Danfoss EKE 347 Data sheet

Data Sheet
Liquid level controller Type EKE 347
An intuitive and easy to navigate controller with Modbus network capability
The EKE 347 controller is used for regulation of the liquid level in:
• Pump reservoirs
• Separators
• Intermediate coolers
• Economisers
• Condensers
• Receivers
By comparing the measured value with the level setpoint entered by the customer, the controller dictates the valve to increase or decrease the liquid ow to or from the reservoir.
AI190286434038en-000501
Liquid level controller, Type EKE 347
Features
• Liquid level control
• Alarm if the set alarm limits are exceeded
• Relay outputs for upper and lower level limits and for alarm level
• User friendly and easy setup Wizard for rst time conguration
• PI control
• Low or High side control
• When AKV/A is selected, a MASTER/SLAVE system can run up to 3 AKV/A with distributed Opening Degree
• Manual control of output
• Limitation of Opening degree possible
• ON/OFF operation with hysteresis
• Programming menu with 3 access levels and separate passwords
• Connection to other EKE 347 controllers possible
• Wired remote display possible
• BUS communication:
CAN Bus (Danfoss internal only)MODBUS RTU RS485 for communication with e.g. PLC
© Danfoss | Climate Solutions | 2021.02 AI190286434038en-000501 | 2
EKE 347 assembly
MODBUS communication
Remote Display - option
Danfoss
M84H0081_1
AKS 4100/ AKS 4100U
EKE 347
Danfoss
M84H0086_1
PLC Master
PLC Slave
EKE 347 Slave
EKE 347 Slave
MODBUS-RTU network
Danfoss
M84H0087_1
Remote display
EKE 347
EKE 347
Danfoss CAN bus
EKE 347
Signaltransmitter
With the guided micro wave rod AKS 4100/4100U it is possible to set the refriger­ant level within a wide range.
EKE 347
The controller receive a signal which enable it to contol low or high side applica­tions (see page 3). EKE 347 does support 2 types of Danfoss expansion valves. (see below) One analog input is available as feed back from ICM in order to indicate opening degree of the ICM.
Expansion valves
Two types of Danfoss expansion valves can be used
ICM
ICM are direct operated motorized valves driven by digital stepper motor type ICAD
AKV/A
AKVA or AKV are pulse-width modulating expansion valves.
MODBUS communication
EKE 347 include as standard RS 485 based MODBUS­RTU bus communication interface to third party equipment like PLC. Via the MODBUS it is possible to read and write parameters to the EKE 347 Operation, monitoring and data collection can then be performed via PLC from a SCADA system.
Remote Display - option
A remote display for panel mounting is available. From the remote display a full overview and access is possible to all individual EKE 347 controllers connected to the internal Danfoss CAN bus.
Liquid level controller, Type EKE 347
Functions
Table 1: Functions
Table 2: Functions
© Danfoss | Climate Solutions | 2021.02 AI190286434038en-000501 | 3
ICM with ICAD mo tor
EKE 347
AKS 4100/ AKS 4100U
AKS 4100/ AKS 4100U
EKE 347
Liquid level controller, Type EKE 347
Applications
Pump reservoir
Modulating control of injection for a more stable liquid level and suction pressure.
Figure 1: System conguration ICAD
Separator on ooded evaporator
Modulating control and the valve’s large capacity range ensure a stable level - even under conditions of quickly changing loads.
Figure 2: System conguration AKV/A
Intermediate cooler
The level transmitter’s wide measuring range enables it to monitor the liquid at all levels of the reservoir - and hence to use the signal for safety functions in connection with the max. permissible level.
© Danfoss | Climate Solutions | 2021.02 AI190286434038en-000501 | 4
EKE 347
AKS 4100/ AKS 4100U
System configuration AKV/A
Regulating principle: Low Level Signal setup: AKS 4100/U
EKE 347
AKS 4100/ AKS 4100U
System configuration AKV/A
Regulating principle: High Level Signal setup: AKS 4100/U
Liquid level controller, Type EKE 347
Figure 3: System conguration AKV/A
Receiver / condenser
The control system’s short reaction time makes it very suited for high-pressure oat systems with small refrigerant charges.
Figure 4: System conguration AKV/A
© Danfoss | Climate Solutions | 2021.02 AI190286434038en-000501 | 5
Supply voltage
24 V AC ±20% 50 / 60 Hz or 24 V DC ±20% (the supply voltage is galvanically separated from the input and output signals. Input/output are not individual galvanic isolated)
Power consumption
Controller 20 W coil for AKV or AKVA
15 VA / 10W 55 VA
Input signal * Ri = 0(4) – 20mA: 33 ohm 0(2) – 10 V: 100 kohm
Level signal *
4 – 20 mA or 0 – 10 V
ICM valve feedback signal *
From ICAD 0/4 – 20 mA
Contact function start / stop of regulation
Relay output
3 pcs. SPDT (Lower level alarm, Upper level alarm, Common alarm / NC Solenoid)
Normally Open:
3 A GP*, 2.2 FLA / 13.2 LRA, 1/6 hp, PD 220 VA, 250 V AC 100 k 3 FLA / 18 LRA, 1/10 hp, PD 150 VA, 125 V AC 100 k
Normally Closed:
3 A GP*, 250 V AC 100 k (*GP = General purpose) Max 240 V AC or 24 V AC / DC can be used, but same voltage type must be used on DO3 and DO2
Current output
0 – 20 mA or 4 – 20 mA
Max. load: 500 ohm
Valve connection
ICM - via current output AKV/A- via 24 AC Pulse-Width Modulating output
Data communication
MODBUS RTU: Communication to system controller,
MODBUS on RS485: galvanic isolation (500 V DC)
CAN: Communication to other EKE controllers
Supported Modbus Commands
Supported commands with max of 50 ms response time 03 (0x03) Read Holding Registers
04 (0x04) Read Input Registers
06 (0x06) Write Single Register
Supported commands without
dened max response time 08 (0x08) Diagnostics
16 (0x10) Write Multiple Registers (up to 20 registers)
43 (0x2b) Read Device
Identication
Environments
-20 °C – 55 °C, during operation
-30 °C – 80 °C, during storage
90% Rh, not condensed
No shock
inuence / vibrations
Enclosure
IP20 / IP40 for the front mounted into a panel
Weight
193 g
Mounting
DIN rail
Display
Graphical LCD display
Terminals
plugs 1.5 or 2.5 mm2 multicore
Terminals
28-29
Supply voltage 24 V a.c. or d.c.
1-7
Signal from level transmitter type AKS 4100/4100U
7-10
Signal from level transmitter type AKS 41
36-37
Expansion valve type AKV or AKVA
23-24
Expansion valve type: ICM with ICAD
13-14
Switch function for start/stop of controller. If a switch is not connected, terminals 13 and 14 must be shortcircuited
Liquid level controller, Type EKE 347
Product specication
Electrical connection
Table 3: Electrical connection
Material specication
Table 4: Material specication
Connection
Table 5: Necessary connections
NOTE:
See the gures on the next pages.
© Danfoss | Climate Solutions | 2021.02 AI190286434038en-000501 | 6
AKS4100 /4100U
AKS 41
DI1 - main switch
4-20 mA
CANbus connection
to other EKE controllers
plug for
remote display
ModBUS
4-20 mA
24V DC
yellow
blue
orange
ICAD 1stgen
ICAD/ICM
feedback
ICAD 2ndgen
blue
24V AC
L
N
+
1
2 3
yellow
gray
orange
ICAD 1stgen (p re 2010)
ICAD 2ndgen (2010 +)
yellow
green
brown
brown
white
24V+
15V+
5V+
COM
AI 5
AI 4
AI 3
AI 2
AI 1
COM
COM
DI 2
DI 1
COM
R120
CAN H
CAN L
GND
R GNDD+D-
COM
AO 1
CAN RJ
24V DC
24V DC
1
15 16 17 18 19 20 21 22 23 24
2 3 4 5 6 7 8 9 10 11 12 13 14
Upper level
Danfoss
80Z8109
Terminals
33-35
Relay for common alarm. Installer can choose between Normally Open (33-34) or Normally Closed (34-35) circuits. The relay will switch according to the programmed setting
25-27
Relay for low level limit. Installer can choose between Normally Open (26-27) or Normally Closed (25-26) circuits. The relay will switch when the set value is passed.
30-32
Relay for upper level limit. Installer can choose between Normally Open (30-31) or Normally Closed (31-32) circuits. The relay will switch when the set value is passed.
6-10
ICM valve feedback signal from ICAD 0/4 – 20 mA
Liquid level controller, Type EKE 347
Table 6: Application dependent connections
Figure 5: Connections - Upper level
© Danfoss | Climate Solutions | 2021.02 AI190286434038en-000501 | 7
Loading...
+ 16 hidden pages