Danfoss Electronic Controls Service guide

MAKING MODERN LIVING POSSIBLE
Electronic Controls
Fitter’s Notes
www.danfoss.com
Fitter notes – Electronic Controls
2 DKRCC.PF.000.G2.02 / 520H8626
Fitter notes – Electronic Controls
Contents
Measuring 4
Electrical connections 13
Pulse width modulation electronically operated expansion valve type AKV 13 Stepper motor electronically operated expansion valve type ETS 13 Digital Input (DI) / Digital Output (DO) 14 No power 14 Split sensors and AKV 14 External Start/Stop of regulation 14
Controlling 15
Input and output 15 Op eratio n 15 Evaporator controls 16 Parameters 16 What is the controller doing...? 17 Quick start 17
What is wrong....? 18
Communication 19
Why...? 19 How…? 19 Cable selection / termination 20 Requirement to installation 20 Cable 21 Addressing 24 Trouble shooting 24
DKRCC.PF.000.G2.02 / 520H8626 3
Fitter notes – Electronic Controls
R
NTC
PTC
Pt
T
Measuring
Measuring a temperature
Pressure temperature inputs
With the use of electronic controllers such as Danfoss ADAP-KOOL® products the installation requirements must be followed to ensure the electrical connections, pressure and temperature sensors and any communication network connections are correct so that the unit operates as intended. The following are some general guidelines:
y Pressure temperature inputs
It is very important that the correct type of temperature sensor is used for the temperature range, sensing application, and the temperature sensor signal is compatible with the electronic refrigeration controller, (please see the technical manual for the controller to ensure the correct temperature sensor is used).
y Sensor types
The product programme of temperature sensors for refrigeration consists of two main families: AKS and EKS. These sensor elements are based on the three technologies: Pt, PTC and NTC.
Temperature sensor type: AKS11, AKS12, AKS21, AK-HS 1000
Pt sensor
These sensors are also known as RTD´s, Resistance Temperature Detectors. The sensing elements is made of platinum, example
PT1000, where the number describes the nominal resistance at 0°C, here 1.000Ω. The resistance increases 4Ω per 1°C. The sensor characteristic is linear. In Danfoss these sensors are the type AKS. The tolerance of a Pt1000 sensor is less than ± (0.3 + 0.005 T). This translates into a temperature error of less than 0.5 degree for refrigeration control. The Pt1000 sensor must be used for food safety logs and regulation of superheat as they conform to the tolerance requirements of EN 60751 Class B and therefore satisfy the HACCP requirements of EN 12830, EN 13485.
Extension of sensor cables
When extending a sensor cable, the new resistance value of the longer cable may give rise to indication error. It is recommended that the total cable resistance should not exceed 2Ω corresponding to an indication error of 0.5°C (Pt1000Ω).
Note
Up to 50m use 0.75mm² Up to 100m use 1.5mm² Up to 150m use 2.5mm²
The typical resistance values for cables are:
y -2.4Ω/100m for core cross-sectional area of 0.75mm². y -1.2Ω/100m for core cross-sectional area of 1.5mm². y -0.7Ω/100m for core cross-sectional area of 2.5mm² .
AKS 11, AKS 12, AKS 21, AK-HS 1000
°C ohm °C ohma
0 1000.0 1000.0
1 1003.9 -1 996.1 2 1007.8 -2 992.2 3 1011.7 -3 988.3 4 1015.6 -4 984.4 5 1019.5 -5 980.4 6 1023.4 -6 976.5 7 1027.3 -7 972.6 8 1031.2 -8 968.7 9 10.35.1 -9 964.8 10 1039.0 -10 960.9 11 1042.9 -11 956.9 12 1046.8 -12 953.0 13 1050.7 -13 949.1 14 1054.6 -14 945.2 15 1058.5 -15 941.2 16 1062.4 -16 937.3 17 1066.3 -17 933.4 18 1070.2 -18 929.5 19 1074.0 -19 925.5 20 1077.9 -20 921.6 21 1081.8 -21 917.7 22 1085.7 -22 913.7 23 1089.6 -23 909.8 24 1093.5 -24 905.9 25 1097.3 -25 901.9 26 1101.2 -26 898.0 27 1105.1 -27 894.0 28 1109.0 -28 890.1 29 1112.8 -29 886.2 30 1116.7 -30 882.2 31 1120.6 -31 878.3 32 1124.5 -32 874.3 33 1128.3 -33 870.4 34 1132 -34 866.4 34 1132.2 -34 866.4 35 1136.1 -35 862.5 36 1139 -36 858.5 37 1143.8 -37 854.6 38 1147.7 -38 850.6 39 1151.5 -39 846.7 40 1155.4 -40 842.7 41 1159.3 -41 838.8 42 1163.1 -42 835.0 43 1167.0 -43 830.8 44 1170.8 -44 826.9 45 1174.7 -45 822.9 46 1178.5 -46 818.9 47 1182.4 -47 815.0 48 1186.3 -48 811.0 49 1190.1 -49 807.0 50 1194.0 -50 803.1
approx 3.9 ohm/K
4 DKRCC.PF.000.G2.02 / 520H8626
Fitter notes – Electronic Controls
Temperature sensor type EKS 111
PTC sensor
The PTC sensor got their name as the sensing element has a positive temperature coecient. The sensing element is a semi conductor, example PTC1000 where the number describes the nominal resistance at 25°C. The sensor characteristic is almost linear but is not standardized, the manufacturer can dene their own characteristics.
In Danfoss the EKS111 is a PTC1000 type. The PTC temperature sensor type EKS111 must not be used for food safety logs as they do not conform to the requirements EN 12830, EN 13485 or regulation of superheat because they do not have the needed accuracy of +/- 0.5K.
R (typ.) Ohm Tem p. °C Error K Te mp ° F
1679 100 +/-3.5 212
1575 90 194
1475 80 176
1378 70 15 8
128 6 60 14 0
119 6 50 12 2
1111 40 104
1029 30 86
990 25 +/-1.3 77
951 20 68
877 10 50
807 0 32
740 -10 14
677 -20 -4
617 -30 -2 2
562 -40 -40
510 -50 -58
485 -55 +/-3.0 - 67
Temperature sensor type EKS 211
NTC sensor
The sensing element in NTC´s is a thermistor having a negative temperature coecient. The sensor characteristic is described by a number, that as with PTC´s, indicates the nominal resistance at 25°C, and by a β-value which denes the curve characteristic. Due to the variety of characteristics it is not possible to develop a standard NTC sensor that can be used for all controller types. Hence, when making service you must install an “original” NTC sensor to ensure the controller to work properly.
Temperature sensor type EKS 211
NTC characteristic matches controllers type EKC and AK-CC. The NTC temperature sensor type EKS211 must not be used for food safety logs as they do not conform to the requirements EN 12830, EN 13485 or regulation of superheat because they do not have the needed accuracy of +/- 0.5K.
R_nom Ohm Tem p. °C Temp °F
631.0 80 176
743.2 75 167
878.9 70 158
104 4 65 149
1247 60 14 0
1495 55 131
1803 50 12 2
2186 45 113
2665 40 104
3266 35 95
4029 30 86
5000 25 77
6246 20 68
7855 15 59
9951 10 50
12696 5 41
16330 0 32
21166 -5 23 27681 -10 14
36503 -15 5
48 614 -20 -4
65333 -25 -13
88766 -30 -22
12179 5 -35 - 31
16915 7 -40 -40
DKRCC.PF.000.G2.02 / 520H8626 5
Fitter notes – Electronic Controls
Positioning sensors
It is very important that during the installation process and also during maintenance schedules the correct position and mounting of all temperature sensors is in line with the recommendations. Incorrect mounting can cause faulty temperature signals to be used by the controller which will result in, in-correct operation of the refrigeration application.
Ø=
Ø=
125
in.
8
12 - 16mm
341
1
8
18 - 26mm
in.
12
1
2
3
4
12
1
2
3
4
Evaporator positions
Nomenclature of temperature tensors & pressure transmitters in Danfoss controllers
y S1: Temperature sensor measuring evaporating temperature
(Can be used as a less accurate measurement of evaporating temperature without the need for a pressure transmitter)
y Pe: Pressure transmitter measuring true evaporating pressure
(preferred method)
y S2: Suction temperature outlet of the evaporator y S3: Air entering the evaporator y S4: Air leaving the evaporator y S5: Defrost termination temperature sensor when defrost is
being used
y S6: Is used as a product sensor (type AK-HS1000,HACCP
compliance for food safety)
Pack positions
y Po: Pressure transmitter - Suction pressure y Pc: Pressure transmitter - Discharge pressure y Ss: Temperature sensor - Suction temperature to work out
suction superheat in connection with suction pressure Po
y Sd: Temperature sensor - Discharge temperature y Sc3: Temperature sensor - Ambient temperature of the air
entering the condenser
Ø=6.5
S6 S4
M M
S3
Po Pc
S
S
NB!
Pe
S2
S5
Sd
S
CS
6 DKRCC.PF.000.G2.02 / 520H8626
Fitter notes – Electronic Controls
S1 and S2 sensors
S1 and S2 sensors measuring saturation temperature and temperature of superheat gasses.
y S1: This sensor is measuring the evaporating temperature of
the evaporator and therefore must be mounted on the coldest point on the evaporator, normally the rst return bend. The reading should be checked against the suction gauge pressure to conrm that the pressure and temperature relationship is correct otherwise the control of superheat will be incorrect.
Where and how to mount the S1 sensor
S1
S1S1A
S1
B
B
y S2: Sensor function is to measure the temperature of the
refrigerant exiting at the evaporator’s pipe outlet and, has thus, the same goal as a thermostatic expansion valve’s bulb and should be placed exactly according to the same rules. Only a Pt1000 AKS11 type sensor must be used, as it is the only type providing the necessary accuracy needed for this purpose.
How to mount S2 sensor on a vertical pipe
Steel pipes
If steel pipes are used on the evaporator outlet the superheat signal it must be measured using a pocket sensor “S2” to get a correct signal. This is absolutely necessary to get a good injection control.
Copper pipes (exceeding 50mm)
When pipe dimensions go up so does the material thickness. Bigger thickness also means greater temperature dierence between inner and outer temperatures. You should use immersion pocket sensors here also.
Where and how to mount the S2 sensor
Mount on vertical pipe if possible not too close to bend and not to far from evaporator outlet
AA
Cut A-A
Cut A-A
A
S2
S2 B
The sensor should be mounted rmly on the pipe using heat-conducting paste and the sensor should be insulated
S2
Pipe isolation
S2 sensor
Oil splash can disturb the signal
How to mount S2 sensor on a horizontal pipe
The sensor should be
When mounted on horizontal pipe the position depends on the size of the pipe.
y Mount at 1 o’clock when diameter is between 1/2 and 5/8inch
(12-16mm).
y Mount at 2 o’clock when diameter is between 3/4 and
1- 1/8inch (18-26mm). y Mount at 4 o’clock when diameter is over 1- 1/2inch (38mm). y Use immerse pocket sensor if you want to measure on steel
pipe.
B
B
Cut B-B
mounted rmly on the pipe using heat-conducting paste and the sensor should be insulated
S2
S2 sensor
Pipe
Isolation
DKRCC.PF.000.G2.02 / 520H8626 7
Fitter notes – Electronic Controls
Measuring a pressure
It is very important that the correct type of pressure transmitter is used for the pressure range, sensing application, and the pressure transmitter signal is compatible with the electronic refrigeration controller, (please see the technical manual for the controller to ensure correct pressure transmitter is used).
AKS ratiometric
Typ e Operating range [bar] Permissible working pressure
AKS 2050 -1 to 59 100
-1 to 99 150
-1 to 159 250
PB [b ar]
AKS 32, ver sion 1-5V
Operating range Max working pressure PB
LP
HP
AKS 32, ver sion 0-10V
LP
HP
AKS 33, version 4-20mA
LP
HP
-1 --> 6 [bar] 33 [bar]
-1 --> 12 [bar] 33 [bar]
-1 --> 20 [bar] 40 [bar]
-1 --> 34 [bar] 55 [bar]
Operating range Max working pressure PB
-1 --> 5 [bar] 33 [bar]
-1 --> 9 [bar] 33 [bar]
-1 --> 21 [bar] 10 [b ar]
-1 --> 39 [bar] 60 [bar]
Operating range Max working pressure PB
-1 --> 5 [bar] 33 [bar]
-1 --> 6 [bar] 33 [bar]
-1 --> 9 [bar] 33 [bar]
-1 --> 12 [bar] 33 [bar]
-1 --> 20 [bar] 40 [bar]
-1 --> 34 [bar] 55 [bar]
0 --> 16 [bar] 40 [bar]
0 --> 25 [bar] 4 0 [bar]
8 DKRCC.PF.000.G2.02 / 520H8626
Loading...
+ 16 hidden pages