Danfoss EKE 400 Data sheet

Data Sheet
vaporator and room control
E Type EKE 400
For industrial refrigeration applications
1
ppendix A
See A
2
Pulse Width Modulating valves like Danfoss type AKV or AKVA.
The EKE 400 controller is a dedicated controller
or evaporators typically used in industrial
f refrigeration applications. EKE 400 will be able to manage the complete operation in cooling and defrost mode.
Features:
• Approved and qualied b refrigeration applications
• One product covering multiple valve
congurations
• HMI includes wizard for easy setup
• Multiple EKE 400 can be interconnected for signal sharing via integrated CANBUS.
(defrost coordination etc.)
• Easy to connect to third party equipment like PL
C via integrated MODBUS
• EKE 400 can be connected to AK-SM 800 series
• EKE 400 is available without HMI to save cost
• One remote HMI can interface multiple EKE 400
• One EKE 400 cover both 24 V AC and 24 V DC
• One EKE 400 cover wide voltage and frequency range; 85 – 265 V AC, 50/60 Hz
• Flexible Analog input. Cover both Pt-1000/NTC temperature sensor and 4 – 20 mA / 1 – 5 V Pressure transmitter
• 2 Digital output out of 8 Digital output is solid state for PWM
• EKE 400 with HMI includes multilanguage suppor Spanish)
• International units supported. Metric and Imperial
• HMI will during setup, lter out irrelevant parameters or conversely, show parameters that are relevant based on earlier selection
(2)
(puls) valves
t (English, Chinese, Portuguese,
(1)
, temperature sharing
AI306444073210en-000801
Evaporator and room control, type EKE 400
Application
igure 1: EKE 400 without/with HMI
F
For industrial refrigeration applications the Danfoss EKE 400 can control the operation of the valves and the fans for ev
aporators to achieve optimal cooling mode and defrost sequence for an ecient, safe and trouble-free operation
of the evaporators, complying with IIAR
This means:
• Controls operation of the valves and the fans for each evaporator
• Controlling and optimizing defrost sequence and performance
• Applicable for defrosting ooded ev
• Supports various defrost methods: Hot gas defrost by pressure control or liquid drain, water/brine defrost, and electrical defrost.
• EKE 400 is using industry terminology in both the HMI feed line etc.)
(3)
safety recommendations for hot gas defrost.
aporators, including Ammonia and CO
(4)
in
terface and associated literature (wet return line, liquid
2
EKE 400 is available both with and without HMI. The HMI contains a graphical display and a six push button to operate and navigate through the menu system. A menu wizard will guide the user through basic conguration questions. Based on parameter selections, irrelevant parameters will be ltered out and minimize time at commissioning the EKE 400
As EKE 400 is a dedicated controller for industrial refrigeration it will have full support of Danfoss industrial refrigeration valves
(5)
:
• ICF valve station
• ICM motorized valve
(6)
• ICS servo valve with constant pressure control pilots like CVP
• OFV o
verow valve
• ICLX 2-step gas powered solenoid valve
• ICSH dual position solenoid valve
• ICFD Defrost module
• Various solenoid valves; EVRA, EVRAT, EVRS, EVRST, ICS with EVM, ICF with ICFE
Product function features
roduct function features
P
Examples of applications supported by EKE 400:
• Flooded ammonia/CO2/HCFC/HFC
• Direct expansion (DX) ammonia/CO2/ HCFC/HFC
• Superheat Control by
Fixed Superheat referenceLoad dened rMinimum Stable Superheat (MSS)
eference (LoadAP)
3
International Institute of Ammonia Refrigeration
4
Human Machine Interface (HMI) is the interface between the EKE 400 controller and the user.
5
Competitors valves may be used with EKE 400.
6
EKE 400 can support: ETS 6, ETS, KVS, ETS Colibri®, KVS Colibri®, CTR, CCMT valves. See A
© Danfoss | Climate Solutions | 2021.03
ppendix B
AI306444073210en-000801 | 2
Evaporator and room control, type EKE 400
• Modulating Thermostat (MTR) or simple ON/OFF
• Media temperature control of suction line valve with motorized valve (Danfoss type ICM/ICAD or similar)
• Media temperature control of suction line valve with servo valve (Danfoss type ICS/CVE/ICAD or similar)
• Pressure control of suction line valve with motorized valve (Danfoss type ICM/ICAD or similar)
• Pressure control of suction line valve with servo valve (Danfoss type ICS/CVE/ICAD or similar)
• Modulating Thermostat (MTR) by modulating the valve (Danfoss type AKV/AKVA) or similar in the liquid line
• Defrost
• Support of Multiple Defrost methods
Hot Gas defrost by pressureHot Gas defrost by liquid drainDefrost by water or brineIndividual defrost schedules by single weekdays, Saturdays and Sundays
• Defrost start
Defrost start by PLC via MODBUS or Digital InputDefrost start by time interval (time since last defrost start)Defrost start according to accumulated cooling timeDefrost start via defrost schedules and Real Time Clock (RTC)Forced manual defrost via HMI or by PLC via MODBUS
• Defrost stop
Defrost stop on time durationDefrost stop on temperature
• Separate Drip tray control (separate from main Hot Gas valve)
• Emergency cooling - failsafe operation
• Safe startup after power failure
• Product temperature alarm option
© Danfoss | Climate Solutions | 2021.03 AI306444073210en-000801 | 3
ABCDEFG
H
Soft-opening
CHV
CHV
EVRST
ICSH
ICLX
ICF
ICFE
ICFSICFR
ICFF
ICFC
ICFW
ICFD
ICF
ICFS
ICFE
ICFS
CHV
CHV
ICS
ICLX
EVM
ICF
ICFE
ICFSICFR
ICFF
ICFC
ICFW
ICF
ICFS
ICFS
ICFE
ICFD
ICS
EVM
Soft-opening
CHV
CHV
EVRST
ICSH
ICLX
EVM
CVP
ICS
ICF
ICFE
ICFSICFR
ICFF
ICFC
ICFW
CHV
CHV
ICS
ICLX
EVM
ICF
I
CFE
ICFSICFR
ICFF
ICFC
ICFW
EVM
CVP
ICS
ICS
EVM
A
B B
B B
C C
C C
A
D D
D D
A A
E E
E E
F F
F F
G G
G G
H H
H H
Danfoss
80G8136
Soft opening
Evaporator
Drip tray
Wet return line
Defrost drain line
Liquid feed line
Hot gas defrost line
Drip tray line
Evaporator and room control, type EKE 400
Figure 2: Flowchart
© Danfoss | Climate Solutions | 2021.03
AI306444073210en-000801 | 4
Danfoss
80G8231
Evaporator and room control, type EKE 400
DX and Hot gas defrost
X and Hot gas defrost
D
EKE 400 oers the possibility to control DX applications and combine with Hot gas defrost across all the possible valves available. E.g. EKE 400 can support DX and CO2, combined with Hot gas defrost with ICF valve stations.
Figure 3: Application sketch
© Danfoss | Climate Solutions | 2021.03 AI306444073210en-000801 | 5
Evaporator and room control, type EKE 400
MTR (Modulating TheRmostat) in Liquid Line Flooded systems
TR (Modulating TheRmostat) in Liquid Line Flooded systems
M
As for DX systems, EKE 400 has an adapted function of MTR also for ooded systems. Selecting this function, EKE 400 wil be able to control the room temperature much more accurate than a traditional ON/OFF temperature control. EKE 400 will also equalize the load on the system to get better operating conditions. MTR requires PWM (Pulse Width Modulating) valves like Danfoss type AKV or AKVA in the liquid line. Typical industrial applications with the refrigerant Ammonia or CO2 is in scope.
Figure 4: MTR in Liquid line ooded systems
Media temperature and pressure control - suction line
M
edia temperature and pressure control - suction line
EKE 400 will be able to control valves in the wet suction return line. The control mode can be either temperature or pressure. Support of Danfoss Industrial Refrigeration Valves like ICM with ICAD and ICS/CVE/ICAD can be combined with multiple defrost methods, including Hot Gas.
Figure 5: Media temperature and pressure control - suction line
(7)
7
Same basic media temperature functions as in EKC 361, but with updated and optimized algorithm. See A
© Danfoss | Climate Solutions | 2021.03
ppendix C
AI306444073210en-000801 | 6
Home Active alarms Old Alarms reset
Observe: Text examples only
Controller info
From any status screen press ENTER f
or 2 sec. to access main menu
Press ESCAPE to go back to status Press UP to decrease digit Press DOWN to increase digit
Press ENTER to login
Press LEFT / RIGHT to go to next / previous digit
Press ESCAPE to go one lev
el back
Parameter
Password level
Functions
Password level 0
Level 0 will only allow to see the screens: "Status screen 1", "Active alarms", "Alarm Reset" and "Controller info"
G07
Password level 1
Level 1 will give access to see all parameters and sub menus, but no settings can be changed.
G08
Password level 2
Enter password for level 2 access. Level 1 will give access to see all parameters and sub menus. Some settings can changed
.
G09
Password level 3
Enter password for level 3 access. Level 1 will give access to see all parameters and sub menus. All settings can changed
.
Evaporator and room control, type EKE 400
Product specication
Basic operation
asic operation: Conguration and daily operation of EKE 400 is done via the built-in HMI or via a remote
B
connected HMI. The display supports multiple languages and engineering units.
Status screens: Get an overview of how the system is running in the status screens. Use the LEFT / RIGHT buttons to view the status screens.
Figure 6: Status screen
Password
ee EKE 400 Wizard, Parameterlist, for further details further details on Password levels and user rights
S
Table 1: Password level
Conguration
f the I/O conguration can not be met, after the Wizard is completed, a warning will be displayed
I
Go to IO c
onguration or IO status and go through Digital output/input and Analog output/input
© Danfoss | Climate Solutions | 2021.03
AI306444073210en-000801 | 7
Danfoss
80G8010
Evaporator and room control, type EKE 400
Identify the IO with and exclamation mark “!” and recongure it.
Setup overview
T
here are two ways in which the controller can be set up:
Wizard
• Here you will be led through a series of selected parameters that are commonly needed to be c start up. This will also mean faster setup for many applications.
• Please observe, that some parameters not included in the Wizard may still need to be congured. this must then be done from the complete Parameter list
Parameter list
• Here a complete list of all parameters can be found
ongured at every
perating principles:
O
1.
Select position using arrow keys
2.
Select using “Enter”
3.
Use the “X” to return
Figure 7: EKE 400
© Danfoss | Climate Solutions | 2021.03
AI306444073210en-000801 | 8
ABC
A B C
Hold “Enter” down for 2 seconds to come to password entry
The default password upon delivery is 300. Use the arrow keys to set the password. End by pressing “Enter”
Select a set-up method. End by pressing “Enter”
Danfoss
80G8223
Actual Cutout
Therm. setpoint
Actual Cutin
Control temp
Therm. Neutral zone
Evaporator and room control, type EKE 400
Figure 8: Start screen upon delivery
Temperature control
F
igure 9: Temperature control
For ON/OFF thermostat and F
looded and DX application
One, two or three temperatures sensors, normally located in the cool room, can be connected to EKE 400. The number of sensors depends normally on the size of the room.
© Danfoss | Climate Solutions | 2021.03
AI306444073210en-000801 | 9
Temperature
Valve OD
SH
Time
Time
Temp setpoint
(T04)
SH ref
Danfoss
80G8224
Evaporator and room control, type EKE 400
If more than one temperature sensor have been selected, then the thermostat function can be selected to control
emperature from the average or the highest temperature from the temperature sensors.
t
A Temperature setpoint (T04) and a Neutral zone(T05) are entered in EKE 400. Neutral zone divided by 2 will give Cut-in and Cut-out temperature of the thermostat, normally the liquid line valve ON/OFF.
Modulating thermostat (MTR)
DX only Observe: The MTR function must not be enabled in a system containing only 1 evaporator
Modulating thermostat (MTR regulation maintains a more constant temperature and also equalize the load on the system to get better operating conditions:
• Each of the individual evaporator sections is controlled individually using a modulating thermostat function.
• A Temperature setpoint (T04) and a Neutral zone(T05) must be set as with an ON/OFF thermostat.
TR is modulating the cooling capacity to match the cooling demand.
M
In the pull-down phase then the temperature is well above the MTR set point cooling capacity is at maximum and superheat is controlled to be on superheat reference. When temperature is getting close to the MTR reference (typical 4 K) the cooling capacity gradually reduce so that the temperature can be stable on the MTR reference.
The MTR reference is dened by Temperature setpoint (T04).
Figure 10: Modulating thermostat
Superheat reference calculation methods
n superheat mode the controller will control the superheat to be stable and closer to the superheat reference. This
I will give the optimal utilization of heat exchanger and thereby maximum cooling capacity. If superheat is too low, the ow in the expansion is decreased and superheat will be higher.
© Danfoss | Climate Solutions | 2021.03
AI306444073210en-000801 | 10
Danfoss
80G8225
TT
P
S2
TT, S2
P
Pt1000 temperature sensor
Pressure transmitter
Danfoss
80G8226
EKE oper
ating
envelope
Pressure (P)
Enthalpy (H)
Superheat r
eference
Evaporator and room control, type EKE 400
Figure 11: Actual superheat = S2 - T0
P can be display
ed in [Bar] or [psi]. It a refrigerant has been entered in parameter “r20,Refrigerant“ then the calculated evaporating temperature, converted from the pressure transmitter, is called T0 (or Te).
Superheat reference can be calculated based on following 3 dierent methods:
MSS (Minimum Stable Superheat)
The superheat control algorithm will attempt to regulate the superheat down to the lowest stable value between the minimum superheat setting, “Min SH” and the maximum superheat setting, “Max. SH”.
LoadAP Superheat
LoadAP is an abbreviation of “load dened reference”. LoadAP will adjust reference to be higher if load is higher. Load is indicated by the OD of valve. LoadAP is a kind of preprogrammed MSS curve. This method will give a robust SH reference and can in many cases be the best t for systems.
Fixed Superheat
This feature is used in a system where a stable xed superheat is required.
• MSS - Parameter N01, SH ref. mode is set to: Adaptive SH ctrl
• LoadAP - Parameter N01, SH ref. mode is set to: Load dened c
trl
• Fixed Superheat - Parameter N01, SH ref. mode is set to: Fixed SH ref.
Figure 12: Superheat reference
© Danfoss | Climate Solutions | 2021.03
AI306444073210en-000801 | 11
Danfoss
84B1488
100 %
Qo
Unstable r
e
g
ion
(wet)
10 %
Superheat
Danfoss MSS
Danfoss LoadAP
Fixed SH, 3rd party SH control
Danfoss
84B1487
100 %
10 %
40 %
Superheat
Q o
Un
stable r
egion
(wet)
Stable
r
egion (dry)
Min. SH Max. SH
Danfoss MSS
Evaporator and room control, type EKE 400
Figure 13: Comparison between SH reference
MSS
he controller will search for the minimum stable superheat between an upper and lower boundary. If the
T superheat has been stable for a period, the superheat reference is decreased. If the superheat becomes unstable. the reference is raised again. This process continues as long as the superheat is within the bounds set by the user. The purpose of this is to search for the lowest possible superheat that can be obtained while still maintaining a stable system.
Figure 14: MSS
MSS PI controller is made up of 3 parts:
• a stability set point
• the variant from the Te signal
• actual superheat reference
T
he stability set point is given from the “user”. The variants from the T0 signal is used to allow for increased instability if the T0 signal is unstable. Finally the part from the actual superheat allows for more instability at higher superheat references than at lower references.
The superheat reference SH ref is adaptive and adjusted. When using this form of control, there are three settings that have major eect on this mode of control. These are Min. SH, Max. SH and SH close parameters.
© Danfoss | Climate Solutions | 2021.03
AI306444073210en-000801 | 12
Danfoss
80G8227
Start time
Min start
time
The Pctrl is active in
the min star
t time and
until SH cross the
reference
SH
SH ref
Danfoss
80G8228
Start time
Min start
time
The Pctrl is active until
the star
t time if SH
does not get below
reference
SH
SH ref
Parameter
Function
Description
R01
Evaparator control mode
2 = DX control
N01
SH reference mode
2 = Adaptive SH ctrl.
N03
SH max. value
Max. allowed SH reference
N04
SH min. value
Min. allowed SH reference Note: SH min. value must be >0.5K higher than SH close value, if N09 = 1
N18
MSS stability
Stablility factor for regulation of superheat, only relevant for MSS. With a higher value the control func
tion will allow a greater uctuation of the superheat before the reference is changed.
N19
MSS T0 stability factor
Only relevant for MSS. T0 stability factor denes if v
ariation in suction pressure will inuence su­perheat reference. The SH reference change can be adjusted by setting the value 0 to 1 (1 = max T0 inuence and S2, 0 = S2 only). With often change in suction pressure due to compressor start/ stop, some T0 (and S2) inuence on MSS is recommended.
N09
SH close function
0 = O
| 1 = On, default = 1
N10
SH close setpoint
Default value = 2 K (recommended)
Evaporator and room control, type EKE 400
Where to use:
MSS is a benet f
or systems with a long runtime and slow changing conditions like cold rooms, display cases and chillers. Short cycling and system with fast changing operation condition will not benet from MSS as this feature will take time to nd the optimal reference. Adaption to a new set point is approx. 15 min.
Table 2: Functions
Start up
ometimes in one to one applications. the valve does not open suciently on start-up and troublesome low-
S pressure trips happen. The following features allows the valve to open faster as well as to reach the optimal operating conditions quickly.
Proportional (P) control N20, Startup Mode=0
P-control function quickly stabilize the system's superheat by reaching optimal operating conditions in shorter period of time. The controller is programmed for auto proportional control that will quickly change the opening degree based on evaporating temperature and superheat of the system.
Figure 15: SH reference
Figure 16: SH reference
Predened OD with protection N20, Startup Mode=1
After startup, this function will provide a start opening degree during a set time period. If the limiters, the valve will do the auto adjustment based on the operating conditions and the set limitations.
© Danfoss | Climate Solutions | 2021.03
AI306444073210en-000801 | 13
Danfoss
80G8229
Auto control
Forced opening of valve
Auto adjust
v
alve OD%
Valve OD%
Reg. OD%
Forced OD% Normal Reg.
Time for start
Start up time
Start up OD%
(M
inimum)
OD%
Start
Danfoss
80G8230
Auto control
Forced opening of valve
Valve OD%
Forced OD% Normal Reg.
Time for start
Start up time
Start up OD%
OD%
Start
Evaporator and room control, type EKE 400
Figure 17: P
redened OD with protection N20
NOTE:
A
t start up. if the valve is opened too much, it could result in ow of liquid in the compressor or could trigger the HP switch which will stop the system. Whereas if you start the system with too low opening degree. it could also stop the system because of the low-pressure switch cut in. It will be safe to start the system with approximately 50% OD of the valve at start up, if P-control is not being used.
Predened OD without protection N20, Startup Mode=2
After startup, this function will provide a constant opening degree during a set time period regardless of the superheat value. No limiters are taken in consideration during this time.
Figure 18: Predened OD without protection N20
DX with defrost by Hot Gas, and the Defrost Drain Line connected to the receiver
n a DX application, with Hot Gas defrost and the Defrost Drain Line connected to the receiver, the EKE 400 can
I provide a function to manage the valve in the main Hot Gas line. See Figure 19 and Figure 20.
If the Defrost Drain Line is connected to the Liquid receiver it is possible to control the valve in the main HG line from EKE 400. The purpose of the valve in the main Hot Gas line (e.g. Danfoss type ICS with EVM (SI-port) and a CVPP (P-port)) is to build up pressure in the Hot Gas line to the receiver during defrost. I.e. once the EVM is energized then pressure is built up in the Hot Gas line to the receiver via the CVPP.
The EVM can be controlled from the EKE 400. See sketch below: The parameter: D08, Def. seq. status on DO, must be set to: Yes The assigned DO (DO1 to DO8) must be connected to the EVM on the ICS with CVPP in the main Hot Gas line.
© Danfoss | Climate Solutions | 2021.03
AI306444073210en-000801 | 14
Danfoss
80G8231
Danfoss
80G8232
Evaporator and room control, type EKE 400
Figure 19: Application sketch
Figure 20: Application sketch
© Danfoss | Climate Solutions | 2021.03 AI306444073210en-000801 | 15
Label ID
(1)
Parameter name
Description and selection options
Min.
Max.
Factory setting
QS
Select quick setting
Select most common type of applications
S
electing one of below application will then preselect valves the actual appliction
in question. See Table 2
1: Flooded On/O: Flooded, Thermostat ON/FF with Hotgas Defrost by pressure or Liquid drain 2: Dx On/O: DX with Hotgas Defrost by pressure or Liquid drain 3: Flooded Mod WR ctrl: Flooded, Wet Return line control (pressure) Defrost by pressure or Liquid drain 5: PWM mod.ood: PWM Modulating Thermostat (MTR) in Liquid Line. Flooded systems 6: EKC315A replace: Retrot/upgrade from EKC 315A to EKE 400 7: EKC361 replace: Retrot/upgrade from EKC 361 to EKE 400 0: User dened; Means that if none of the applications 1 to 7, match - then select User dened and continue to complete the wizard
070
P01
Display unit
Display unit
0:ME
T: Metric units - Celsius (°C) and Kelvin (°K)
1:IMP: Imperial units - Fahrenheit (°F) and Rankine (°R)
010=MET
R01
Evap. ctrl mode
Evaporator control mode:
-1:None 0:F
lood. evap. On/O
2: DX control
-120=Flood. evap. On/O
D1A
Defrost method
Select the defrost method
0: No defr
ost: No defrost function 1: Hot gas: Defrost done by Hot gas 2:Electrical, water or air defrost (air defrost in rooms with temperature higher than 0 °C (32 °F))
021=Hot gas
T01
Ther. mode
Select thermostat control mode
1: I
ndividual On/O 3: Mod WR ctrl: MTC (Media Temperature Control) in Wet Return line 5: Pwm mod.ood.: Modulating Thermostat (MTR) in Liquid Line. Flooded systems
151=Individual On/O
R04
Mod WR ctrl. Mode
Select the mode for MTC (Media Temperature Control) in Wet Return line
0: T
emp room const.: Temperature control
1: Press.evap const. evap.: Pressure control
010=Temp room cons
R20
Refrigerant
Select Refrigerant
0: not used;1: R12;2: R22;3: R134a;4: R502;5: R717;6: R13;7: R13B1;8: R23;9: R500;10: R503;11: R114;12: R142b;13: U
ser;14:R32;15:R227ea;16: R401A;17: R507A;18: R402A;19: R404A;20: R407C;21: R407A;22: R407B;23: R410A;24: R170;25: R290;26: R600;27: R600a;28: R744;29: R1270;30: R417A;31: R422A;32: R413A;33: R422D;34: R427A;35: R438A;36: R513A;37: R407F;38: R1234zeE;39: R1234yf;40: R448A;41: R449A;42: R452A;43: R450A;44: R452B;45: R454B;46:R1233zdE;47: R1234zeZ;48: R449B;49: R407H;
0490=Not used
R2A
Liq. feed line valve
Select type of valves in Liquid feed line
1: S
olenoid (ICFE): ON/OFF Solenoid ICF 20 Valve station 2: Solenoid (ICS): ON/OFF Solenoid ICS with EVM pilot 3: Solenoid (ICM): Motorized ICM, as slow opening/closing ON/OF valve. Occupy 1 DO
131=Solenoid (ICFE)
R2B
Liq. feed line valve DX
Select Liquid feed line valve for DX
4: AK
V: AKV or AKVA. Occupy 1 DO. DO5 or DO6 must be assigned 5: AKV + Solenoid: AKV or AKVA (Occupy 1 DO. DO5 or DO6 must be assigned) + Solenoid (Occupy 1 DO) 6: Mod ICM; Modulating motorized ICM. Occupy 1 AO 7: Mod ICM + solenoid: Modulating motorized ICM (Occupy 1 AO) + Solenoid (Occupy 1 DO)
474=AKV
R2C
Liq. feed line valve PWM
Select Liquid feed line valve for Modulating Thermostat (MTR) Flooded sy
stems
4: AKV: AKV or AKVA. Occupy 1 DO. DO5 or DO6 must be assigned 5: AKV + Solenoid: AKV or AKVA (Occupy 1 DO. DO5 or DO6 must be assigned) + Solenoid (Occupy 1 DO)
454=AKV
Evaporator and room control, type EKE 400
EKE 400 Wizard
Table 3: EKE 400 Wizard
© Danfoss | Climate Solutions | 2021.03
AI306444073210en-000801 | 16
Label ID
(1)
Parameter name
Description and selection options
Min.
Max.
Factory setting
D3A
Wet return line val.
Select type of valves in Wet return suction line
0: No V
alve 1: Soft (ICS+EVRST): Dual position individual solenoid valves. Occupy 2 DO 2: Soft (ICSH): Dual position solenoid valve. Occupy 2 DO 3: Soft (ICLX): 2-step gas powered solenoid valve. Occupy 1 DO 4: Solenoid (ICS):ON/OFF Solenoid ICS with EVM pilot 5: Solenoid (ICM):Motorized ICM, as slow opening/closing ON/OF valve. Occupy 1 DO 6: Slow (ICM): Motorized ICM, as slow opening/closing modulating valve. Occupy 1 AO
063=Soft (ICLX)
D3C
Wet return line val.
Select type of valves in Wet return line
7: M
od (ICM): Modulating Motorized ICM 8: Mod+PE (ICM+EVRST): Modulating Motorized ICM with pressure Equalization valve EVRA/EVRAT/EVRST
787=Mod (ICM)
D2A
Hot gas line valve
Select type of valves in Hot gas defrost line
0: No V
alve 1: Soft (ICS+EVRST): Dual position individual solenoid valves. Occupy 2 DO 2: Soft (ICSH): Dual position solenoid valve. Occupy 2 DO 3: Solenoid (ICFE): ON/OFF Solenoid ICF 20 Valve station 4: Solenoid (ICS):ON/OFF Solenoid ICS with EVM pilot 5: Solenoid (ICM):Motorized ICM, as slow opening/closing ON/OF valve. Occupy 1 DO 6: Slow (ICM): Motorized ICM, as slow opening/closing modulating valve. Occupy 1 AO
062=Soft (ICSH)
D1B
HG Drain valve
Select type of valves in defrost drain line
0: P
ressure (ICS+CVP): Pressure control valve during hot gas defrost. CVP pilot have adjustable pressure setting 1: Pressure (OFV): Pressure control valve during hot gas defrost. OFV have adjustable pressure setting 2: Liquid drain (ICFD): Liquid drain during defrost
021=Pressure (ICS+CVP)
D2B
HG Drip tray DO
Select possible DO hot gas valve for drip tray line
No: No Dr
ip tray valve/function
Yes: Drip tray valve and function active
0=No
Yes=1
0=No
D4A
Drain solenoid?
Decide if drain solenoid in defrost drain line is installed
No Y
es
0=No
1=Yes
1=Yes
D4B
Quick Drain?
Decide if drain valve is installed to drain liquid quikly out before hot gas en
ter evaporator
No Yes
0=No
1=Yes
0=No
T04
Ther. setpoint
Thermostat set point temperature
-50.0
50.0
2.0
T05
Ther. neutral zone
Thermostat neutral zone
S
tart/Stop limit around the "T03 Ther. Setpoint"
0.1
20.0
2.0
T17
Suc.Pres. SP To
Evaporator pressure Setpoint in [C] / [F]
T
emperature Setpoint in [C]/[F] compared measured pressure value (calulated
into [C]/[F]
-50.0
50.0
0.0
B02
High alarm limit
High alarm limit
H
igh alarm for the room temperature alarm function. Entered as absolute value
-50.0
50.0
6.0
B03
Low alarm limit
Low alarm limit
L
ow alarm for the room temperature alarm function. Entered as absolute value
-50.0
50.0
-30.0
B04
Alarm delay
Alarm delay
A
larm delay time during normal control used for both high- and low temperature
alarms
0
240
120
D11
Def. time interval
Defrost start by time interval
F
ail safe function if another congured defrost start, has failed. A defrost will be started when the interval counter (real time) exceeds the ‘Defrost time interval’ setting. The interval counter is start counting from zero when the defrost is started. The interval counter will be reset at every defrost start. The interval counter shall be in standby (not counting) at "Main switch is OFF". Can be seen in Status Sceen 1. If "D11,Def. time interval" is 0 (zero) the function is disabled
0
240
0
Evaporator and room control, type EKE 400
© Danfoss | Climate Solutions | 2021.03 AI306444073210en-000801 | 17
Label ID
(1)
Parameter name
Description and selection options
Min.
Max.
Factory setting
D12
Def. start acc. cool time
Defrost start by accumulated cooling time
C
an also be used as a fail safe function if another congured defrost start, has failed. A defrost will be started when the accumulated cooling time exceeds "D12,Def. start acc. cool time" setting. The accumulated cooling time will be reset at every defrost start.
0
240
0
D14
Def. start by DI
Defrost start by DI
Option t
o start defrost via DI. Typical external dignal from PLC or a push bottom. If function is enabled, a defrost is started when the DI changes from OFF to ON. Successive change of the DI during the defrost period are ignored.
No: Function disable Yes: Function enabled"
0=No
1=Yes
0=No
D15
Def. start schedule
Defrost start schedule
Option t
o run defrost according to local time scedules in EKE 400. Three schcdules possible (weekdays, saturdays and sunday) with 6 defrost start time each
No: Function disable Yes:Function enabled"
0=No
1=Yes
0=No
D40
Defrost stop method
Defrost stop method
S
elect method for stop of defrost
1: Stop on time: When the time delay "D58,Max defrost time" expires, the defrost is terminated 2: Stop on temp: When the defrost sensor temperature becomes greater than the set point "D43,Def. stop temp. limit", then the defrost is terminated. If the defrost time exceed "D58,Max defrost time", then the alarm ‘Max defrost time’ is send and the defrost is terminated. In case of sensor error, and the time ‘Max defrost time’ expires, the alarm ‘Max defrost time’ is send and the defrost is terminated. The alarm will automatically be reset after 5 minutes. To assign defrost sensor temperature, go to I/O conguration in Main menu and select an available AI"
121=Stop on time
D43
Def. stop temp. limit
Defrost stop temperature limit
S
ee description for "D40, Defrost stop method"
0.0
25.0
8.0
D50
Pump down delay
Pump down delay
Dr
aining the evaporator before defrosting. Always active The pump down state is used to empty the evaporator for liquid. See Figure 21: Defrost sequence.
13010
D51
HG open delay
Hot Gas open delay
T
ime delay in minutes before opening the hot gas valve (delay for valve in the wet return line to close) See Figure 21: Defrost sequence.
1105
D5A
Drip tray pre-heat
Driptray pre-heat
P
re-heating time for hot gas to drip tray See Figure 21: Defrost sequence
0205
D5B
Drip tray delay OFF
Drip tray delay OFF
C
ontinue drip tray heating some dened time
See Figure 21: Defrost sequence
0
120
30
D57
Quick drain time
Quick drain time
En
ter how long time the Quick Drain valve stays open. Quick Drain valve will start opening together with Hot gas valve See Figure 21: Defrost sequence
1
300
30
D53
HG soft time
Hot gas soft time
T
ime between step 1 and step 2 for opening the hot gas valve (2 DO used)
See Figure 21: Defrost sequence.
1303
D58
Max defrost time
Max defrost time
M
ax. allowed defrost duration in minutes
1
120
30
D59
Drip o time
Drip o time
A
llow water on the evaporator to drip o.
See Figure 21: Defrost sequence.
1155
D61
WR soft time
Wet return soft time
T
ime between step 1 and step 2 for opening the wet return valve ("Soft (ICS +EVRST)" or "Soft (ICSH) See Figure 21: Defrost sequence.
1302
Evaporator and room control, type EKE 400
© Danfoss | Climate Solutions | 2021.03
AI306444073210en-000801 | 18
Label ID
(1)
Parameter name
Description and selection options
Min.
Max.
Factory setting
D6A
WR main time
Wet return main time
A
fter defrost and wet return valve has opened (main), enter delay before valve in liquid line to open. See Figure 21: Defrost sequence.
1302
D65
Fan start delay
Fan start delay
T
he fan will be started when the time has elapsed.
See Figure 21: Defrost sequence.
0302
D69
WR Pr. Equalising
WR Pressure Equalizing time
E
qualizing pressure in evaporator by soft opening wet return line valve. Carefully emptying the evaporator for hot gas via a little drain valve (by-pass valve) in the wet return line or soft opening of wet return valve.
1105
P03
Main switch via DI
Mainswitch via DI
R
elease EKE 400 for operation or force EKE 400 out of operation via external
equipment (e.g. PLC), via DI
OFF: EKE 400 is forced out of operation. Observe if "M01,Main switch" is ON, this parameter will also when OFF, force EKE 400 out of operation ON: EKE 400 released for operation. Observe if "M01,Main switch" is ON, this parameter must also be ON, to release EKE 400 for operation
0=No
1=Yes
0=No
Label
ID
(1)
Parameter name
Description and selection options
Min.
Max
Factory S
etting
Dec‐
im‐
als
Locked
b
y Main
switch
Yes/No
Read
Pass‐ w
ord
level to
change/
write
Modbus addr
ess
Read
only
(R
O) / Read Write (RW)
Persis‐
t
ent
Yes/No
Modbus
func
tion
M01
Main switch
Release the controller for operation or f
orce EKE 400 out of operation
OFF: the controller is forced out of operation. Observe if "M02, Ext. Main switch" is ON, this DI will also when OFF, forced the controller out of operation ON: the controller released for operation. Observe if "M02, Ext. Main switch" is ON, this DI must also be ON to release the controller for operation
0=OFF
1=ON
0=OFF0No
Pass­w
ord
level 1,2,3
2
3001RWYes
3, 4 & 16
M02
Ext. Main swit
ch
Status of the external main switch (DI)
0=OFF
1=ON-0
Yes
Pass­w
ord
level 1,2,3
Can nev-
er be changed
3002ROYes
3
Evaporator and room control, type EKE 400
(1)
(1)
Visibility depends on other parameter settings. Numbers are displayed in Metric units ( P01, Temperature units=MET)
Visibility depends on other parameter settings. Numbers are displayed in Metric units ( P01, Temperature units=MET)
Parameter list
ve that many of the individual parameters listed below, will only be visible, if other parameters have been set.
Obser Hereby irrelevant parameters are ltered out, during setup of EKE 400.
NOTE:
See Label ID, G07, G08, G09.
1. All Modbus parameters is type: WORD (signed 16 bit).
2.
Start / Stop
Table 4: Start / Stop
(1)
(1)
Visibility depends on other parameter settings. Numbers are displayed in Metric units ( P01, Temperature units=MET).
Visibility depends on other parameter settings. Numbers are displayed in Metric units ( P01, Temperature units=MET).
© Danfoss | Climate Solutions | 2021.03 AI306444073210en-000801 | 19
Label
ID
(1)
Parameter name
Description and selection options
Min.
Max
Factory S
etting
Dec‐
im‐
als
Locked
b
y Main
switch
Yes/No
Read
Pass‐ w
ord
level to
change/
write
Modbus addr
ess
Read
only
(R
O) / Read Write (RW)
Persis‐
t
ent
Yes/No
Modbus
func
tion
R01
Evap. ctrl mode
Evaporator control mode:
-1: None 0: F
lood. evap. ON/OFF
-100=Flood.
ev
ap.
On/O;
0
Yes
Pass­w
ord
level 1,2,3
3
3020RWYes
3, 4 & 16
R2A
Liq. feed line v
alve
Select Liquid feed line valve
1: S
olenoid (ICFE): ON/OFF Solenoid ICF 20 Valve station 2: Solenoid (ICS): ON/OFF Solenoid ICS with EVM pilot 3: Solenoid (ICM): Motorized ICM, as ON/OF valve. Occupy 1 DO
1310Yes
Pass­w
ord level 1,2,3
3
3021RWYes
3, 4 & 16
R2B
Liq. feed line v
alve
for DX
Select Liquid feed line valve for DX
4: AK
V: AKV or AKVA. Occupy 1 DO. DO5 or DO6 must be assigned 5: AKV + Solenoid: AKV or AKVA (Occupy 1 DO. DO5 or DO6 must be assigned) + Solenoid (Occupy 1 DO) 6: Mod ICM; Modulating motorized ICM. Occupy 1 AO 7: Mod ICM + solenoid: Modulating motorized ICM (Occupy 1 AO) + Solenoid (Occupy 1 DO)
4740Yes
3384RWYes
R2C
Liq. feed line v
alve
PWM
Select Liquid feed line valve for M
odulating Thermostat (MTR)
Flooded systems
4: AKV: AKV or AKVA. Occupy 1 DO. DO5 or DO6 must be assigned 5: AKV + Solenoid: AKV or AKVA (Occupy 1 DO. DO5 or DO6 must be assigned) + Solenoid (Occupy 1 DO)
4540Yes
3380RWYes
R10
LL valve AI f
eedback
Liquid Line feedback from ICAD on ICM v
alve
In IO conguration \ Analog inputs the Analog input type can be selected. 0-10 V;0-20 mA;4-20 mA;2-10 V
No: ICAD not connected to EKE 400 Yes: ICAD connected to EKE 400
No
YesNo0
Yes
Pass­w
ord level 1,2,3
3
3446RWYes
3, 4 & 16
R05
Cool On/O
by DI
Cooling demand from external equipmen
t (e.g. PLC) to EKE 400, via DI
0=No
1=Yes
0=No0Yes
Pass­w
ord level 1,2,3
3
3024RWYes
3, 4 & 16
R06
Forced clos­ing
Forced stop cooling via MODBUS (e.g. PL
C) or local from EKE 400
If a PLC controls cooling ON/OFF, "R06,Forced closing" can be used to stop cooling
OFF: Function disabled ON: Forced stop cooling, regardless of cooling request. Observe. Will automatically after 15 min go back to OFF
0=OFF
1=ON
0=OFF0No
Pass­w
ord level 1,2,3
2
3025RWNo
3, 4 & 16
Evaporator and room control, type EKE 400
Evaporator control \ Evaporator control mode
Table 5: Evaporator control \ Evaporator control mode
© Danfoss | Climate Solutions | 2021.03
AI306444073210en-000801 | 20
Label
ID
(1)
Parameter name
Description and selection options
Min.
Max
Factory S
etting
Dec‐
im‐
als
Locked
b
y Main
switch
Yes/No
Read
Pass‐ w
ord
level to
change/
write
Modbus addr
ess
Read
only
(R
O) /
Read Write (RW)
Persis‐
t
ent
Yes/No
Modbus
func
tion
R07
Forced c
ooling
Forced cooling via MODBUS (e.g. PLC) or lo
cal from EKE 400
The function is typical used to secure enough hot gas to defrost other evaporators If a PLC controls cooling ON/ OFF, "R07,Forced cooling" can be used to start cooling
OFF: Function disabled ON: Forced cooling, regardless of cooling request. Observe. Will automatically after 15 min go back to OFF
0=OFF
1=ON
0=OFF0No
Pass­w
ord level 1,2,3
2
3026RWNo
3, 4 & 16
R08
Forced close b
y DI
Forced stop cooling via external equipmen
t (e.g. PLC) to EKE 400, via DI
If a PLC controls cooling ON/OFF, DI can be used to stop cooling
No: Function disabled Yes: Forced stop cooling, regardless of cooling request. To assign DI, go to I/O conguration in Main menu and select an available DI
0=No
1=Yes
0=No0Yes
Pass­w
ord level 1,2,3
3
3027RWYes
3, 4 & 16
R09
Forced cool b
y DI
Forced cooling via external equipment (e
.g. PLC) to EKE 400, via DI
If a PLC controls cooling ON/OFF, DI can be used to start cooling
No: Function disabled Yes: Forced cooling, regardless of cooling request. To assign DI, go to I/O conguration in Main menu and select an available DI
0=No
1=Yes
0=No0Yes
Pass­w
ord level 1,2,3
3
3028RWYes
3, 4 & 16
Evaporator and room control, type EKE 400
(1)
(1)
Visibility depends on other parameter settings. Numbers are displayed in Metric units ( P01, Temperature units=MET).
Visibility depends on other parameter settings. Numbers are displayed in Metric units ( P01, Temperature units=MET).
© Danfoss | Climate Solutions | 2021.03 AI306444073210en-000801 | 21
Label
ID
(1)
Parameter name
Description and selection options
Min.
Max
Factory S
etting
Dec‐
im‐ als
Locked
b
y Main
switch
Yes/No
Read
Pass‐ w
ord
level to
change/
write
Modbus
addr
ess
Read
only
(R
O) /
Read
Write
(RW)
Persis‐
t
ent
Yes/No
Modbus
func‐
tion
R20
Refrigerant
Select Refrigerant
0: not used;1: R12;2: R22;3: R134a;4: et
c. 0: not used;1: R12;2: R22;3: R134a;4: R502;5: R717;6: R13;7: R13B1;8: R23;9: R500;10: R503;11: R114;12: R142b;13: User;14:R32;15:R227ea;16: R401A;17: R507A;18: R402A;19: R404A;20: R407C;21: R407A;22: R407B;23: R410A;24: R170;25: R290;26: R600;27: R600a;28: R744;29: R1270;30: R417A;31: R422A;32: R413A;33: R422D;34: R427A;35: R438A;36: R513A;37: R407F;38: R1234zeE;39: R1234yf;40: R448A;41: R449A;42: R452A;43: R450A;44: R452B;45: R454B;46:R1233zdE;47: R1234zeZ;48: R449B;49: R407H
04900Yes
Pass­w
ord level 1,2,3
3
3029RWYes
3, 4 & 16
R23
Refrig fact. A1
User dened r
efrigerant
When R20=13 (User dened refrigerant) Enter the Refrigerant factor A1 constants for the Antoine Equation for the actual refrigerant
8000
13000
104003Yes
3032RWYes
R24
Refrig fact. A2
User dened r
efrigerant
When R20=13 (User dened refrigerant) Enter the Refrigerant factor A2 constants for the Antoine Equation for the actual refrigerant
-3200.0
-1200.0
-2255.01Yes
3033RWYes
R25
Refrig fact. A3
User dened r
efrigerant
When R20=13 (User dened refrigerant) Enter the Refrigerant factor A3 constants for the Antoine Equation for the actual refrigerant
220.0
320.0
254.21Yes
3034RWYes
Evaporator and room control, type EKE 400
Evaporator control \ Pressure c
onguration
Table 6: Evaporator control \ Pressure conguration
(1)
(1)
Visibility depends on other parameter settings. Numbers are displayed in Metric units ( P01, Temperature units=MET).
Visibility depends on other parameter settings. Numbers are displayed in Metric units ( P01, Temperature units=MET).
© Danfoss | Climate Solutions | 2021.03
AI306444073210en-000801 | 22
Label
ID
(1)
Parameter name
Description and selection options
Min.
Max
Factory S
etting
Dec‐
im‐
als
Locked
b
y Main
switch
Yes/No
Read
Pass‐ w
ord
level to
change/
write
Modbus addr
ess
Read
only
(R
O) /
Read Write (RW)
Persis‐
t
ent
Yes/No
Modbus
func
tion
N01
SH ref. mode
Select Superheat reference mode:
0: F
ixed SH ref. Used when a stable xed superheat is required 1: Load dened ctrl: LoadAp mode. Reference set in dependence of actual load (Opening Degree) Useful in applications with rapidly changing load conditions and at very short cut-in perios. 2: Adaptive SH ctrl: MSS (Minimum Stable Superheat) The superheat control algorithm will constantly lower the superheat reference, until some instability is registrated
021= Load
dened
c
trl
0xPass-
w
ord level 1,2,3
3
3003RWYes
3, 4 & 16
N02
SH Fixed setpoin
t
Superheat x
ed setpoint
The superheat reference is xed to this set point under all operating conditions
0.5
40.0
8.01Pass-
w
ord level 1,2,3
3
3004RWYes
3, 4 & 16
N03
SH max
Superheat maximum
M
aximum limitation of superheat
reference
0.5
40.0
10.01No
Pass­w
ord level 1,2,3
2
3005RWYes
3, 4 & 16
N04
SH min
Superheat minimum
M
inimum limitation of superheat
reference
Unit: °C / °F
0.5
10.0
4.01No
Pass­w
ord level 1,2,3
2
3006RWYes
3, 4 & 16
N05
SH Tn
Superheat Integration time
I
ntegration time (Tn) in PI controller
Unit: °C / °F
20
900900NoPass-
w
ord level 1,2,3
3
3007RWYes
3, 4 & 16
N06
SH Kp min
Superheat minimum Proportional gain c
onstant
Minimum proportional gain in Superheat PI controller
Unit: °C / °F
0.1
1.0
0.61No
Pass­w
ord level 1,2,3
3
3008RWYes
3, 4 & 16
N07
SH Kp
Superheat Proportional gain constant
P
roportional gain in Superheat PI
controller
Unit: sec
0.1
20.0
1.51No
Pass­w
ord level 1,2,3
3
3009RWYes
3, 4 & 16
N08
SH KpTe
Superheat Pressure feedback gain
P
roportional gain constant on saturated
temperature
0
20.0
3.01No
Pass­w
ord level 1,2,3
3
3010RWYes
3, 4 & 16
N09
SH close func
tion
Superheat close function
No: F
untion Disabled
Yes: Function Enabled
0=No
1=Yes
1=Yes0Yes
Pass­w
ord level 1,2,3
2
3011RWYes
3, 4 & 16
N10
SH close setpoin
t
Superheat close limit
I
f the superheat is below this value the
valve in the liquid line is forced to close
-5.0
20.0
2.01No
Pass­w
ord level 1,2,3
3
3012RWYes
3, 4 & 16
N11
SH close Tn divide
Advanced parameter setting
F
or Danfoss only
1530No
Pass­w
ord level 1,2,3
3
3013RWYes
3, 4 & 16
N12
SH close Kp fac
tor
Advanced parameter setting
F
or Danfoss only
Unit: °C / °F
0.5101.50No
Pass­w
ord level 1,2,3
3
3014RWYes
3, 4 & 16
Evaporator and room control, type EKE 400
Evaporator control mode \ Evaporator DX control
Table 7: Evaporator control mode \ Evaporator DX control
© Danfoss | Climate Solutions | 2021.03 AI306444073210en-000801 | 23
Label
ID
(1)
Parameter name
Description and selection options
Min.
Max
Factory S
etting
Dec‐
im‐
als
Locked
b
y Main
switch
Yes/No
Read
Pass‐ w
ord
level to
change/
write
Modbus addr
ess
Read
only
(R
O) /
Read Write (RW)
Persis‐
t
ent
Yes/No
Modbus
func
tion
N13
MOP func­tion
Maximum Operating Pressure
MOPfunc
tion will limit the valve opening degree such that the saturated evaporation temperature Te is kept below the "N14,MOP" set point. MOP prevents overloading the compressor during start-up, by reducing suction pressure No: Funtion Disabled Yes: Function Enabled
No
Yes
0=No0Yes
Pass­w
ord level 1,2,3
2
3015RWYes
3, 4 & 16
N14
MOP set­poin
t
Maximum Operating Pressure setpoint
A
ctive if "N13, MOP function" is set to Yes The actual MOP Evaporator pressure Setpoint in [C] / [F]
-70.0
50.0
0.01No
Pass­w
ord level 1,2,3
2
3016RWYes
3, 4 & 16
N15
MTR Tn
Advanced parameter
I
ntegration time for the MTR algorithm
20
3600
18000No
Pass­w
ord level 1,2,3
3
3017RWYes
3, 4 & 16
N16
MTR Kp
Advanced parameter
P
roportional factor for the MTR algorithm
Unit: °C / °F
20
3600
18000No
Pass­w
ord level 1,2,3
3
3018RWYes
3, 4 & 16
N17
AKV period
AKV or AKVA period time
P
eriod time of AKV or AKVA Example: "N17, AKV Period" is set to 6 sec., the Opening Degree is calculated to 40 %, then AKV or AKVA is open in 2,4 sec., and closed in 3, 6 sec
3660Yes
Pass­w
ord level 1,2,3
2
3019RWYes
3, 4 & 16
N18
MSS stabili­t
y
Minimum Stable Superheat stability
S
tability factor for regulation of superheat, only relevant for MSS. With a higher value the control function will allow a greater uctuation of the superheat before the reference is changed.
0.0
10.0
5.01Yes
Pass­w
ord level 1,2,3
3
3397RWYes
N19
MSS T0 sta­bilit
y factor
Minimum Stable Superheat stability T0 fac
tor
Only relevant for MSS. T0 stability factor denes if variation in suction pressure will inuence superheat reference. The SH reference change can be adjusted in the range frome 0.0 to 1.0 A value of 1.0 will give max T0 inuence and S2. A value of 0.0 will give inuence on S2 only.
With often change in suction pressure due to compressor start/stop, some T0 (and S2) inuence on MSS is recommended.
0.0
1.0
0.01Yes
Pass­w
ord level 1,2,3
3
3390RWYes
N20
Startup M
ode
Startup Mode (See section Start Up)
A
fter startup, this function will provide a constant opening degree during a set time period regardless of the superheat value. No limiters are taken in consideration during this time.
0: Prop.Ctrl: Proprotional (P) control 1: Fix OD w prot: Predened OD (parameter "N23, Startup OD") with protection 2: Fix OD wo prot: Predened OD (parameter "N23, Startup OD") without protection
0200Yes
Pass­w
ord level 1,2,3
3
3393RWYes
Evaporator and room control, type EKE 400
© Danfoss | Climate Solutions | 2021.03
AI306444073210en-000801 | 24
Label
ID
(1)
Parameter name
Description and selection options
Min.
Max
Factory S
etting
Dec‐
im‐
als
Locked
b
y Main
switch
Yes/No
Read
Pass‐ w
ord
level to
change/
write
Modbus addr
ess
Read
only
(R
O) /
Read Write (RW)
Persis‐
t
ent
Yes/No
Modbus
func
tion
N21
Startup time
"Startup time (See section Start Up)
T
his parameter is related to "N20, Startup
Mode"
Unit: sec
1
600900
Yes
Pass­w
ord level 1,2,3
3
3394RWYes
N22
Min.startup time
Min.startup time (See section Start Up)
T
his parameter is related to "N20, Startup
Mode"
Unit: sec
1
240150
Yes
Pass­w
ord level 1,2,3
3
3395RWYes
N23
Startup OD
Startup Opening Degree (See section S
tart Up)
This parameter is related to "N20, Startup Mode"
Unit: %
1
100320
Yes
Pass­w
ord level 1,2,3
3
3396RWYes
N24
Minimum OD
Minimum Opening Degree
W
hen required, the valve minimum OD can be set to a required minimum opening position, such feature is helpful where the system always requires some minimum ow. The minimum OD limit has eect in injection control mode only
Unit: %
0
10000
Yes
Pass­w
ord level 1,2,3
3
3398RWYes
N25
Maximum OD
Maximum Opening Degree
T
his is useful feature to limit the maximum OD of a oversized valve used in the system. By default the maximum OD of a valve is set at 100 OD%. This maximum OD % can be set to lower value if required. The maximum OD limit has eect in injection control mode only
Unit: %
0
100
1000Yes
Pass­w
ord level 1,2,3
3
3399RWYes
N26
Limit Kp
Limit Kp - Superheat c
onguration
Advance
Proportional gain
1.0
20.0
5.01Yes
Pass­w
ord level 1,2,3
3
3400RWYes
N27
Limit Tn
Limit Tn - Superheat c
onguration
Advance
Integration time
Unit: sec
20
900450
Yes
Pass­w
ord level 1,2,3
3
3401RWYes
N36
S3 air in.t
emp.AI?
Air temperature sensor (S3) installed?
U
sed for MTR 0: No not installed 1: Yes installed To assign AI, go to I/O conguration in Main menu and select an available AI
0100Yes
Pass­w
ord level 1,2,3
3
3405RWYes
Evaporator and room control, type EKE 400
© Danfoss | Climate Solutions | 2021.03 AI306444073210en-000801 | 25
Label
ID
(1)
Parameter name
Description and selection options
Min.
Max
Factory S
etting
Dec‐
im‐
als
Locked
b
y Main
switch
Yes/No
Read
Pass‐ w
ord
level to
change/
write
Modbus addr
ess
Read
only
(R
O) /
Read Write (RW)
Persis‐
t
ent
Yes/No
Modbus
func
tion
N28
Ext.Ref.DX
c
ong
External reference DX c
onguration
Select the signal used to change the Superheat reference.
0: Not used 1: Displace by current: - dene the AI input range via the following settings: “N31,Ref.Current SH High”: 4 to 20 mA, default = 20 “N32,Ref.Current SH Low”: 0 to 20 mA, default = 4 To assign AI, go to I/O conguration in Main menu and select an available AO 2: Displace by voltage: - dene the AI input range via the following settings: “N33,Ref.Voltage SH High”: 0 to10 Volt, default = 10 “N34,Ref.Voltage SH Low”: 0 to 10 Volt, default = 0 To assign AI, go to I/O conguration in Main menu and select an available AI. 3: Displace by MODBUS 4: Displace by DI
0400Yes
Pass­w
ord level 1,2,3
3
3402RWYes
N29
Ref.Oset
SH M
ax
Reference oset Sup
erheat maximum
Scaling of range for superheat displacement - Maximum value. See "N28, Ext.Ref.DX cong"
Unit: K
0.0
50.0
0.01No
Pass­w
ord level 1,2,3
3
3410RWYes
N30
Ref.Oset
SH M
in
Reference oset Sup
erheat minimum
Scaling of range for temperature displacement - Minimum value See "N28, Ext.Ref.DX cong"
Unit: K
-50.0
0.0
0.01No
Pass­w
ord level 1,2,3
3
3409RWYes
N31
Ref.Current SH H
igh
Reference current Superheat high
S
caling of range for AI current - high
value See "N28, Ext.Ref.DX cong"
Unit: mA
N32
20.0
20.01No
Pass­w
ord level 1,2,3
3
3354RWYes
N32
Ref.Current SH L
ow
Reference current Superheat low Scaling of r
ange for AI current - low value See
"N28, Ext.Ref.DX cong" Unit: mA
0.0
N31
4.01No
Pass­w
ord level 1,2,3
3
3355RWYes
N33
Ref.Voltage SH H
igh
Reference voltage Superheat high
S
caling of range for AI voltage - high
value See "N28, Ext.Ref.DX cong"
Unit: V
N34
10.0
10.01No
Pass­w
ord level 1,2,3
3
3356RWYes
N34
Ref.Voltage SH L
ow
Reference voltage Superheat low
S
caling of range for AI voltage - low value
See "N28, Ext.Ref.DX cong"
Unit: V
0.0
N33
0.01No
Pass­w
ord level 1,2,3
3
3357RWYes
N35
Re.Oset
SH M
odbus
Reference oset Sup
erheat by
MODBUS
Oset value via MODBUS (e.g. PLC) added to current SH reference.
Unit: K
-50.0
50.0
0.01No
Pass­w
ord level 1,2,3
3
3358RWYes
N38
Ref. O
set
SH by DI
Reference O
set Superheat when DI is
open, 0 K if closed
If P10, Ext ref. cong.=Displace by DI, then if the assigned DI:
OFF: No oset added ON: Value entered here will be added to SuperHeat reference
Unit: K
-70.0
50.0
0.01No
Pass­w
ord level 1,2,3
3
3470RWYes
3, 4 & 16
N37
Tn SH track­ing
Tn SH tracking
Unit: sec
3
600
2000No
Pass­w
ord level 1,2,3
3
3413RWYes
Evaporator and room control, type EKE 400
© Danfoss | Climate Solutions | 2021.03
AI306444073210en-000801 | 26
Loading...
+ 58 hidden pages