Danfoss EKE 1A, EKE 1B, EKE 1C, EKE 1D Data sheet

Data Sheet
Superheat controller Type EKE 1A, 1B, 1C, 1D (PV04)
For commercial air conditioning and refrigeration applications
The exible pre-programmed EKE superheat controller from Danfoss provides ultimate software control, allowing you to tailor the performance of your system to your exact requirements. EKE is ideal for controlling a wide range of commercial air conditioning and refrigeration applications, such control helps you to achieve the highest eciency in the system reducing the operational cost by up to 20% with minimal eort. EKE is generally used where there is a requirement for accurate control of superheat or temperature control in connection with air conditioning and refrigeration. The superheat is regulated to the lowest possible value within a short period of time. It regulates the superheat of the evaporator by charging optimally even when there are great variations of load resulting in reduction of energy consumption and operational cost
Typical Applications:
• Chillers
• Processing plant / Cabinet cooling
• Cold store (air coolers)
• A/C plant / Air conditioning
• Heat pumps. Residential Heat Pump
• Transport cooling
• Stepper Motor Driver
AI197986442906en-000501
Features
EKE 1A
EKE 1B
EKE 1C
EKE 1D
Power supply:
Power Supply Type
24 V AC / DC ± 20%••••
Battery Backup input
18-24 V DC••••
Class of insulation
Class II
Data communication
MODBus
RS 485 RTU••
Wired CANbus
(4 wires)
(3 wires)
CANbus RJ 12
Danfoss MMI service port
•••
Inputs::
Number of temperature sensors
123
2
Temperature sensor types
PT1000
NTC 10K, type EKS••••
NTC 10K, type ACCPBT
•••
NTC 10K, type Sensata
•••
Number of Pressure sen­sor
112*
1
Pressure Transmitter types
Ratiometric 0.5 - 4.5 V
•••
Voltage signal 0 – 10 V
•••
Current signal 0 – 20 mA
Share Pressure Signal
Hardware (Up to 5 devi­ces)
•••
Via wired CANbus (not possible to share ratio­metric sensor)
Via MODbus••
Number of external refer­ences
111
1
External reference
0-20mA
User dened current
0-10V
•••
0- 5V
•••
User dened voltage( max 10V)
•••
Digital input Dry contact
3
2
Outputs
Digital output
1
Relay
Normally Open
3A General purpose, 250V ac, 100k
Normally closed
2A General purpose, 250V ac, 100k
Relay Function
Alarm relay or LLSV (Liquid Line Solenoid Valve)
User interfaces
Koolprog Software tool
•••
MMIGRS2 screen••••
Master controller••
Superheat controller, Type EKE 1A, 1B, 1C, 1D
Portfolio overview
Table 1: Portfolio overview
*The 2nd pressure sensor is mounted on AI4
© Danfoss | Climate Solutions | 2022.02 AI197986442906en-000501 | 2
Red constant
Green constant
Flashing red
Flashing green
Flashing red and green
Hardware functions
Digital inputs
Used to interact with the EKE for systems where the EKE is not connected to a system controller via data communica­tion. The available digital inputs DI can be used for the following functions: a. Injection control ON/OFF(DI1). b. Defrost sequence (DI2). c. Heating and cooling selection mode (DI2) d. Preset OD (DI2)
Digital Output (Relay)
• The relay for the liquid line solenoid valve will operate when refrigeration is required
• The contact of the relay is closed in alarm situations and when the controller is de-energized.
• The digital output DO1 O013 can be congured for solenoid valve, max capacity or for alarm function.
NC1+C1
Power On
NO
Power On +Alarm
NC
Power Off
NC
NO1+C1
Power On
NC
Power On +Alarm
NO
Power Off
NO
Handling power failure
For safety reasons the liquid ow to the evaporator must be cut o in case of power failure. The valve’s stepper Motor will remain open in power failure situation There are two ways of coping with this situation One of the following two solutions can be applied in the system
• Mounting of a solenoid valve in front of EEV (using LLSV relay signal from EKE)
• Mounting of a battery backup for EEV valve (Use Danfoss EKE 2U)
Analog Inputs
External Reference Signal: Used for:
• Driving the stepper motor valve to a desired opening degree (Driver Mode)
• Displacing temperature reference, superheat reference or max OD
The voltage signal e.g., 0 – 10 V can be used in all EKE controllers whereas current signal e.g 0 – 20 mA signal is only available in EKE 1C
Communication: RS485 Modbus / CANbus
The controller can be provided with data communication for connecting to other devices in the systems. In this case, monitoring and data collection can be performed from one device i.e., PLC – which will be benecial for the diagnostic or during the installation processes. For example, it is possible to substitute the physical sensors of the EKE controller by writing sensor values via Bus. The frequency of update should be according to the Modbus maximum update interval G004 (Refer to parameter list)
Light-emitting diodes (LEDs)
Two sets of light-emitting diodes make it possible to follow the operation status of the valve and the controller. They indicate the following
• Power/data transmission and Alarm/Error indication
• Stepper valve operational status
LED status:
valve is closed
valve is fully open
valve is moving in close direction
valve is moving in open direction
Error
Superheat controller, Type EKE 1A, 1B, 1C, 1D
Functions
The EKE 1x products supports a wide range of functionalities illustrated in table 3 and 4. Check the user guide for more detail about congurations and other detailed options.
Table 2: Hardware functions
© Danfoss | Climate Solutions | 2022.02 AI197986442906en-000501 | 3
Valve Driver
The EKE controls the opening degree of the valve, the control signal can be an analog signal or a value via communica­tion bus
Superheat Reference Calculation
Fixed Superheat The controller keep the superheat at a xed reference value determined by the user. SH xed setpoint can be varied according to the need of application.
Minimum Stable Superheat (MSS): The superheat control algorithm will attempt to regulate the superheat down to the lowest stable value between the minimum superheat setting, “Min SH” and the maximum superheat setting, “Max. SH”.
LoadAP Superheat LoadAP is a kind of preprogrammed MSS curve. In Load ap application, SH reference follows a dened curve as shown in the diagram. This two-point curve is dened by SH max and SH min, this method will give a robust SH reference and can in many cases be the best t for systems.
Delta temp. superheat SH reference is calculated as a ratio between the media temperature and evaporator tempera­ture. This reference mode is only possible if media temperature (S3) sensor is available and if the system uses n and tube evaporator.
Temperature Control *
EKE has a feature to regulate the temperature control. This can be done with either
Thermostat cut in/cut out function: if temperature is above the set point + dierential, cooling is started with maxi­mum cooling capacity. In maximum capacity superheat is controlled to be on superheat set point. Cooling is active until the temperature is below set point.
Modulating Thermostat (MTR): When temperature is getting close to the MTR reference the cooling capacity gradually reduce so that the temperature can be stable on the MTR reference and the superheat will be oating.
Protection Functions
Failsafe operation: During operation if sensors error occurs, the valve position can be set to full close, xed
opening degree or average calculated OD as required.
Superheat close: When the superheat is below a set minimum value, the valve will close faster to protect the compres­sor from the risk of getting liquid in the suction line and bring the superheat back to superheat reference.
Maximum Operating Pressure (MOP): To reduce the strain on the compressor, a maximum operating pressure is set. If the pressure comes above this limit the controller will control the valve to provide a lower pressure instead of a low su­perheat.
Low Operating Pressure (LOP): known as Cold start feature, it allows applications such as heat pumps to operate at lower ambient conditions to prevent compressor from stopping due to low suction pressure in the startup phase.
High Condensing temperature protection (HCTP)**: High condensing temperature protection will make sure that the load on the condenser is reduced in case a too high condensing temperature is reached. This is done by limiting the valve opening degree.
Minimum S4/leaving media (freeze protection) *: Lowers the ow in the expansion valve if temperature of leaving media out of the evaporator is below a minimum value set by the user.
Other Functions
Fast Start up: Quickly open an EEV valve when compressor turns ON to prevent too low suction pressure as well as for faster stabilization of superheat or temperature set point. This can be ensured by setting either P-control, Start opening degree with protection or Fixed opening degree without protection. This start up condition is kept until the start time expire or superheat reaches at setpoint.
Defrost sequence: The controller does not itself handle defrost of the evaporator. It is however possible to enter a spe­cial defrost sequence which will overrule the normal control of the valve.
Manual control: The valve can be controlled manually by setting the desired opening degree via Analog signal or com­munication bus used for commissioning purpose. A special service mode is also available for service and testing purpose.
Service mode: Service mode is designed to provide a very simple way of operating the valve for diagnostic and service purpose. There is neither application nor protection in this mode. The user can open and close the valve using simple button presses on MMIGRS2.
Superheat controller, Type EKE 1A, 1B, 1C, 1D
Table 3: Control Functions
*Not available in EKE 1A
**Only Available EKE 1C
© Danfoss | Climate Solutions | 2022.02 AI197986442906en-000501 | 4
Danfoss
80G8221.01
EEV
TT
Pe
S2
Battery
Optional connection
Alarm indication
Normal close
Mandatory connection
ON/OFF signal
Modbus or Analog signal
Power 24 V AC / 24 V DC
EKE controller (in driver mode)
MASTER controller
Superheat controller, Type EKE 1A, 1B, 1C, 1D
Applications
EKE series devices are used where precise control of superheat in air conditioning system is needed. It helps achieving high energy eciency and reliable operation
EKE serves 2 main applications:
• Driver Mode
• Controller Mode
1.
Superheat controller
2.
Temperature controller
Driver mode
Driver Mode:A master is commanding the valve open degree to the EKE controller. The control signal can be fed for
example by:
• Analog signal e.g., 0 – 10 V, a 4 – 20 mA
• Bus communication via RS485 (Modbus RTU).
Figure 1: EKE as Driver Mode
NOTE:
'Normal closed' valve in front of EEV is optional alternative to a battery backup solution which closes the EEV in case of power fail. The Digital output can also be used as alarm indication to the master controller. The Master can send a start signal to EKE DI terminals
Controller Mode
Controller Mode:
Superheat Control: EKE can serve as a PI controller that controls the superheat of the evaporator based on a
pressure Pe and temperature (S2) sensors. In superheat mode the controller will control the superheat to be stable and close to the superheat reference. If superheat is too low the ow in the expansion is decreased and superheat will be higher
© Danfoss | Climate Solutions | 2022.02 AI197986442906en-000501 | 5
Danfoss
80G8222.01
TT S2
EEV
EKE 1X
Pe
Danfoss
80G8223.01
EEV
EKE controller
Preset OD
Defrost Heat / cool mode
Battery Power 24 V AC / 24 V DC
External reference
Optional connection
Mandatory connection
Temperature control
Alarm indication
Normal close
External main switch
TT
S4
Pe
TT S2
TT
S3
Superheat controller, Type EKE 1A, 1B, 1C, 1D
Figure 2: Superheat control application
Temperature controller The temperature control is an ON/OFF thermostat that opens/closes the stepper valve or modulating thermostat that regulates temperature more smoothly following a temperature reference point. The temperature control can be accomplished via a signal from temperature sensor S3 placed in the air ow before the evaporator or S4 placed in the air ow after the evaporator.
EKE has 2 methods of controlling temperature:
• ON/OFF thermostat
• Modulating thermostat (MTR)
The need for cooling can either be dened by the incoming media (S3) or the outgoing media (S4) temperature
Figure 3: Temperature control application
NOTE:
EKE1A can only work in the driver mode or superheat control mode as it supports only one temperature sensor input
© Danfoss | Climate Solutions | 2022.02 AI197986442906en-000501 | 6
Feature
Description
Power supply
Galvanic isolation by switch mode power supply Input voltage rating (AC): 24 V AC ± 20 % (min.19.2 V AC - max. 28.8 V AC Input frequency (AC): 50 / 60 Hz Input voltage rating (DC): 24 V DC (min. 20 - max. 40 V DC) Provides 5 W at 5 V and 15 V outputs isolated from the 24 V input Insulation between power supply and the extra-low voltage. Class of insulation Class II
Power Consumption
Total Power consumption with following valve in operation and MMIGRS2 con­nected to the controller: CCMT 16 - CCMT 42: 15VA/10W ETS 6: 11 VA / 7.5W ETS 12C - ETS 100C: 20VA / 14W KVS C: 20VA / 14W ETS 12.5 - ETS 400 7 VA / 5W CCMT 2 - CCMT 8 7 VA / 5W CTR 20: 7 VA / 5W
Plastic Housing
• DIN rail mounting complying with EN 50022
• Self-extinguishing V0 according to IEC 60695-11-10 and glowing / hot wire test at 960 °C according to IEC 60695-2-12
• Material used for Enclosure are UL94-V0 and RoHS compliant
• Ball test: 125 °C according to IEC 60730-1
• Leakage current: ≥ 250 V according to IEC 60112
Connectors
• Plug able Screw connector Pitch 3.5 mm, relay and power connector Pitch 5 mm, CAN MMI: Modular Jack 6P4C
• Material used for connectors are RoHS and UL approved
Feature
Type
Description
Protection
Short circuit
Motor driver: dissipative over current protection
Over voltage
Analog input: current limit and internal clamp diode Digital input: current limit and internal clamp diode Communication: transceiver IC
Over Temperature
Motor driver: thermal shutdown at 150 °C
Unstable Digital Input
Continuous variation of the digital input state
I/O
Type
Specications
Analog inputs
• Max. 15 V input voltage
• Open circuit HW diagnostics available for voltage input on: AI3, AI4 (EKE 1C) AI4 (EKE 1A and EKE 1B).
WARNING:
Do not connect voltage sources without current limitation (overall 80 mA) to analog inputs while unit is not powered.
0 – 5 V
EKE 1C (AI3, AI4) and EKE1A/1B/1D AI3 | Accuracy ± 40 mV, resolution 1.2 mV.
0 – 10 V
EKE 1C (AI3, AI4) and EKE1A/1B/1D AI3 | Accuracy ± 50 mV, resolution 2.5 mV.
0 – 20 mA (EKE 1C only)
Accuracy ± 100 μA, resolution 10 μA. Input resistance: <100 Ω
NTC Sensor
NTC temperature probes: 10 kΩ at 25 °C range: 300 kΩ to 100 Ω Accuracy: 50 – 120 °C: 1.5 K, -40 – 50 °C: 0.4 K, 0 °C: 0.2 K Resolution: ≤ 0.1 K, ≤ 0.3 K (EKC 1C, AI5)
Pt1000 sensor
Range: 723 Ω to 1684 Ω Accuracy: ≤ 0.5 K Resolution: ≤ 0.1K
Pressure Sensor
Type: Ratiometric
• Accuracy: 1.6 %
• Range: 0.5 – 4.5 V
• Resolution: 1.2 mV
• Supply voltage: 5 V DC / 15 mA, overload protection approximately 150 mA
Superheat controller, Type EKE 1A, 1B, 1C, 1D
Product specication
Technical data
Table 4: General specication
Table 5: Electrical specication
Table 6: Input/Output
© Danfoss | Climate Solutions | 2022.02 AI197986442906en-000501 | 7
I/O
Type
Specications
Digital Input DI
Voltage free contacts
Steady current of 1 mA (EKE 1C only). A cut-in input will activate a func­tion. Cleaning current of 100 mA at 15 V DC. On: RIL <= 300 Ω . O: RIH >= 3.5kΩ. No destructive if Vbat + is connected to DI (only for DI on bottom pcb). Min. pulse time 64 ms.
Digital output (D01)
Relay
Normally Open: 3 A General purpose, 250 V AC, 100 k cycle Normally Open: 3 A Inductive (AC-15), 250 V AC, 100 k cycle Normally Closed: 2 A General purpose, 250 V AC, 100 k cycle
Stepper motor
Bipolar and unipolar stepper Mo­tor Output
Danfoss ETS / KVS / ETS C / KVS C / CCMT 2 – CCMT 42 / CTR / CCMTL Valves (green, red, black, white)
ETS 6 / CCMT 0 / CCMT 1 (black, red, yellow, orange) Other Valves:
• speed 10 - 400 pps
• drive mode full step, half step, 1/8 microstep
max. peak phase current: 1.2 A (848 mA RMS)
• max. output power 12 W
Battery backup
VBATT: 18 – 24 V DC: Leakage: <15 μA @30 V DC Optional: critical low alarm below 12V Optional: low alarm at 17 V, high voltage alarm at 27 V The valve will not close at power fail if voltage is higher than 27 V Required power to do 1 closing of stepper valve: ETS 6: 110 J / 30 VmAh ETS 12.5 - ETS 400: 60 J / 17 VmAh KVS 15 / KVS 42: 60 J / 17 VmAh ETS 12C - ETS 100C: 55 J / 15 VmAh KVS 2C / KVS 5C: 55 J / 15 VmAh CCMT 2 - CCMT 8: 60 J / 17 VmAh CCMT 16 - CCMT 42: 175 J / 49 VmAh CTR 20: 60 J / 17 VmAh
NOTE:
Danfoss recommends using EKE 2U as a battery backup
Communication
RS-485 RTU (only for EKE 1B and 1C)
Galvanic isolation. No Built-in termination. Supported commands with max. of 50 ms response time: 0 x 03, 0 x 04, 0 x 06 Supported commands without dened max response time : 0x08, 0x10, 0x14, 0x15,0x2b
CAN
• EKE 1A/1B: CANOpen over RJ12 connector.
• EKE 1C: CANOpen over CAN 4pin terminal and RJ12 connector.
• EKE 1D: CANOpen over CAN 3pin terminal and RJ12 connector.
NOTE:
• For EKE EKE 1A/1B, RJ12 connector is used directly connect and sup­ply a user interface MMI
• Refer to the user guide for information about type of connection ca­bles
Feature
Description
Operating conditions
-20 – 60 °C, 90% RH non-condensing
Storage / Transport conditions
-30 – 80 °C, 90% RH non-condensing
Vibration and shock
According to IEC 60068-2-27 Ea
Integration
In Class I and / or II appliances
Index of protection
IP40 only on the front cover (General IP20 )
PCB protection
None (no conformal coating)
Period of electric stress across insulating parts
Long
Superheat controller, Type EKE 1A, 1B, 1C, 1D
Environmental conditions:
Table 7: Environmental conditions
© Danfoss | Climate Solutions | 2022.02 AI197986442906en-000501 | 8
Loading...
+ 17 hidden pages