check. Discharge the
electric machine afterwards.
Lifting
Do not touch the electrical terminals when the rotor is rotated. The electrical terminals have
dangerous voltage during rotation. Contact Danfoss representative if the rotor can not be
rotated.
Remove the transportation supports of the electric machine.
Check upon arrival and unpacking
•
The electric machine and the package must be inspected immediately upon arrival. Make sure that
the rating plate data in the cover letter complies with the purchase order. Any external damage (in
shaft-ends, flanges, electrical interfaces and paint) must be photographed and reported immediately.
•
It is recommended to measure the insulation resistance of the electric machine upon arrival, or before
installing the electric machine. Reference value of 150 MΩ shall be exceeded in room temperature,
otherwise contact Danfoss representative. Refer to Chapter Insulation resistance test on page 37.
•
Remove any shaft locks and rotate the shaft. It is normal for the rotation of the shaft to be difficult.
Use correct, adequately dimensioned lifting devices and inspect them before lifting.
Do not lift from the shaft of the electric machine!
The electric machine must not be subject to any external vibrations during storage to avoid damage
•
to the bearings.
Use anti-condensation heaters, if fitted, or direct winding heating to avoid water condensing in the
•
electric machine.
Rotate the shaft of the electric machine by hand monthly at least ten revolutions to prevent grease
•
migration. If necessary, use a tool, for example a spanner. Do not damage the shaft in any case.
Extended storage
Electric machines equipped with relubricable bearings: apply grease before and after long term storage.
It is recommended to inspect the electric machine in storage at periodic intervals. Use attached storage
checklist.
Rotate the shaft of the electric machine once a month.
Keep the electric machine in its installation position while in storage. For example, vertically installed
electric machines should be stored in vertical position.
The following safety and information related symbols appear in this user guide and on the electric
machine.
Risk of electric shock when the connection box is open. When you work with power
connections make sure that electricity is disconnected and rotor rotation is prevented.
Magnetic and electromagnetic fields generated near the current-carrying conductors and
permanent magnets in electric machines represent a health danger to persons with heart
pacemakers, metal implants and hearing aids. Persons with a heart pacemaker, metal
implants or hearing aids must consult a doctor before they enter the following areas:
•
Areas in which electric equipment and parts are operated.
•
Areas in which electric equipment with permanent magnets are stored, mounted, operated
or repaired.
Risk of electric shock when working with the electric machine. Use isolated electric tools.
Only trained and qualified personnel familiar with the relevant safety requirements can work
with the electric machine.
Use correct personal protective equipment when you are near the electric machine.
Read the instructions in this user guide before you install the electric machine.
Following tools are required to install the electric machine:
•
Grease pump.
•
Ratchet torque wrench.
•
Hex head wrench kit with different metric sizes.
•
Socket wrench kit with different metric sizes.
•
Cable gland tightening tool. Size according to cable glands.
•
Cable skinning knife.
•
Crimping tool for cable lugs. Consult cable lug manufacturer for correct size and crimping.
•
Lifting slings with sufficient rated capacity.
•
Lifting eyes. Size according to machine type. See Chapter Lifting on page 32.
Do not touch the electric machine during the insulation resistance check. Discharge the
electric machine afterwards.
Mechanical installation
Measure the insulation resistance of the electric machine before and after the installation of
the electric machine.
Use a voltage of 500 V in the insulation resistance test.
Measure the insulation resistance of the electric machine before and after the installation of the electric
machine. Because of the structure of the electric machine, it is possible that the stator is damaged during
the installation.
If the electric machine is in continuous use, it is recommended to do the insulation resistance test three
or four times a year.
The reference value of 150 MΩ must be exceeded in room temperature. Contact Danfoss representative if
the reference value is not exceeded. Reference value of 150 MΩ has to be exceeded at reference ambient
temperature 25°C (measured with 500 VDC / 1 min Megger).
Allowed mounting positions
If the application is a moving work machine or similar, it is allowed to deviate from the
allowed mounting position for the duration of 30% of the work cycle. This applies to electric
machines with grease lubricated bearings.
It is in some cases possible to make an exception from the limitations of the mounting
positions. Document Allowed bearing loads for EM-PMI machines DOC-000454 gives more
information about this. Contact Danfoss to obtain the document.
See Figures below for mounting limitations of the electric machine.
Allowed deviations from the horizontal mounting limitations
Line typeMeaning
Allowed deviations from the horizontal mounting limitations, continuous operation. (Depicted from
the shaft end.)
Allowed deviations from the horizontal mounting limitations, for the maximum duration of 30% of
the work cycle. (Depicted from the shaft end.)
Do not exceed the maximum axial and radial forces calculated for the shaft.
Document Allowed bearing loads for EM-PMI machines DOC-000454 gives more
information about this. Contact Danfoss to obtain the document.
Do not use the N-end of the electric machine for mounting the electric machine.
Refer to Chapter Allowed mounting positions for the correct mounting positions of the electric
machine.
Mount the electric machine on a correct supporting structure as discussed in Chapter Supporting structure
requirements.
Horizontal assembly
1. Lift the electric machine to the correct mounting position. See Chapter Lifting for details.
2. The electric machine is mounted from its D-end flange (SAE3 transmission housing flange). SAE3
flywheel housing is required as a mating flange.
3. Align the electric machine with the mating housing alignment. See Chapter Shaft alignment and load.
4. Connect the shaft of the electric machine, make sure to use full spline engagement. Lubricate the
spline.
A recommended spline lubricant is a 50/50 compound of a high temperature grease and a
molybdenum disulphide powder. When applied initially and re-applied at proper intervals, it
will help prevent fretting corrosion and premature wear. This lubricant is not soluble in oil
and should be used accordingly. Further products which may be recommended are Molycote,
Metaflux, Never Seeze, Optimol and similar.
5. Attach the mounting bolts. For steel housing the minimum length of the bolt is 35 mm and for
aluminum housing 40 mm. (40 mm and 45 mm for EM-PMI375-T800).
6. The electric machine N-end flange (SAE 4 flywheel housing) can be used for auxiliary components or
support.
Use tightening torque of 40 Nm for D-end bolts and 30 Nm for N-end bolts.
Mechanical mounting connections of the electric machine (horizontal mounting)
1 Shaft of the electric machine; spline structure of the shaft DIN5480W50x2x24x8f.
2 D-end flange (SAE3) and bolt bores for mounting the electric machine.
N-end flange (SAE 4 flywheel housing) with 12x30°xM10x1,5 bores. Depth of the thread is 19 mm. Minimum bolt
thread engagement of 15 mm is required.
3 Bores for the lifting eyes.
Mounting bolts (12 pcs of DIN912 M10). Not included in the delivery.
Shaft (male) in the N-end of the electric machine with option NE2 is DIN5480W50x2x24x8f.
Vertical assembly
In vertical assembly, follow the Steps given in the previous Section Horizontal assembly.
Mechanical mounting connections of the electric machine (vertical mounting)
1 N-end flange (SAE 4 flywheel housing) with 12x30°xM10x1,5 bores. Depth of the thread is 19 mm. Minimum bolt
thread engagement of 16 mm is required.
2 Bores for the lifting eyes, N-end.
3 Shaft of the electric machine; spline structure of the shaft (DIN5480 W50x2x24x8f)
4 D-end flange (SAE3). Use mounting bolts (12 pcs of DIN912 M10, not included in the delivery).
Side mounting holes, +SM1 option
1Side mounting threaded holes M10x1.5, 12 pcs
All side mounting threaded holes (12 pcs) are plugged by default with M10x10, DIN 913, (ISO 4026), SET
SCREW.
Use a normal hexagonal socket screwdriver to open the plugs you need to remove. Note that only plugs
in holes which are going to be used should be removed.
Make sure that cooling liquid runs freely into and out from the electric machine.
To prevent damage to the cooling connectors, refer to the documentation of the
manufacturer for the correct tightening torque of the cooling liquid nipples.
When selecting cooling liquid nipples, choose nipples that can resist galvanic corrosion.
Cooling connectors have G3/4 bores.
Electrical installation
Connect the electric machine properly to the cooling circuit. Make sure that the coolant flow is equal or
higher than rated and the coolant temperature at the inlet of the machine cooling is lower or equal to the
rated temperature. For more information, see Chapter Recommended coolants and product data sheet.
Rated values can be found in the electric machine rating plate.
Aluminum frame water-cooled construction is only to be used with a closed fresh water circulation with
corrosive inhibitor described in the data sheet. The water cooling circuit connection is described in the
data sheet. Use only suitable and high-class connection parts and seals to connect the electric machine to
the water circuit. Check for possible leaks after the piping and joints have been connected.
It is recommended to use coolant connector equipped with o-ring seal or to use sealing washer (for
example Usit or Bonded seals) in the connection. In addition, it is recommended to use thread sealant
(Loctite 577 or similar) at the coolant connections to prevent loosening. Loosening can be caused by
vibration or temperature variations.
The electric machines are equipped with at least three PT100 temperature sensors in the windings. The
amount of the sensors depend on the options chosen. The temperature signal(s) can be read out from
the measurement connector of the machine.
You can connect the temperature signal to the temperature monitoring pin in the inverter (EC-C) and
make sure that the inverter has the electric machine temperature protection feature activated.
Power connections
High voltage connection
Risk of electric shock when connection box is open. When you work with power connections
make sure that electricity is disconnected and shaft rotation is prevented.
When installing the connection box lid, make sure there are no foreign particles between the
connection box lid and the insulation and that all connection box fasteners are in place.
Missing or loose screws can compromise the insulation.
Make sure the power cables exit straight from the terminals and do not rub against the sharp
cable through-holes or other sharp edges which could wear out the cable insulation over
time.
Do not place any excess weight on the connection box lid(s).
The high voltage cables of the electric machine are connected to the connection box(es) of the electric
machine. The Figure below shows the components of the high voltage connection box assembly.
Remove the cover of the terminal box.
1.
Install the power cables.
2.
Install the cover of the terminal box back.
3.
High voltage connection assembly structure
Part NumberQtyDescriptionType
2412Bolt, socket headM6 x 16, ISO 7380, A4-70
251Plate, T=5Gasket extruding
263NutM8, DIN 934, Zinked
273Spring, Disc-D8, DIN 2093, 8,2 x 16 x 0,9
283WasherD8, DIN 125
293Cable glands M25 x 1,5BG225MSTRI Pflitsch
TRI option connection points
Connection diagram
The electric machines are intended to be powered and controlled by three-phase alternating current,
supplied by an inverter or inverters. The electric machine is not suitable for direct online use.
The amount of inverters depends on the electric machine and converter current ratings. See also the
relevant wiring diagrams.
For an electric machine with option SINGLE (one connection box containing one three-phase system), the
electrical connection principle from the inverter is shown in the Figure below.
For an electric machine with option DUAL (two connection boxes each containing one three-phase
system), the electrical connection principles from the inverters are shown in the Figure below.
Connection diagram for DUAL option
For an electric machine with option TRI (three galvanically isolated three-phase systems), the electrical
connection principles from the inverters are shown in the Figure below.
If you are not using the recommended cable lugs, select cable lugs that leave 10 mm gap
between each and every cable lug on the same connection plate.
The pictures are schematic, and the actual components can look different.
This Chapter describes how to assemble screened power cables to the electric machine. See the cable
glands recommendations from the Table below. Cable gland assembly instruction can also be found from
PFLITSCH gland catalog available from http://www.pflitsch.de.
Use correct type of gland for different cable diameters. These are shown in the Table below.
Cut the cable sheath at the distance A from the end of the cable, see Figure below. Pull the cut part of
2.
the sheath partly (length B is from 10 to 15 mm) off the cable as shown in the Figure. The distance A
depends of the length of the cable lug used. Measure with the cable lug that is used and cut to
suitable length.
Install two layers of copper tape on the cable so that the distance B is covered. Use 3M
Copper Foil Tape 1181 or similar.
The maximum distance between the copper tape or the shield (braid) of the cable and the
cable lug or the conductor (which ever is closer), is 10 mm.
Do not remove the cable sheath completely at this point and do not cut the braid screen of
the cable!
Cut length of the cable sheath
™
Insert the cable to the cable gland with slight turning motion. This helps the cable to go through the
3.
spring inside the cable gland. Push the cable gland against the sheath of the cable as shown in Figure
below.
Cut piece of shrink tube and shrink it over the cable lug and braid screen as shown in Figure below.
7.
This is done to keep the braid screen in place and for extra insulation.
The shrink tube must be specified for operating temperature range from -40 ºC to 150 ºC.
Self gluing shrink tube is recommended.
Shrink tube
Insert the cable through the corresponding hole in the connection box and connect the cable lug to
8.
the connection point. Use spring washer between the cable lug and the connection screw or nut.
Example of the connection is shown in Figure below. Do not tighten the connection at this point to
ensure fitting of the cable gland.
Make sure that there is at least 10 mm air gap between the cable lug and other metallic
structures including the braid of the cable. If the air gap is smaller, use extra insulation
shrink tube to cover the lug.
Cable lug connection to the connection box (example only, the connection box may look different)
Screw the cable gland to the connection box as shown in the Figure above. Tighten the cable gland
9.
from the body of the gland. See Chapter Tightening torques.
Tighten from the body of the cable gland with the correct torque. Then tighten the cap of
the cable gland manually, but so that the insulation does not come out of the joint.
Tighten the cable lug. Use tightening torque of 15 Nm.
10.
Repeat the procedure to the other cables and connection box (if the machine includes DUAL or TRI
11.
option).
Check that the phase connections order in the connection box is correct, that is, the corresponding
12.
phases between the inverter and the machine are connected (U, V, W correspond to the L1, L2, L3
phases).
Close the connection box. Tighten the connection box cover screws. See Chapter Tightening
13.
torques. Use thread locking compound that makes it possible to remove the screws. (For example
Loctite 221).
Check the power cable shield grounding, see Chapter Grounding connections.
Low voltage connections
Plug the unused socket holes of the low voltage connector with suitable plugs:
•
DEUTSCH 0413-003-1605 (size 16)
•
DEUTSCH 0413-204-2005 (size 20)
See more information and instructions about DEUTSCH connectors at https://
www.deutschconnector.com/.
Electric machine can have a low voltage connector or optionally a low voltage connection box
(option +LVB1).
The electric machine has a connector or a connection box which is used to read out in-built temperature
and rotation sensor (resolver) data from the electric machine. The temperature data comes from PT100
sensors in the stator windings and in some cases in the bearings. The rating plate has the information
about the options of the electric machine: different options add sensors, and some electric machines do
not have all the sensors. For more information about the options, refer to Chapter Product naming
convention on page 5.
Recommended cable types for low voltage connections
Pin configuration of LV connections (+LVB1 option)
PINDescription
1
2
3
4
5
6
Temperature 1, PT100 (P), windings
Temperature 1, PT100 (N), windings
Temperature 2, PT100 (P), windings
Temperature 2, PT100 (N), windings
Temperature 3, PT100 (P), windings
Temperature 3, PT100 (N), windings
The grounding points on the frame of the electric machine are for safety grounding, and
signal cables and power cable shields have their own grounding points.
The machine enclosure grounding point, safety grounding
Testing the power cable shield grounding (earthing)
The power cable shields are grounded (earthed) through the cable glands to the connection box and
further to the electric machine enclosure. After the cable gland assembly and power cable installations,
and any time when needed, make sure that the grounding (earthing) connections are correct.
1.
Connect one terminal of the measurement device to the cable shield of one power cable (in the
inverter end of the cable)
2.
Connect the other terminal of the measurement device to the cable shield of an other power cable.
You can also use the machine enclosure grounding point for the measurement.
3.
Measure the resistance between the two cable shields or between the cable shield and the enclosure
grounding point.
4.
Change the measurement device terminal(s) to the shield of different power cable and repeat the
measurement until all cables have been measured.
Testing the low voltage (measurement signal) cable shield grounding (earthing)
The low voltage (measurement signal) cable shield is connected to the grounding (earthing) point. After
cable installation, and any time when needed, make sure that the grounding (earthing) connection is
valid.
1.
Connect one terminal of the measurement device to the low voltage cable shield (in the nonmachine end of the cable).
2.
Connect the other terminal of the measurement device to the machine enclosure grounding point.
3.
Measure the resistance between the cable shield and the enclosure grounding point.
Do not run the electric machine when an anti-condensation heater is in use.
Water condensing inside the electric machine enclosure can result in failure or corrosion of the electric
machine. This often happens in cooler temperatures or higher humidity areas typically in marine
environment, when the machine is not running.
The electric machine can be equipped with anti-condensation heater to avoid condensation issues. The
anti-condensation heater (+HEAT1) or heaters (+HEAT2) are factory assembled. The installed heater may
not be used when the electric machine mains are switched on or when the electric machine is running.
The installed anti-condensation heater must be supplied with 230 Vac power. The heater connector used
is HUMMEL Twilock connector, illustrated in Figure below.
Connection of the heater element
1L
2N
3PE
If the electric machine has an anti-condensation heater and failure is suspected, contact Danfoss
representative.
Only trained and qualified personnel familiar with the relevant safety requirements are
allowed to operate the electric machine.
Do not use the electric machine without properly dimensioned and operating cooling system.
Maximum operation temperature, current and rotational speed of the electric machine must
not be exceeded to avoid permanent damage.
The surface of the electric machine might be hot. Do not touch the electric machine during
operation.
Entanglement hazard! Do not touch the electric machine during operation.
Use the anti-condensation heater, if fitted, when the electric machine is not in use. This
prevents condensation and possible damage to the electric machine.
Use sufficient personal protective equipment when you are near the electric machine.
Read the instructions in this user guide before you install the electric machine.
The electric machine should be used for its intended purpose only and within limits specified by the
manufacturer, concerning:
•
Loading.
•
Cooling.
•
Speed range.
•
Service interval.
•
Ambient condition such as temperature and moisture.
The electric machine is designed for the following conditions:
•
Ambient temperature limits: -40°C...+65°C.
•
Maximum altitude 1000 m above sea level.
•
Maximum coolant liquid temperature at the inlet of the coolant circuit, see product data sheet.
•
Coolant liquid must be water- glycol mixture with maximum of 50 % glycol content. See
Chapter Recommended coolants.
If electric machine operation limits are exceeded, please contact Danfoss representative.
Condition monitoring during operation
Recommended lubricants
Supervise the electric machine during operation to make sure that the electric machine
operates correctly and has a designed lifetime.
If you notice any deviations from the normal operation, for example elevated temperatures,
noise or vibration, stop the electric machine. Find the reason for the deviation and repair the
electric machine. Refer to Chapter Troubleshooting on page 69.
Maximum temperature of the bearings of the electric machine is:
120°C.
The maximum allowed winding temperature of the electric machine is shown on the rating
plate and in the data sheet.
Do not mix different types of greases!
Greased for life bearings do not need relubrication during their lifetime. Grease relubricable bearings
(BHS option) need regular greasing. For further information, see Chapter Bearings and lubrication on page
63.
The recommended grease type for the machine bearings is SKF LGHP-2 or equivalent. LGHP-2 is high
performance, high temperature bearing grease. For further information, see http://www.skf.com/.
Ethylene glycol is a toxic compound. Avoid exposure to the coolant.
Copper ions concentration of more than approx. 0.06 ppm causes copper induced pittingcorrosion. Do not use copper components in the cooling system.
Hard piping made of metal is recommended for the coolant instead of soft piping as rubber
hoses.
Use correct personal protective equipment when you handle the coolant.
Emergency operation
The electric machines are designed to work properly with water based coolant. Plain water with
appropriate corrosive inhibitor is acceptable, for example 50 % water- 50 % glycol coolant.
Glycol coolant options:
•
Ethylene glycol based Glysantin® G48® (includes also corrosion inhibitors).
•
Propylene glycol based coolants, like Splash® RV&Marine antifreeze.
The electric machine should be operated within the operation limits and in the conditions specified by
the manufacturer. However, it can be used with some limitations in the following fault/emergency
situations.
Cooling of the electric machine fails
The cooling system failure can be caused by dregs (sediment) accumulating to the cooling system tubes.
Try opening the possible blockage by changing the coolant flow direction. See also Chapter Cooling
system maintenance.
If the cooling of the electric machine fails, limited operation is still possible with no coolant flow. The
operation speed must be limited to half (1/2) of the rated speed and maximum 20 % of the nominal
torque may be used. In such case, the electric machine may be operated for maximum one hour. Repair
the cooling system as soon as possible. For further information, contact Danfoss representative.
The temperature measurement of the electric machine fails
The operation temperature of the electric machine is measured by PT100 temperature sensors in the
electric machine windings. The temperature signals can be read out from the measurement connector of
the electric machine, and connect to the temperature surveillance pin in the inverter for example. In case
of a temperature measurement sensor failure in the electric machine, an additional PT100 sensor can be
mounted close to the end of the windings at the low voltage (measurement signal) connector opening.
1. Remove the low voltage (measurement signal) connector from the electric machine enclosure. Be
careful not to damage the cables and joints.
2. Mount (glue) an additional PT100 temperature sensor close to the end of the windings at the
opening. Use resin/glue specified for correct temperatures (Temp.class in the rating plate, class F /
155 ºC).
3. Connect the PT100 sensor to the low voltage connector (replace the failed sensor connection by the
new connection).
4. Remount the low voltage connector to its place.
When reading the temperature (resistance) values from the additional sensor, add +15ºC to the
measured value. This gives more correct estimation of the inner temperature of the electric machine. In
case of the temperature measurement failure and using additional temperature sensor, replace the
electric machine as soon as possible, but no later than in two months.
Danfoss service contact information
Contact Danfoss service at https://danfosseditron.zendesk.com/hc/en-gb or send email to
editron.service@danfoss.com.
This Chapter contains necessary information for the qualified and trained personnel to carry out regular
maintenance work.
Do not disassemble the electric machine. Only procedures described in this user guide may be
done.
Only trained and qualified personnel familiar with the relevant safety requirements are
allowed to do maintenance to the electric machine.
Risk of electric shock when the connection box is open.
Voltage may be connected to the anti-condensation heater.
Use correct personal protective equipment when you are near the electric machine.
Read the instructions in the user guide before you start to work with the electric machine. To
make sure that the operation of the electric machine is safe and reliable, obey the
maintenance instructions.
Regular maintenance
Inspect the electric machine at regular intervals.
Do not attempt to tighten bolts or screws that are not discussed in this user guide and that are
not needed for normal installation and maintenance procedures. The sealing of the bolts and
screws can break.
Correct supervision and maintenance of the electric machine makes sure that the electric machine has
reliable operation and designed lifetime.
Never open or remove the watertight ventilation plugs. Clean them only from the outside.
Risk of electric shock if the electric machine is cleaned against instructions allowing water to
go in to the electric machine.
Bearings and lubrication
Keep the electric machine clean. For cleaning, use non-abrasive and non-corrosive cleaning products.
Make sure that the detergent may be used for aluminum.
When pressure washing the electric machine, make sure that the water spray does not directly hit the
gaskets.
Ventilation plugs
Grease relubricable bearings
The grease relubricable bearings need regular greasing. Follow the relubrication interval and
instructions described in this Chapter.
Grease can cause skin irritation and eye inflammation. Follow all safety precautions specified
by the manufacturer of the grease.
Make sure that the automatic greasing and the oil lubrication function correctly after you
start the electric machine.
The bearing type of the electric machine can be found on the rating plate of the electric
machine.
It is recommended to have a piping for the grease exiting the electric machine. The grease
exit hole is often in an inconvenient location when the electric machine is installed.
The mechanical bearing lifetime (grease relubricable bearings) of the electric machine is shown below. It
depends on the bearing operation temperature and rotation speed.
Electric machine with grease relubricable bearing option
The expression of L
in bearing lifetime information is a standard way of expressing the lifetime and
10
means the time period at the end of which 90% of the bearings are still reliably working. Grease
lubricated bearings (+BHS option) need regular greasing. This is due to the limited lubricant (grease)
lifetime in operation conditions, and is shorter time period than the actual bearing lifetime.
The standard bearing type for EM-PMI375-T1100 is 6214/C3 (non-insulated bearing, grease lubricated).
See the recommended lubricant in Chapter Recommended lubricants on page 59.
Greased for life (BGL) bearing option
Greased for life bearings (BGL option) do not need relubrication during their lifetime.
The standard bearing type for EM-PMI375-T200, T500 and T800 is 6211-2RS1/C3WT (non-insulated
bearing, greased for life) or SKF 6211 2RS1/HC5C3WT (insulated bearing).
The lifetime of the bearing depends on the mounting position of the electric machine. The lifetime
depends also on the rotation speed of the electric machine and the temperature of the bearing. The
bearing lifetime is a combination of both mechanical bearing lifetime and bearing grease lifetime, and is
shown in the figures below, both for horizontal and vertical mounting.
Bearing lifetime with greased for life bearings, horizontal mounting
Bearing lifetime with greased for life bearings, vertical mounting
The expression of L
in bearing grease lifetime information is a standard way of expressing the lifetime
10
and it means the time period at the end of which 90% of the bearings are still reliably lubricated and
working.
The information of bearing lifetime and bearing grease lifetime are approximations only. The
bearing lifetime and bearing grease lifetime in customer application may vary. Danfoss is not
responsible for the actual bearing lifetime in use. For more information contact Danfoss.
Bearing relubrication
Beware of rotating parts. Do not touch the electric machine during operation.
The surface of the electric machine can be hot. Use correct protective equipment (heat
resistant gloves) when you handle the electric machine.
The information of bearing lifetime and bearing grease lifetime are estimations only to
provide a magnitude of them. The bearing lifetime and bearing grease lifetime in customer
application may vary. Danfoss is not responsible for the actual bearing lifetime in use. For
further information, contact Danfoss representative.
The maximum relubrication interval in operation is six months. The amount of grease per
relubrication is 20 g.
The relubrication interval depends on the used rotation speed and bearing temperature, and is
presented in the Figure below. The different curves represent different bearing temperatures. The higher
the temperature is and the higher the rotation speed is, the lower the relubrication interval is.
Relubrication interval of the machine (BHS option) compared to rotation speed and bearing temperature
Relubrication interval of EM-PMI375-T1100 (BHS option) compared to rotation speed and bearing
temperature, horizontal installation
For more information about the location of grease nipples and grease escape holes, see
Chapter Connections and interfaces on page 22.
Bearing relubrication:
It is normal if no grease exits the electric machine. This is because the cavities inside the
electric machine can hold a lot of grease.
Make sure that the electric machine has reached its operating temperature.
1.
Remove the plugs from the grease escape holes.
2.
Open the grease nipple plugs.
3.
Use grease piston to enter specific amount of grease into the grease nipple.
4.
If possible, let the electric machine run approximately one hour to let the old grease exit.
5.
Install the plugs on the grease nipples and on the grease escape holes.
6.
Cooling system maintenance
It is recommended to change the direction of the coolant liquid flow yearly. This is done by changing the
order of the coolant connections, or changing the coolant pump direction. The reason for changing the
coolant flow direction is to prevent possible dregs (sediment) accumulating to the cooling system.
The quality of the coolant must be checked yearly. The mixture of coolant fluid must be according to
specification. See Chapter Recommended coolants.
Make sure that the mating structure is not damaged. Do not pluck any bores or use at headed
bolts or rods for pushing the electric machine out of the mating structure.
For dismounting the electric machine, follow the Steps below.
See Chapter Mounting the electric machine on page 39. Dismount the electric machine in reverse order.
1. Prepare the electric machine for lifting, for more information refer to Chapter Lifting on page 32.
Support the electric machine with lifting slings when dismounting.
2. Loosen the mounting bolts. For more information refer to Chapter Mounting the electric machine on
page 39.
3. If force is required, use the bores in D-end flange to push the electric machine out from the mating
structure, or use some other method that does not damage the electric machine.
4. Lift the electric machine off. Support the electric machine when lifting.
Some difficulties may occur while operating the electric machine. Possible causes and actions are given in
the Table below. If the situation occurs, it should be corrected as soon as possible. These instructions do
not cover all details or variations in the equipment nor provide information for every possible condition
to be met in connection with installation, operation or maintenance.
For more information, contact Danfoss service at https://danfosseditron.zendesk.com/hc/en-gb or send
email to editron.service@danfoss.com.
Maintenance and service of the electric machine is limited to the procedures described in this user guide.
If the electric machine has service parts available, you can find them in Chapter Service parts on page 70.
For further information, go to https://danfosseditron.zendesk.com/hc/en-gb or send email to
editron.service@danfoss.com.
The recommended service parts are listed in this Section. Quantity describes the number of components
in a single electric machine. Maintenance procedures not described in this user guide require special
tools and instructions. Contact Danfoss for more information and purchasing.
5Bolt, socket headM8 x 30 | DIN 912 | A4-80
5Seal, washerBonded seals, U 8,7 x 13 x 1
5Bolt, socket headM8 x 25 | DIN 912 | A4-80
1Wear sleeveSpeedi sleeve SKF 99196
5Bolt, socket headM8 x 30 | DIN 912 | A4-80
5Seal, washerBonded seals, U 8,7 x 13 x 1
5Bolt, socket headM8 x 25 | DIN 912 | A4-80
1Wear sleeveSpeedi sleeve SKF 99196
2Grease nipple (both in D-end and N-end)DIN 71412, M8 x 1
2Cover, grease nippleTecalemit 351010022
2Plug for Grease escape hole (D/N-end)M12 x 1,5 24-HFM-12
2Plug for grease inlet holeM8x1, 24-HFM-08
12Bolt, socket headM6 x 16 | ISO 7380 | A4-70
3Nut (for cable attachment)M8 | DIN 934 | Zinked
3Spring, disk (for cable attachment)D8 | DIN 2093 | 8,2 x 16 x 0,9
3Washer (for cable attachment)D8 | DIN 125
1Ventilation plugPMF 100444 Metal Vent
Electric machine enclosure grounding connected☐☐☐
Low voltage cable shield grounding connected ☐☐☐
Power cable shield connection resistances to ground
(electric machine enclosure) measured and valid
Low voltage cable shield grounding resistances measured
and valid
Notes:
☐☐☐
☐☐☐
•
•
•
•
•
•
•
•
•
•
•
•
•
Date:
Signature:
Do not try to tighten bolts or screws that are not discussed in the product manual and that are not
needed for the normal installation procedures. Sealing of the screws may break.
Electric machine weekly maintenance checklist
Date:
Electric machine and customer information
Customer:Electric machine type (from the rating plate):
Customer reference:Electric machine serial number:
Service reference:Date installed:
Electric machine yearly maintenance checklist (continued)
AcceptanceN.APASSFAIL
Coolant flow direction changed and connection checked☐☐☐
Coolant quality as specified☐☐☐
Used coolant:
Functioning of the cooling system in general☐☐☐
Tightness of the tubing and connections (no leakages)☐☐☐
Cleanliness of the ventilation plug☐☐☐
Grounding
Power cable shield connection resistances to ground
(electric machine enclosure) checked
Low voltage cable shield grounding resistances checked☐☐☐
Connection to grounding points checked☐☐☐
Notes:
☐☐☐
•
•
•
•
•
•
•
•
•
•
•
•
•
Do not try to tighten bolts or screws that are not discussed in the product manual and that are not
needed for the normal installation procedures. Sealing of the screws may break.
For cleaning instructions, refer to Chapter Cleaning on page 63.
Used service parts
Part descriptionPart typeQuantityItem (order) number
Part descriptionPart typeQuantityItem (order) number
_
Notes:
•
•
•
•
•
•
•
•
•
•
•
•
Date:
Signature:
Electric machine storage checklist
Date:
Electric machine and customer information
Customer:Electric machine type (from the rating plate):
Customer reference:Electric machine serial number:
Service reference:Date installed:
This storage checklist is used when storing the electric machine. Regular inspection is required. See
specifications for storage in this User Guide or in the Data Sheet.
Fill in the date of each inspection to the Table below.
Storage checklist
ProcedureDateDateDateDateDate
Storage base as
specified (vibration
free)
Storage temperature
and humidity as
specified
Electric machine type
and serial number is
correct
Electric machine
supported correctly
Corrosion protection of
non-painted surfaces
(for example shaft-end
and grounding points)
2800 East 13th Street
Ames, IA 50010, USA
Phone: +1 515 239 6000
Danfoss
Power Solutions Trading
(Shanghai) Co., Ltd.
Building #22, No. 1000 Jin Hai Rd
Jin Qiao, Pudong New District
Shanghai, China 201206
Phone: +86 21 2080 6201
Products we offer:
Hydro-Gear
www.hydro-gear.com
Daikin-Sauer-Danfoss
www.daikin-sauer-danfoss.com
Cartridge valves
•
DCV directional control
•
valves
Electric converters
•
Electric machines
•
Electric motors
•
Gear motors
•
Gear pumps
•
Hydraulic integrated
•
circuits (HICs)
Hydrostatic motors
•
Hydrostatic pumps
•
Orbital motors
•
PLUS+1® controllers
•
PLUS+1® displays
•
PLUS+1® joysticks and
•
pedals
PLUS+1® operator
•
interfaces
PLUS+1® sensors
•
PLUS+1® software
•
PLUS+1® software services,
•
support and training
Position controls and
•
sensors
PVG proportional valves
•
Steering components and
•
systems
Telematics
•
Danfoss Power Solutions is a global manufacturer and supplier of high-quality hydraulic and
electric components. We specialize in providing state-of-the-art technology and solutions
that excel in the harsh operating conditions of the mobile off-highway market as well as the
marine sector. Building on our extensive applications expertise, we work closely with you to
ensure exceptional performance for a broad range of applications. We help you and other
customers around the world speed up system development, reduce costs and bring vehicles
and vessels to market faster.
Danfoss Power Solutions – your strongest partner in mobile hydraulics and mobile
electrification.
Go to www.danfoss.com for further product information.
We offer you expert worldwide support for ensuring the best possible solutions for
outstanding performance. And with an extensive network of Global Service Partners, we also
provide you with comprehensive global service for all of our components.
Local address:
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alterations can be made without subsequent changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.