Stepper valve driver EKF series is used where stepper valves must be accurately controlled typically in commercial
air conditioning, heat pumps, commercial refrigeration and food retail applications.
Features
• Support both Bipolar and Unipolar stepper motor valves
• Driven by analog input signal
• Fast installation and setup
• Lost step prevention
• Open circuit detection
• LED indication for valve movement and alarm/warnings
• On board DIP switch for quick selection
• Plug and play
• 4 pole terminal block and JST-XHP 5 pin connections
EKF series stepper valve drivers can be used in application where accurate control of stepper motor valves are
needed using analog input signals (0-10V, 0-5V, 4-20 mA, 0-20 mA) from unit programmable controllers. The
product can be used for both Bipolar and Unipolar type valves. General applications include use in commercial air
conditioning, heat pumps, commercial refrigeration and food retail application
There are both 4 pin terminal and JST 5 pin terminal available on the board per stepper drive output.
Only one of the terminals should be used per valve.
Do not connect valves to both 4 pin terminal and JST terminal of the same stepper driver output.
Power sharing
EKF can share power from the same source with a battery backup or unit controller only if battery backup/unit
controller ports are galvanically isolated.
Danfoss recommends to use EKE 2U as the preferred battery backup device.
NOTE:
EKE 2U can only support 2 valves for emergency closing, thus EKE 2U should not be shared with more than one EKF
2A or more than two EKF 1A.
The basic product conguration can be done through DIP switch present on the hardware.
EKF 1A supports 1 stepper drive output and 1 Dip switch for settings.
EKF 2A supports 2 stepper drive output and 2 Dip switch for settings.
Figure 5: DIP switch
The image above shows a schematic of a dip switch
Each DIP switch consists of 8 switches.
The below table shows what each Dip switch section represents.
Table 3: Dip switch section
Steps to follow to congure EKF using Dip switch:
1.
Disconnect the EKF from power supply.
2.
Connect the valves and AI inputs to EKF.
3.
Make the needed settings on the EKF dip switch.
4.
Turn the power back on to EKF.
5.
EKF is ready to use with the new settings
NOTE:
Any changes made to EKF dip switch while EKF is powered ON will result in warning and the new settings are not
active. In case of the above error switch the power OFF and then ON the EKF. The newly made settings will now be
active.
The tables below can be used to help select dip switch positions.
Valve selection (Switch 1-5)
Green denotes ON position of DIP switch
Only applicable for EKF 2A When using Manifold valves.
Dip switch 1 for stepper driver 1 should be selected to base valve type.
Eg: ETS C should be selected in Dip switch 1 if ETS Colibri is used in manifold operation.
ETS 250/400 should be selected if using ETS 500P/ETS 800P.
Dip switch 2 for stepper driver 2 should be selected as manifold valve (Group H).
While setting Dip switch 2 as manifold valve EKF automatically recognize that it is using only 1 Analog input to
control both valves and by default AI1 is used as the analog input. Analog sharing function is automatically
activated.
Analog input selection (Switch 7 & 8)
Green denotes ON position of DIP switch
Figure 7: DIP analog input selection
Analog sharing selection (Switch 6)
Green denotes ON position of DIP switch
Figure 8: DIP analog sharing selection
NOTE:
Analog sharing is used only in EKF 2A.
Analog sharing can be done to run 2 valves using the same analog input.
If stepper driver 1 should use analog input from AI2 (AI2 is meant for stepper driver 2 analog input).
Then Dip switch 1 should have switch 6 at position ON.
EKF 2A will then use AI2 signal to control stepper valve 1.
If stepper driver 2 should use analog input from AI1 (AI1 is meant for stepper driver 1 analog input).