Danfoss Electric Heating Mats Installation guide

IMPORTANT!
DO NOT CROSS OR CUT THE RED CABLE
REMEMBER TO MEASURE, VERIFY AND
RECORD THE RESISTANCE
Danfoss
BRINGING WARMTH TO LIFE
LX
Installation Manual
Electric Heating Mats
Manuel d'installation
Tapis chauffants électriques
Manual de instalación
Mallas calefactoras eléctricas
Table of Contents
LX Floor Heating System....................................... .......................................................................................................................................... 2
Typical Installations and Cautions ................................................................................................................................................................ 3
General Installation Guidelines ..................................................................................................................................................................... 4
Warranty................................................................................................................................................................................................................. 9
APPENDIX A: Typical Electrical Wiring
Spécifications techniques des tapis chauffants Danfoss LX .................................................................................................................... 10
Installations typiques et mises en garde......................................................................................................................................................... 11
Instructions d'installation d’ordre général ..................................................................................................................................................... 12
.
.......................................................................................................................................................... 26
Garantie ...................................................................................................................................................................................................................... 17
ANNEXE A: Câblage Électrique Typique........................................................................................................................................................... 26
Sistema de calefacción por suelo radiante DanfossLX ............................................................................................ 18
Instalaciones y precauciones típicas. ........................................................................................................................................................... 19
Pautas generales de instalació ....................................................................................................................................................................... 20
Garantía .................................................................................................................................................................................................................. 25
APÉNDICE A: Cableado Eléctrico Típico
....................................................................................................................................................... 26
...............................
Copyright 2009 Danfoss Inc.
088L3380 - 06/09
TEL: 866-676-8062. FAX: 905-285-2055
1
Danfoss LX Floor Heating System
CAUTION!
It is important that this equipment is installed only by qualified electricians who are familiar with the proper sizing, installation, construction and operation of floor warming system and the hazards involved. The heating mat is designed for under floor heating purposes only.
Note!
The installation shall be in accordance with the manufacturer’s instructions and national and local codes. The installation shall be in accordance with Part 424-J, American National Standard Institute / National Fire Protection Association (ANSI/NFPA70), National Electrical Code (NEC) and Canadian Electrical Code (CEC), Part 1. Danfoss recommends GFCI for heating cable in normally wet areas (i.e. bathrooms, showers, kitchens).
LX Mat Specifications
Type: Voltage: Output: Heating Element Size:
Twin conductor 120V, 240V 12W/sq.ft. (130 W/m ) Width: 2’
2
Length: Refer to product label Height: approx 1/8” (4 mm)
Cold Lead Bending radius: Wire insulation: Casing: Max. Allowable Temp.: Min. Installation Temp.:
Note: Operating the 240V mat at 208V reduces power output to approximately 9W/sq.ft. (25% reduction)
10’ (3.0 m) Minimum 3/4” (19 mm) FEP, Teflon
TM
PVDF 212°F (100°C) 40°F (5°C)
WARNING:
Remember to measure resistance.
Little Buzzer
Connection 120V
Phase - Black Neutral - Blue Ground - Shield
Connection 240V
Phase - Black Phase - Blue Ground - Shield
MONITOR YOUR INSTALLATION!
USE THE LITTLE BUZZER CONTINUITY
ALARM (PART#088L0028)
The resistance should be measured between the two conductors, blue and black. Compare the measured resistance to the resistance listed on the product label (on the power lead).
Record the resistance on your warranty card.
infinity.
Copyright 2009 Danfoss Inc.
Also, measure the resistance between the blue, black and shielding/ground wire. Both should read
088L3380 - 06/09
TEL: 866-676-8062. FAX: 905-285-2055
2
Danfoss LX typical installations and applications
Directly on plywood:
Directly on concrete.
Alternative method: self-leveling cement is recommended for large surfaces and the following floor materials: engineered wood, laminate, floating floors, vinyl, linoleum and carpet.
Ceramic tiles
Thermostat sensor Thinset cement adhesive
fanD oss LX Plywood on joists Joists Insulation (optional)
Ceramic tiles
Thin set cement adhesive Danfoss LX
Thermosta Concrete
t sensor
Warning:
Consult the manufacturer for information on special installation requirements for wood, laminate and vinyl or linoleum flooring.
Caution!
=Read the instructions carefully before installing
LX mat
=Do not install LX mat in walls or ceilings;
=The mat must be embedded in mortar,
thinset, concrete or similar material;
=The minimum installation temperature is
40°F (5°C);
=Never cut the red heating wire;
=It is recommended to use AWG 16 or greater
copper wire only if you need to extend the cold lead
=Never install the LX mat such that two red
heating wires touch, cross or overlap;
=Measure the resistance between the blue,
black and shielding/ground wire. Both should read infinity.
lRe memb er to al ways me asur e, ver ify and
record the actual resistance throughout the install ation process (out of the box, af ter installation, before thin set cement or self-leveler application and after installation of floor tiles) and compare all reading to the ratings on the product label.
lRemember to check that the supply voltage
matches the voltage of the Danfoss LX mat;
lRemember to place the labels as written in
this instruction;
lOnly for indoor installation;
lMetal struct u res or materials used for the
support of or on which the Danfoss LX mat is insta lled m ust be gro u nded in a ccorda n ce with CSA Standard C22.1, section 10 and the NEC.
Please consult the factory for any other questions or advice;
Copyright 2009 Danfoss Inc.
088L3380 - 06/09
TEL: 866-676-8062. FAX: 905-285-2055
3
General Installation Guidelines
1
2
Step 1. PLAN LAYOUT
Make a sketch layout or a floor plan of the room; include all permanent furnishings such as toilets, bathtubs, appliances, cabinetry, etc. Indicate all dimensions required to determine the available floor are a and the position of th e LX thermo s t at.
TIP: Danfoss recommends installation is documented with photos to note the location of connections and the sensor.
Step 2. TRANSFER LAYOUT TO FLOOR
Draw an outline of the layout on the room floor including a foot print of all furnishings that are not yet installed. Unroll the first few feet of the LX mat. The starting point of the cable must be placed within 10 ft. from the thermostat. Mark the position of the connection point between the power lead and the red LX heating cable. This connection must be concealed in thinset or self-leveling cement. When using a floor temperature sensing thermostat, mark the sensor position in the middle of 2 heating cables, about 10 in. (25cm) away from the wall (within the heated area), as close as possible to the thermostat.
Copyright 2009 Danfoss Inc.
3A
088L3380 - 06/09
Step 3. INSTALL SENSOR
(recommended in conduit, part#19809099 included) If using a floor temperature sensing thermostat, install the sensor now, either in conduit tube, or directly to the subfloor. It is recommended that the sensor be installed in conduit tube. This will allow the sensor to be easily replaced in the unlikely event of failure.
The sensor and/or tube needs to be installed between the thermostat wall box and the sensor position. The conduit tube must be partially countersunk into the subfloor. Cut a channel 5/16” deep by 5/16” wide in the floor and wall up to the thermostat large enough to accommodate the sensor conduit. The conduit has to go from the thermostat and minimum of 10 “ away from the wall towards the middle of the floor.
TEL: 866-676-8062. FAX: 905-285-2055
4
4
IMPORTANT: the sensor conduit must be centered in the cable loop (between two red heating wires).
Seal the end of the conduit that is placed in the floor with a piece of duct tape. This will prevent thinset from penetrating the conduit.
Use duct tape to hold the sensor conduit into the groove to prevent it from floating up when the mortar or thinset is poured.
If the sensor is installed directly in the mortar bed, use duct tape to secure to subfloor.
Step 4. PREPARE SUBFLOOR SURFACE
Clean and vacuum the floor thoroughly and remove dust and debris from the floor that may damage the heating cable or reduce adhesion.
Ensure that the subfloor is secure and stable. Carefully fill in all cracks to prevent any potential damage to the new tiles resulting from shifts in the subfloor.
5A
(Optional) To ensure maximum adhesion, apply a primer or sealer as recommended by the thinset or self-leveling cement manufacturer. If using a primer, ensure that the entire floor is covered. Allow the primer to dry thoroughly before proceeding to the next steps.
Step 5A. MEASURE THE RESISTANCE
Use a digital ohm meter to measure the resistance of the Danfoss LX mat and compare it to the resistance listed on the product label. The resistance should be measured between the two conductors, blue and black. Compare the measured resistance to the resistance on the product label, located 3 inches from the splice, on the cold lead. Also, measure the resistance between the blue, black and shielding/ground wire. Both should read infinity.
Record the measured resistance on the warranty card. Documenting the resistance at each stage of in stallatio n is req uired for warra nty purpose s.
Copyright 2009 Danfoss Inc.
088L3380 - 06/09
TEL: 866-676-8062. FAX: 905-285-2055
5
5B
Step 5B. INSTALL THE LX MAT
An adhesive has been added to the bottom of the mat which will prevent the mat from moving during installation. Start by placing the mat such that the connection point and the temperature sensor are in their intended positions and bring the power cable to the thermostat or connection box.
Begin unrolling the LX mat evenly across the floor outside the areas that you marked previously. The adhesive on the mat is made such that the mat may be mo ved s ever al t i mes b e fore i t l ose s i ts adhesiveness. When you reach the next wall, cut the grey mesh, turn the mat, and begin rolling in the desired direction.
NEVER CUT OR SHORTEN THE RED HEATING CABLE!
Ensure that the LX mat is in full contact with the subfloor at all times. Avoid walking on the heating mat. If this is not possible, use shoes with soft soles.
When approaching obstacles (toilets, cabinets, etc.), carefully remove some of the red heating cable f r o m t h e m a t a n d l e a d t h e c a b l e around the obstacle. In some cases pieces of the grey mesh will be cut away entirely. Remember to never cut the red cable. Use hot melt glue or a thin strip of tape to secure the loose cable to the floor.
Copyright 2009 Danfoss Inc.
088L3380 - 06/09
TEL: 866-676-8062. FAX: 905-285-2055
6
6
Step 6. INSTALL FLOOR COVERING
Measure the resistance in the mat and record it on the warranty certificate. It is highly recommend to take
photographs of the installed LX mat before installing the flooring.
ENSURE THAT THE SENSOR CONDUIT HAS BEEN PROPERLY INSTALLED BEFORE PROCEEDING (see Step 3).
In the case of tiles, proceed with the installation of the tiles by covering the heating cables with a layer of thin-set cement as directed by the tile manufacturer. Ensure that the thin-set mortar covers the entire height of the heating cable as the tiles are installed. In the case of a wood, engineered or laminate floor covering, it is recommended that the flooring manufacturer be contacted. For wooden floors, a minimum of 3/16 in. of self-leveling cement over the heating cable is recommended. Ensure that all moisture in the self-leveling cement has been fully eliminated in accordance with the drying times recommended by the manufacturer (consult the manufacturer for exact drying time).
Once the thin-set cement has dried, measure the resistance in the mat and record it on the warranty certificate. The LX mat must not be turned on until the thin- set cement has fully dried. A minimum of seven (7) days is recommended.
Copyright 2009 Danfoss Inc.
088L3380 - 06/09
Step 7. CONNECT POWER SUPPLY AND THERMOSTAT
(See Appendix A)
The connection of the power supply and the LXstat GFCI thermostat must be done by a qualified electrician in accordance with the National Electrical Code (NEC) and the Canadian Electrical Code (CEC). The electrician should also feed the sensor cable into the installed conduit and connect it to the thermostat.
TEL: 866-676-8062. FAX: 905-285-2055
7
Loading...
+ 22 hidden pages