Data Sheet
Superheat controller
Type EKE 1A, 1B, 1C, 1D (PV04)
For commercial air conditioning and refrigeration applications
The exible pre-programmed EKE superheat
controller from Danfoss provides ultimate
software control, allowing you to tailor the
performance of your system to your exact
requirements. EKE is ideal for controlling a wide
range of commercial air conditioning and
refrigeration applications, such control helps
you to achieve the highest eciency in the
system reducing the operational cost by up to
20% with minimal eort. EKE is generally used
where there is a requirement for accurate
control of superheat or temperature control in
connection with air conditioning and
refrigeration. The superheat is regulated to the
lowest possible value within a short period of
time. It regulates the superheat of the
evaporator by charging optimally even when
there are great variations of load resulting in
reduction of energy consumption and
operational cost
Typical Applications:
• Chillers
• Processing plant / Cabinet cooling
• Cold store (air coolers)
• A/C plant / Air conditioning
• Heat pumps. Residential Heat Pump
• Transport cooling
• Stepper Motor Driver
AI197986442906en-000501
Number of temperature
sensors
Number of Pressure sensor
Pressure Transmitter
types
Hardware (Up to 5 devices)
Via wired CANbus (not
possible to share ratiometric sensor)
Number of external references
User dened voltage( max
10V)
Digital input Dry contact
3A General purpose, 250V ac, 100k
2A General purpose, 250V ac, 100k
Alarm relay or LLSV (Liquid Line Solenoid Valve)
Superheat controller, Type EKE 1A, 1B, 1C, 1D
Portfolio overview
Table 1: Portfolio overview
*The 2nd pressure sensor is mounted on AI4
© Danfoss | Climate Solutions | 2022.02 AI197986442906en-000501 | 2
Used to interact with the EKE for systems where the EKE is not connected to a system controller via data communication.
The available digital inputs DI can be used for the following functions:
a. Injection control ON/OFF(DI1). b. Defrost sequence (DI2). c. Heating and cooling selection mode (DI2) d. Preset OD
(DI2)
• The relay for the liquid line solenoid valve will operate when refrigeration is required
• The contact of the relay is closed in alarm situations and when the controller is de-energized.
• The digital output DO1 O013 can be congured for solenoid valve, max capacity or for alarm function.
For safety reasons the liquid ow to the evaporator must be cut o in case of power failure. The valve’s stepper Motor
will remain open in power failure situation
There are two ways of coping with this situation
One of the following two solutions can be applied in the system
• Mounting of a solenoid valve in front of EEV (using LLSV relay signal from EKE)
• Mounting of a battery backup for EEV valve (Use Danfoss EKE 2U)
External Reference Signal:
Used for:
• Driving the stepper motor valve to a desired opening degree (Driver Mode)
• Displacing temperature reference, superheat reference or max OD
The voltage signal e.g., 0 – 10 V can be used in all EKE controllers whereas current signal e.g 0 – 20 mA signal is only
available in EKE 1C
Communication: RS485 Modbus / CANbus
The controller can be provided with data communication for connecting to other devices in the systems.
In this case, monitoring and data collection can be performed from one device i.e., PLC – which will be benecial for
the diagnostic or during the installation processes.
For example, it is possible to substitute the physical sensors of the EKE controller by writing sensor values via Bus. The
frequency of update should be according to the Modbus maximum update interval G004 (Refer to parameter list)
Light-emitting diodes (LEDs)
Two sets of light-emitting diodes make it possible to follow the operation status of the valve and the controller. They
indicate the following
• Power/data transmission and Alarm/Error indication
• Stepper valve operational status
LED status:
valve is moving in close direction
valve is moving in open direction
Superheat controller, Type EKE 1A, 1B, 1C, 1D
Functions
The EKE 1x products supports a wide range of functionalities illustrated in table 3 and 4. Check the user guide for
more detail about congurations and other detailed options.
Table 2: Hardware functions
© Danfoss | Climate Solutions | 2022.02 AI197986442906en-000501 | 3
The EKE controls the opening degree of the valve, the control signal can be an analog signal or a value via communication bus
Superheat Reference Calculation
• Fixed Superheat The controller keep the superheat at a xed reference value determined by the user. SH xed setpoint
can be varied according to the need of application.
• Minimum Stable Superheat (MSS): The superheat control algorithm will attempt to regulate the superheat down to
the lowest stable value between the minimum superheat setting, “Min SH” and the maximum superheat setting, “Max.
SH”.
• LoadAP Superheat LoadAP is a kind of preprogrammed MSS curve. In Load ap application, SH reference follows a
dened curve as shown in the diagram. This two-point curve is dened by SH max and SH min, this method will give a
robust SH reference and can in many cases be the best t for systems.
• Delta temp. superheat SH reference is calculated as a ratio between the media temperature and evaporator temperature. This reference mode is only possible if media temperature (S3) sensor is available and if the system uses n and tube
evaporator.
EKE has a feature to regulate the temperature control. This can be done with either
• Thermostat cut in/cut out function: if temperature is above the set point + dierential, cooling is started with maximum cooling capacity. In maximum capacity superheat is controlled to be on superheat set point. Cooling is active until
the temperature is below set point.
• Modulating Thermostat (MTR): When temperature is getting close to the MTR reference the cooling capacity gradually
reduce so that the temperature can be stable on the MTR reference and the superheat will be oating.
• Failsafe operation: During operation if sensors error occurs, the valve position can be set to full close, xed
opening degree or average calculated OD as required.
• Superheat close: When the superheat is below a set minimum value, the valve will close faster to protect the compressor from the risk of getting liquid in the suction line and bring the superheat back to superheat reference.
• Maximum Operating Pressure (MOP): To reduce the strain on the compressor, a maximum operating pressure is set. If
the pressure comes above this limit the controller will control the valve to provide a lower pressure instead of a low superheat.
• Low Operating Pressure (LOP): known as Cold start feature, it allows applications such as heat pumps to operate at
lower ambient conditions to prevent compressor from stopping due to low suction pressure in the startup phase.
• High Condensing temperature protection (HCTP)**: High condensing temperature protection will make sure that
the load on the condenser is reduced in case a too high condensing temperature is reached. This is done by limiting the
valve opening degree.
• Minimum S4/leaving media (freeze protection) *: Lowers the ow in the expansion valve if temperature of leaving
media out of the evaporator is below a minimum value set by the user.
• Fast Start up: Quickly open an EEV valve when compressor turns ON to prevent too low suction pressure as well as for
faster stabilization of superheat or temperature set point. This can be ensured by setting either P-control, Start opening
degree with protection or Fixed opening degree without protection. This start up condition is kept until the start time
expire or superheat reaches at setpoint.
• Defrost sequence: The controller does not itself handle defrost of the evaporator. It is however possible to enter a special defrost sequence which will overrule the normal control of the valve.
• Manual control: The valve can be controlled manually by setting the desired opening degree via Analog signal or communication bus used for commissioning purpose. A special service mode is also available for service and testing purpose.
• Service mode: Service mode is designed to provide a very simple way of operating the valve for diagnostic and service
purpose. There is neither application nor protection in this mode. The user can open and close the valve using simple
button presses on MMIGRS2.
Superheat controller, Type EKE 1A, 1B, 1C, 1D
Table 3: Control Functions
*Not available in EKE 1A
**Only Available EKE 1C
© Danfoss | Climate Solutions | 2022.02 AI197986442906en-000501 | 4
Danfoss
80G8221.01
EEV
TT
Pe
S2
Battery
Optional connection
Alarm indication
Normal close
Mandatory connection
ON/OFF signal
Modbus or Analog signal
Power 24 V AC / 24 V DC
EKE controller (in driver mode)
MASTER controller
Superheat controller, Type EKE 1A, 1B, 1C, 1D
Applications
EKE series devices are used where precise control of superheat in air conditioning system is needed. It helps
achieving high energy eciency and reliable operation
EKE serves 2 main applications:
• Driver Mode
• Controller Mode
1.
Superheat controller
2.
Temperature controller
Driver mode
Driver Mode:A master is commanding the valve open degree to the EKE controller. The control signal can be fed for
example by:
• Analog signal e.g., 0 – 10 V, a 4 – 20 mA
• Bus communication via RS485 (Modbus RTU).
Figure 1: EKE as Driver Mode
NOTE:
'Normal closed' valve in front of EEV is optional alternative to a battery backup solution which closes the EEV in case
of power fail. The Digital output can also be used as alarm indication to the master controller. The Master can send a
start signal to EKE DI terminals
Controller Mode
Controller Mode:
Superheat Control: EKE can serve as a PI controller that controls the superheat of the evaporator based on a
pressure Pe and temperature (S2) sensors. In superheat mode the controller will control the superheat to be stable
and close to the superheat reference. If superheat is too low the ow in the expansion is decreased and superheat
will be higher
© Danfoss | Climate Solutions | 2022.02 AI197986442906en-000501 | 5
Danfoss
80G8222.01
TT
S2
EEV
EKE 1X
Pe
Danfoss
80G8223.01
EEV
EKE controller
Preset OD
Defrost
Heat / cool mode
Battery
Power 24 V AC / 24 V DC
External reference
Optional connection
Mandatory connection
Temperature control
Alarm indication
Normal close
External main switch
TT
S4
Pe
TT
S2
TT
S3
Superheat controller, Type EKE 1A, 1B, 1C, 1D
Figure 2: Superheat control application
Temperature controller The temperature control is an ON/OFF thermostat that opens/closes the stepper valve or
modulating thermostat that regulates temperature more smoothly following a temperature reference point. The
temperature control can be accomplished via a signal from temperature sensor S3 placed in the air ow before the
evaporator or S4 placed in the air ow after the evaporator.
EKE has 2 methods of controlling temperature:
• ON/OFF thermostat
• Modulating thermostat (MTR)
The need for cooling can either be dened by the incoming media (S3) or the outgoing media (S4) temperature
Figure 3: Temperature control application
NOTE:
EKE1A can only work in the driver mode or superheat control mode as it supports only one temperature sensor
input
© Danfoss | Climate Solutions | 2022.02 AI197986442906en-000501 | 6
Galvanic isolation by switch mode power supply
Input voltage rating (AC): 24 V AC ± 20 % (min.19.2 V AC - max. 28.8 V AC
Input frequency (AC): 50 / 60 Hz
Input voltage rating (DC): 24 V DC (min. 20 - max. 40 V DC)
Provides 5 W at 5 V and 15 V outputs isolated from the 24 V input
Insulation between power supply and the extra-low voltage.
Class of insulation Class II
Total Power consumption with following valve in operation and MMIGRS2 connected to the controller:
CCMT 16 - CCMT 42: 15VA/10W
ETS 6: 11 VA / 7.5W
ETS 12C - ETS 100C: 20VA / 14W
KVS C: 20VA / 14W
ETS 12.5 - ETS 400 7 VA / 5W
CCMT 2 - CCMT 8 7 VA / 5W
CTR 20: 7 VA / 5W
• DIN rail mounting complying with EN 50022
• Self-extinguishing V0 according to IEC 60695-11-10 and glowing / hot wire
test at 960 °C according to IEC 60695-2-12
• Material used for Enclosure are UL94-V0 and RoHS compliant
• Ball test: 125 °C according to IEC 60730-1
• Leakage current: ≥ 250 V according to IEC 60112
• Plug able Screw connector Pitch 3.5 mm, relay and power connector Pitch 5
mm, CAN MMI: Modular Jack 6P4C
• Material used for connectors are RoHS and UL approved
Motor driver: dissipative over current protection
Analog input: current limit and internal clamp diode
Digital input: current limit and internal clamp diode
Communication: transceiver IC
Motor driver: thermal shutdown at 150 °C
Continuous variation of the digital input state
• Max. 15 V input voltage
• Open circuit HW diagnostics available for voltage input on: AI3, AI4
(EKE 1C) AI4 (EKE 1A and EKE 1B).
WARNING:
Do not connect voltage sources without current limitation (overall 80
mA) to analog inputs while unit is not powered.
EKE 1C (AI3, AI4) and EKE1A/1B/1D AI3 | Accuracy ± 40 mV, resolution 1.2
mV.
EKE 1C (AI3, AI4) and EKE1A/1B/1D AI3 | Accuracy ± 50 mV, resolution 2.5
mV.
Accuracy ± 100 μA, resolution 10 μA.
Input resistance: <100 Ω
NTC temperature probes: 10 kΩ at 25 °C range: 300 kΩ to 100 Ω
Accuracy: 50 – 120 °C: 1.5 K, -40 – 50 °C: 0.4 K, 0 °C: 0.2 K
Resolution: ≤ 0.1 K, ≤ 0.3 K (EKC 1C, AI5)
Range: 723 Ω to 1684 Ω
Accuracy: ≤ 0.5 K
Resolution: ≤ 0.1K
Type: Ratiometric
• Accuracy: 1.6 %
• Range: 0.5 – 4.5 V
• Resolution: 1.2 mV
• Supply voltage: 5 V DC / 15 mA, overload protection approximately
150 mA
Superheat controller, Type EKE 1A, 1B, 1C, 1D
Product specication
Technical data
Table 4: General specication
Table 5: Electrical specication
Table 6: Input/Output
© Danfoss | Climate Solutions | 2022.02 AI197986442906en-000501 | 7
Steady current of 1 mA (EKE 1C only). A cut-in input will activate a function.
Cleaning current of 100 mA at 15 V DC.
On: RIL <= 300 Ω . O: RIH >= 3.5kΩ.
No destructive if Vbat + is connected to DI (only for DI on bottom pcb).
Min. pulse time 64 ms.
Normally Open: 3 A General purpose, 250 V AC, 100 k cycle
Normally Open: 3 A Inductive (AC-15), 250 V AC, 100 k cycle
Normally Closed: 2 A General purpose, 250 V AC, 100 k cycle
Bipolar and unipolar stepper Motor Output
Danfoss ETS / KVS / ETS C / KVS C / CCMT 2 – CCMT 42 / CTR / CCMTL
Valves (green, red, black, white)
ETS 6 / CCMT 0 / CCMT 1 (black, red, yellow, orange)
Other Valves:
• speed 10 - 400 pps
• drive mode full step, half step, 1/8 microstep
•
max. peak phase current: 1.2 A (848 mA RMS)
• max. output power 12 W
VBATT: 18 – 24 V DC:
Leakage: <15 μA @30 V DC
Optional: critical low alarm below 12V
Optional: low alarm at 17 V, high voltage alarm at 27 V
The valve will not close at power fail if voltage is higher than 27 V
Required power to do 1 closing of stepper valve:
ETS 6: 110 J / 30 VmAh
ETS 12.5 - ETS 400: 60 J / 17 VmAh
KVS 15 / KVS 42: 60 J / 17 VmAh
ETS 12C - ETS 100C: 55 J / 15 VmAh
KVS 2C / KVS 5C: 55 J / 15 VmAh
CCMT 2 - CCMT 8: 60 J / 17 VmAh
CCMT 16 - CCMT 42: 175 J / 49 VmAh
CTR 20: 60 J / 17 VmAh
NOTE:
Danfoss recommends using EKE 2U as a battery backup
RS-485 RTU (only for EKE 1B and
1C)
Galvanic isolation. No Built-in termination.
Supported commands with max. of 50 ms response time: 0 x 03, 0 x 04, 0
x 06
Supported commands without dened max response time : 0x08, 0x10,
0x14, 0x15,0x2b
• EKE 1A/1B: CANOpen over RJ12 connector.
• EKE 1C: CANOpen over CAN 4pin terminal and RJ12 connector.
• EKE 1D: CANOpen over CAN 3pin terminal and RJ12 connector.
NOTE:
• For EKE EKE 1A/1B, RJ12 connector is used directly connect and supply a user interface MMI
• Refer to the user guide for information about type of connection cables
-20 – 60 °C, 90% RH non-condensing
Storage / Transport conditions
-30 – 80 °C, 90% RH non-condensing
According to IEC 60068-2-27 Ea
In Class I and / or II appliances
IP40 only on the front cover (General IP20 )
None (no conformal coating)
Period of electric stress across insulating parts
Superheat controller, Type EKE 1A, 1B, 1C, 1D
Environmental conditions:
Table 7: Environmental conditions
© Danfoss | Climate Solutions | 2022.02 AI197986442906en-000501 | 8