Measuring a temperature 4
Temperature sensor type EKS 111 5
Temperature sensor type EKS 211 5
Positioning sensors 6
Evaporator positions 6
S1 and S2 sensors 7
How to mount S2 sensor on a vertical pipe 7
How to mount S2 sensor on a horizontal pipe 7
Measuring a pressure 8
Positioning sensors 11
Pressure transmitter in liquid line with pulse snubber 12
Electrical connections 13
Pulse width modulation electronically operated expansion valve type AKV 13
Stepper motor electronically operated expansion valve type ETS 13
Digital Input (DI) / Digital Output (DO) 14
No power 14
Split sensors and AKV 14
External Start/Stop of regulation 14
Controlling 15
Input and output 15
Op eratio n 15
Evaporator controls 16
Parameters 16
What is the controller doing...? 17
Quick start 17
With the use of electronic controllers such as
Danfoss ADAP-KOOL® products the installation requirements must
be followed to ensure the electrical connections, pressure and
temperature sensors and any communication network
connections are correct so that the unit operates as intended.
The following are some general guidelines:
y Pressure temperature inputs
It is very important that the correct type of temperature sensor
is used for the temperature range, sensing application, and the
temperature sensor signal is compatible with the electronic
refrigeration controller, (please see the technical manual for the controller to ensure the correct temperature sensor is used).
y Sensor types
The product programme of temperature sensors for
refrigeration consists of two main families: AKS and EKS.
These sensor elements are based on the three technologies:
Pt, PTC and NTC.
Temperature sensor type:
AKS11, AKS12, AKS21, AK-HS 1000
Pt sensor
These sensors are also known as RTD´s, Resistance Temperature
Detectors. The sensing elements is made of platinum, example
PT1000, where the number describes the nominal resistance at
0°C, here 1.000Ω. The resistance increases 4Ω per 1°C. The sensor
characteristic is linear. In Danfoss these sensors are the type AKS.
The tolerance of a Pt1000 sensor is less than ± (0.3 + 0.005 T).
This translates into a temperature error of less than 0.5 degree for
refrigeration control.
The Pt1000 sensor must be used for food safety logs and
regulation of superheat as they conform to the tolerance
requirements of EN 60751 Class B and therefore satisfy the HACCP
requirements of EN 12830, EN 13485.
Extension of sensor cables
When extending a sensor cable, the new resistance value of the
longer cable may give rise to indication error. It is recommended
that the total cable resistance should not exceed 2Ω
corresponding to an indication error of 0.5°C (Pt1000Ω).
Note
Up to 50m use 0.75mm²
Up to 100m use 1.5mm²
Up to 150m use 2.5mm²
The typical resistance values for cables are:
y -2.4Ω/100m for core cross-sectional area of 0.75mm².y -1.2Ω/100m for core cross-sectional area of 1.5mm².y -0.7Ω/100m for core cross-sectional area of 2.5mm² .
The PTC sensor got their name as the sensing element has a
positive temperature coecient.
The sensing element is a semi conductor, example PTC1000
where the number describes the nominal resistance at 25°C.
The sensor characteristic is almost linear but is not standardized,
the manufacturer can dene their own characteristics.
In Danfoss the EKS111 is a PTC1000 type.
The PTC temperature sensor type EKS111 must not be used for
food safety logs as they do not conform to the requirements
EN 12830, EN 13485 or regulation of superheat because they do
not have the needed accuracy of +/- 0.5K.
R (typ.) OhmTem p. °CError KTe mp ° F
1679100+/-3.5212
157590194
147580176
13787015 8
128 66014 0
119 65012 2
111140104
10293086
99025+/-1.377
9512068
8771050
807032
740-1014
677-20-4
617-30-2 2
562-40-40
510-50-58
485-55+/-3.0- 67
Temperature sensor type EKS 211
NTC sensor
The sensing element in NTC´s is a thermistor having a
negative temperature coecient.
The sensor characteristic is described by a number, that as with
PTC´s, indicates the nominal resistance at 25°C, and by a β-value
which denes the curve characteristic.
Due to the variety of characteristics it is not possible to develop a
standard NTC sensor that can be used for all controller types.
Hence, when making service you must install an “original” NTC
sensor to ensure the controller to work properly.
Temperature sensor type EKS 211
NTC characteristic matches controllers type EKC and AK-CC.
The NTC temperature sensor type EKS211 must not be used for
food safety logs as they do not conform to the requirements
EN 12830, EN 13485 or regulation of superheat because they do
not have the needed accuracy of +/- 0.5K.
R_nom OhmTem p. °CTemp °F
631.080176
743.275167
878.970158
104 465149
12476014 0
149555131
18035012 2
218645113
266540104
32663595
40293086
50002577
62462068
78551559
99511050
12696541
16330032
21166-523
27681-1014
36503-155
48 614-20-4
65333-25-13
88766-30-22
12179 5-35- 31
16915 7-40-40
DKRCC.PF.000.G2.02 / 520H8626 5
Fitter notes – Electronic Controls
Positioning sensors
It is very important that during the installation process and also
during maintenance schedules the correct position and mounting
of all temperature sensors is in line with the recommendations.
Incorrect mounting can cause faulty temperature signals to be
used by the controller which will result in, in-correct operation of
the refrigeration application.
Ø=
Ø=
125
in.
8
12 - 16mm
341
1
8
18 - 26mm
in.
12
1
2
3
4
12
1
2
3
4
Evaporator positions
Nomenclature of temperature tensors & pressure
transmitters in Danfoss controllers
y S1: Temperature sensor measuring evaporating temperature
(Can be used as a less accurate measurement of
evaporating temperature without the need for a pressure
transmitter)
y Pe: Pressure transmitter measuring true evaporating pressure
(preferred method)
y S2: Suction temperature outlet of the evaporatory S3: Air entering the evaporator y S4: Air leaving the evaporator y S5: Defrost termination temperature sensor when defrost is
being used
y S6: Is used as a product sensor (type AK-HS1000,HACCP
compliance for food safety)
Pack positions
y Po: Pressure transmitter - Suction pressurey Pc: Pressure transmitter - Discharge pressurey Ss: Temperature sensor - Suction temperature to work out
suction superheat in connection with suction pressure Po
y Sd: Temperature sensor - Discharge temperaturey Sc3: Temperature sensor - Ambient temperature of the air
entering the condenser
Ø=6.5
S6S4
MM
S3
PoPc
S
S
NB!
Pe
S2
S5
Sd
S
CS
6 DKRCC.PF.000.G2.02 / 520H8626
Fitter notes – Electronic Controls
S1 and S2 sensors
S1 and S2 sensors measuring saturation temperature and
temperature of superheat gasses.
y S1: This sensor is measuring the evaporating temperature of
the evaporator and therefore must be mounted on the
coldest point on the evaporator, normally the rst return
bend.
The reading should be checked against the suction gauge
pressure to conrm that the pressure and temperature
relationship is correct otherwise the control of superheat
will be incorrect.
Where and how to mount the S1 sensor
S1
S1S1A
S1
B
B
y S2: Sensor function is to measure the temperature of the
refrigerant exiting at the evaporator’s pipe outlet and, has
thus, the same goal as a thermostatic expansion valve’s
bulb and should be placed exactly according to the same
rules.
Only a Pt1000 AKS11 type sensor must be used, as it is the
only type providing the necessary accuracy needed for
this purpose.
How to mount S2 sensor on a vertical pipe
Steel pipes
If steel pipes are used on the evaporator outlet the superheat
signal it must be measured using a pocket sensor “S2” to get a
correct signal. This is absolutely necessary to get a good injection
control.
Copper pipes (exceeding 50mm)
When pipe dimensions go up so does the material thickness.
Bigger thickness also means greater temperature dierence
between inner and outer temperatures. You should use
immersion pocket sensors here also.
Where and how to mount the S2 sensor
Mount on vertical pipe if possible not too close to bend
and not to far from evaporator outlet
AA
Cut A-A
Cut A-A
A
S2
S2 B
The sensor should be
mounted rmly on the
pipe using heat-conducting
paste and the sensor
should be insulated
S2
Pipe isolation
S2 sensor
Oil splash can disturb the signal
How to mount S2 sensor on a horizontal pipe
The sensor should be
When mounted on horizontal pipe the position depends on the
size of the pipe.
y Mount at 1 o’clock when diameter is between 1/2 and 5/8inch
(12-16mm).
y Mount at 2 o’clock when diameter is between 3/4 and
1- 1/8inch (18-26mm).
y Mount at 4 o’clock when diameter is over 1- 1/2inch (38mm).y Use immerse pocket sensor if you want to measure on steel
pipe.
B
B
Cut B-B
mounted rmly on the
pipe using heat-conducting
paste and the sensor
should be insulated
S2
S2 sensor
Pipe
Isolation
DKRCC.PF.000.G2.02 / 520H8626 7
Fitter notes – Electronic Controls
Measuring a pressure
It is very important that the correct type of pressure transmitter is
used for the pressure range, sensing application, and the pressure
transmitter signal is compatible with the electronic refrigeration
controller, (please see the technical manual for the controller to ensure correct pressure transmitter is used).
AKS ratiometric
Typ eOperating range [bar]Permissible working pressure
AKS 2050 -1 to 59100
-1 to 99150
-1 to 159250
PB [b ar]
AKS 32, ver sion 1-5V
Operating rangeMax working pressure PB
LP
HP
AKS 32, ver sion 0-10V
LP
HP
AKS 33, version 4-20mA
LP
HP
-1 --> 6 [bar]33 [bar]
-1 --> 12 [bar]33 [bar]
-1 --> 20 [bar]40 [bar]
-1 --> 34 [bar]55 [bar]
Operating rangeMax working pressure PB
-1 --> 5 [bar]33 [bar]
-1 --> 9 [bar]33 [bar]
-1 --> 21 [bar]10 [b ar]
-1 --> 39 [bar]60 [bar]
Operating rangeMax working pressure PB
-1 --> 5 [bar]33 [bar]
-1 --> 6 [bar]33 [bar]
-1 --> 9 [bar]33 [bar]
-1 --> 12 [bar]33 [bar]
-1 --> 20 [bar]40 [bar]
-1 --> 34 [bar]55 [bar]
0 --> 16 [bar]40 [bar]
0 --> 25 [bar]4 0 [bar]
8 DKRCC.PF.000.G2.02 / 520H8626
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.