Danfoss EKC 414A User Manual

REFRIGERATION AND AIR CONDITIONING
ADAP-KOOL
®
Refrigeration control systems
Controller for controlling one evaporator
EKC 414A
Manual
2 Manual RS.8C.K3.02 © Danfoss 09-2003 EKC 414A
Introduction
Application
The controller is a complete control unit for refrigeration appliances with integrated refrigeration-technical functions capable of replacing a setup of thermostats and timers.
The relays are used for operating:
- Compressor
- Fan
- defrost
- Alarm
- Light
The controller can operate one evaporator.
The intended placing of the controller is “on/near the refrigeration appliance” and the controller is therefore provided with plugs at the sensor connection points. All sensors used must therefore be fitted with a belonging plug.
Operation
The controller comes without operating buttons on the front panel, and it will require no operation once it has been set and started up. When the controller is operated, it can be done in one of the following ways:
• Connection of an external display with operating buttons
- The display will currently show measurements and settings in the menu system
- In case of malfunction the relevant error code will be shown on the display
- Four light-emitting diodes will show the system’s actual function: › refrigeration › power for the AKV valve › defrost › fan operating › when there is an alarm the three LED’s will flash
• Data communication The controller can be hooked up with other products in the series of ADAP-KOOL® refrigeration controls. The operation, monitoring and data collection can then be performed from a PC – either on site or at a service company.
Customer display
If the temperature in the appliance is to be visible to, say, customers, a display can be mounted.
Inject ON function
The expansion valve closes when the signal at the 230V input is removed or receives a signal via the data communication. In this way it is ensured that the expansion valve will not charge the evaporator when the compressor has stopped. (The threading of the function may be cancelled via a setting).
Digital input
A digital input can be defined for one of the following applica­tions: Door alarm Defrost start Night operation Start/stop of regulation Joint defrost start/stop with a master/slave function
Data communication
The controller is provided with LON RS 485 data communica­tion. More about this data communication on page 18.
EKC 414A Manual RS.8C.K3.02 © Danfoss 09-2003 3
Function
Liquid supply
The supply of liquid is controlled on the basis of signals from the pressure transmitter, temperature sensor S2 and the air temperature. The sensors create a signal so that the superheat is continuously kept at a minimum whatever the operating conditions.
The AKV valve functions both as expansion valve and solenoid valve. The valve opens and closes based on signals from the controller.
Temperature control
The temperature is controlled on the basis of signals from one or two temperature sensors. If there is only one sensor it may optionally be placed in the air before or after the evaporator. If there are two sensors, one must be placed before and one after the evaporator. With a setting it is subsequently defined how large an influence the individual sensor is to have on the control. The actual temperature control can take place in two ways: as an ordinary ON/OFF regulation with a belonging differential, or as a modulating control there the temperature variation will not be nearly as great as in ON/OFF control. There is however a limit to the use of them as a modulating control can only be used in central plant. In a decentralised plant the thermostat function with ON/OFF control should be selected. In a central plant the thermostat function may either be selected for ON/OFF control or modulating control.
Defrost
With a simple function defrost can be started x times per day and night. But the controller may also receive a signal from a defrost clock or from another unit via the data communication, so that defrost will take place at defined times of the day or night. An on-going defrost can be stopped based on temperature, normally the one measured with the S5 sensor, or it may be stopped based on time. A combination with stop based on temperature and with the time factor as a precautionary measure is also a possibility.
Clock module (accessory)
If the controller is mounted without data communication and defrost has to be carried out at specific times, a clock module can be mounted. The controller comes prepared with plug and terminals so that the module just has to be pushed in. Subsequently, up to six defrosts per day can be set. The module has battery back-up.
On / Off control
Modulating control
4 Manual RS.8C.K3.02 © Danfoss 09-2003 EKC 414A
noitcnuF -araP
retem
aivnoitarepO
noitacinummocatad
Th noitcnuftatsomre lortnoctatsomrehT
ecnerefeR
tesehtfoegnahcA.eulavtesehtfosisabehtnosetalugertatsomrehtehT
.30rdna20rnisgnitteshtiwdekcol/detimilebnaceulav
-pmettuotuC
laitnereffiD
eht,laitnereffidteseht+ecnereferehtnahtrehgihsieruarepmetehtnehW
semocerutarepmetehtnehwniagatuotuclliwtI.nituceblliwyalerrosserpmoc
.ecnerefertesehtotnwod
10rlaitnereffiD
ecnerefeRoitatimiln
tahtos,nwoddeworranebyamecnereferehtrofegnargnittess’rellortnocehT
gnitluserhtiw-yllatnediccatestoneraseulavwoloothcumrohgihoothcum
.segamad
eulavecnereferelbawolla.xameht,ecnereferehtfognitteshgihootadiovaoT
.derewolebtsum
20rtuotuCxaM
ootadiovaoT eulavecnereferelbawolla.nimeht,ecnereferehtfognitteswol
.desaercniebtsum
30rtuotuCniM
tinuerutarepmeT
niseulaverutarepmetwohsotsirellortnocehtfierehteSC°
.F°niro
50rtinu.pmeT
0=
ehtrevetahw,MKAnoC°ylnO(
)gnittes
)tuoS(4SmorflangisfonoitcerroC
elbacrosnesgnolhguorhtytilibissopnoitasnepmoC
90rtuoStsujdA
)niS(3SmorflangisfonoitcerroC
elbacrosnesgnolhguorhtytilibissopnoitasnepmoC
01rniStsujdA
noitaregirferfopots/tratS
.deppotsdnadetratsebnacnoitaregirfergnittessihthtiW
hctiwslanretxeehthtiwdehsilpmoccaeboslanacnoitaregirferfopots/tratS
.tupniIDehtotdetcennocnoitcnuf
21rhctiwSniaM
eulavkcabtesthgiN
ehtnehweulavsihtybdesaercnieblliwecnerefertess’tatsomrehtehT
otsierehtfieulavevitagenatceleS(.noitarepothginotrevosegnahcrellortnoc
).noitalumuccadloceb
31rtesffothgiN
noitcnuftatsomrehT
yranidronasarehtiE.etarepootsitatsomrehtehtwohdenifedsitiereH
.tatsomrehtgnitaludomasarotatsomrehtFFO/NO
tatsomrehtFFO/NO:1
gnitaludoM:2
ostnaregirferfowolfehttimillliwevlavVKAeht”gnitaludom”sinoitareponehW
.tatsomrehtFFO/NOehtrofnahtsseleblliwnoitairaverutarepmetehttaht
.gnittestatsomrehtFFO/NOehttcelestsumuoytnalpdesilartnecedanI
onlacitnediebtsumlaitnereffiddnaeulavtuotucrofsgnittess’tatsomrehtehT
tatsomrehtehtsi4Sfi,K5.g.E.detcelessisnoitcnufowtehtfohcihwrettam
.rosnestatsomrehtehtsi3Sfi,K3ro,rosnes
.K5nahtrewoltesebtontsumlaitnereffidehtstatsomrehtgnitaludomroF
41redom.mrehT
Ref. Dif.
Survey of functions
EKC 414A Manual RS.8C.K3.02 © Danfoss 09-2003 5
rosnestatsomrehtfonoitceleS
,3S.noitcnuflortnocstirofesuotsitatsomrehtehtrosnesehtenifeduoyereH
htiW.)niS(desusi3Sylno,%0gnittesehthtiW.mehtfonoitanibmocaro,4S
)tuoS(4Sylno,%001
51r%tuoS
noitcnuftleM
ehttahtserusnenoitcnufehT.)C°01+ot5-(noitaregirferfolortnocrofylnO
otsinoitcnufehtnetfowohtesuoyereH.tsorfybdesolcebtonlliwrotaropave
sierehtfieciro(retawottsorfehtmrofsnartecnehdnanoitaregirferehtpots
.)tsorfhcumoot
61rlavretnitleM
doireptleM
.tsalotsinoitcnuftlemgniog-nonagnolwohtesuoyereH
71rdoireptleM
kcabteSthgiN
noitarepoyadsevigFFO
noitarepothginsevigNO
sgnittesmralA sgnitteSmralA
.snoitautistnereffidnimralaevignacrellortnocehT
tnorfehtnohsalflliw)DEL(sedoidgnittime-thgilehtmralanasierehtnehW
.261AKEfolenap
noyaleDmralaerutarepmet
eblliwnoitcnufremita,dedeecxesi41Aro31AseulavtimilowtehtfoenofI
.dessapsiyaledemittesanehwelbisivemocebylnolliwmralaehT.detrats
.setunimnitessiyaledemitehT
30AyaledmralA
mralaroodrofyaledemiT
ehtninoitinifedees(noitcnufgnirotinomroodarofdesusitupnilatigidehtfI
nepohtiwdoirepnevigalitnunevigebtonlliwmralana)noitces”suoenallecsiM
.despalesahrood
.setunimnitessiyaledemitehT.
40AlednepOrooD
gniloocrofyaledemiT
aretfayletaidemmi,tsorfedgnirud,pu-tratsgniruddesusiyaledemitsihT
otrevo-egnahceblliwerehT.desuneebsahnoitcnufNOehtnehwdna,tsorfed
tesehtwolebdeppordsaherutarepmetehtnehw)30A(yaledemitlamroneht
.timilmralareppu
.setunimnitessiyaledemitehT
21AlednwodlluP
timilmralareppU
sieulavtimilehT.tratsotsierutarepmethgihrofmralaehtnehwtesuoyereH
.noitarepothgingniruddesiareblliweulavtimilehT.)eulavetulosba(nites
fidesiarebylnolliwtub,kcabtesthginroftesenoehtsaemasehtsieulavehT
.evitisopsieulaveht
31AriAmiLhgiH
timilmralarewoL
sieulavtimilehT.tratsotsierutarepmetwolrofmralaehtnehwtesuoyereH
.)eulavetulosba(nites
41AriAmiLwoL
mralateseR
nehwsmralallastesernoitcnufehT
.NO.sopnites
rorreCKE
.sutatsmralaehtdaernacuoyereH
Cnoitcnufrosserpmo lortnocrosserpmoC
ehtnehW.tatsomrehtehthtiwnoitcnujnocniskrowyalerrosserpmocehT
.detarepoebyalerrosserpmocehtlliwnoitaregirferrofsllactatsomreht
semitgninnuR
sirosserpmocehtemitehtroftesebnacseulav,noitareporalugerritneverpoT
.deppotsebotsahtsaeltatignolwohrofdnA.detratsneebsahtiecnonurot
)setunimni(emit-NO.niM 10cemitnO.niM
)setunimni(emit-FFO.niM 20cemitffO.niM
6 Manual RS.8C.K3.02 © Danfoss 09-2003 EKC 414A
tsorfeD lortnoctsorfeD
langisaaiv,noitacinummocatadehtaiv:syawevifnidetratsebnactsorfedA
ybronoitcnufremitlanretninaaiv,gnittesdnaeludomkcolcaiv,tupniIDehtta
ehttesotdednemmocersitI.snottublortnoc’syalpsidehtforewolehtnohsupa
noitcnufremitehT.desusisnoitpotsrifeerhtehtfoenofinevenoitcnufremit
ehT.eudrevoebdluohstratstsorfedlanigiroehtfidoirepytefassatcanehtlliw
ebnacrosneserutarepmetaro,emitnodesabdeppotsebnacflestitsorfed
erutarepmetnodesabdeppotsebnactsorfedtahtosrotaropaveehtnodecalp
.eulav
tsorfeDerutarepmetpots
ebnactsorfedeht,rotaropaveehtnodetnuomneebsahrosnestsorfedafI
tsorfedafI.tessieulaverutarepmetehT.erutarepmetnevigatadeppots
.emitnodesabdeppotseblliwtsorfedeht,detnuomneebtonsahrosnes
.01ddna4d.fC
20dpmeTpotS.feD
stratstsorfedneewteblavretnI
aaivronoitacinummocatadehtaivtsorfedehttratsotdednemmocersitI
ehtfierusaemyranoituacerpsagnittessihtesunehtdnatupniIDehttalangis
retaergebtsumlavretniemiteht(raeppaotliafdluohslangistsorfedlamron
.)stratstsorfedlamronowtneewtebemitehtnaht
noitcnuftratstsorfedelpmisasadesueboslayamnoitcnuflavretniehttuB
otsitsorfedfI.sruohthgieyreve,yas,yllacidoirepdetratssitsorfedehterehw
.ylgnidroccaedamebtsumgnitteseht,yadehtfosemitcificepstademrofrepeb
.)eruliafrewoparetfatesorezsiretnuoclanretniehT(
.tratstsorfedhcaetatesersilavretniemitehT
30dlavretnI.feD
noitarudtsorfed.xaM
lliwgnittessiht,erutarepmetnodesabtsorfedpotsotnesohcevahuoyfI
nodesabpotsonfideppotseblliwtsorfedehterehwdoirepytefasaetutitsnoc
.nehtybecalpnekatsaherutarepmet desabpotstsorfeddetcelesevahuoyfI
.emittsorfedehteblliwgnittessiht,emitno
40demit.feDxaM
pu-tratsgnirudsnituctsorfedfotnemecalpsidemiT
rosecnailppanoitaregirferlarevesevahuoyfi,tnavelerylnosinoitcnufehT
oslasinoitcnufsihT.decalpsidebottsorfedehtekildluowuoyerehwspuorg
.)30d(tratslavretnihtiwtsorfeddetcelesevahuoyfitnavelerylno
yrevehtroftub,setunimforebmuntesehtybtsorfedehtsyalednoitcnufehT
.desigreneneebsahrellortnocehtnehwtiseodylnotitsorfedtsrif
50d.ggatsemiT
emitffo-pirD
litnudnatsorfedafodneehtmorfespaleotsitahtemitehttesuoyereH
osserpmocehtffognippirdsiretawnehwemitehT(.demuserebotsir
.)rotaropave
60demitffOpirD
Ftsorfedretfayaledtratsna
detratssirosserpmocehtnehwmorfespaleotsitahtemitehttesuoyereH ehterehwemitehT(.noitarepoemuseryamnafehtlitnudnatsorfedaretfa
.)rotaropaveehtot”dnuob“siretaw
70d.leDtratSnaF
erutarepmettratsnaF
nafdeyaleD“rednudenoitnemnahtreilraeelttiladetratseboslayamnafehT
uoyereH.eulavelbissimrepasretsigerrosnestsorfedehtfi”tsorfedretfatrats
.tratsyamnafehtnehwrofeulavehttesnac
80d.pmeTtratSnaF
tsorfedgnirudnitucnaF
.tsorfedgnirudetarepootsinafehtrehtehwtesuoyereH
tnavelertonera80ddna70dnisgnitteseht,detcelessinoitcnufNOehtfI
90d.feDgniruDnaF
rosnestsorfeD
ebotsirosnestsorfedehtrehtehwtesuoyereH5S,4Sgniogtonsierehtfiro
.llatarosnestsorfedaebot
S(4S:0
tuo
)
:1S(5S
fed
)
.emitnodesabsipotstsorfeD.rosnestsorfedoN:2
01drosneSpotSfeD
purewoptatsorfeD
sirewopnehwtsorfedahtiwtratsotsirellortnocehtrehtehwtesuoyereH
noitcnufehT.eruliafrewoparetfaropu-tratsgnirudrellortnocehtotdeilppus
rewoptneuqerfhtiwskrowtenkaewnodemrofrepeblliwtsorfedtahtserusne
.seruliaf
31dpUrewoPtA.feD
trats.feD
tsorfedlaunamatratsnacuoyereH
.feDretfAdloH
sirellortnocehtnehwNOswohS
.tsorfeddetanidroochtiwgnitarepo
EKC 414A Manual RS.8C.K3.02 © Danfoss 09-2003 7
lortnocnoitcejnI lortnocnoitcejnI
ecnerefertaehrepusehtrofeulav.xaM
90n
HSxaM
ecnerefertaehrepusehtrofeulav.niM
01nHSniM
erutarepmetPOM
FFO.soptceles,deriuqersinoitcnufPOMonfI
11n.pmetPOM
)FFOotsdnopserroc51foeulavA(
sdnocesnidoirepemits’evlavVKA
noitcusehtdnatnalpdesilartnecedasitifieulavrewolaottesebylnodluohS
.evlavVKAehtfogninepoehthtiwenilnidnatolasetautculferusserp
.ffatsdeniartyllaicepsybdegnahcebylnodluohseulavehT
31ndoirepVKA
lortnocevitpadA
eergedgninepos’evlavehttsujdaflestilliwrellortnocehtlortnocevitpadahtiW taehrepuselbissimrepmuminimehtsahemitehtllarotaropaveehttahtos eblliw71ndna61nnisgnitteseht,FFO.sopnitessinoitcnufehtfI.)SSM(
deniartyllaicepsybedamebylnodluohsgnittesFFOehT.lortnocehtnidesu
ffats
41ntcejni.padA
eergedgninepoegarevA
ehtsesudnaeergedgninepos’evlavehtsretsigerylsuounitnocrellortnocehT
.lortnocehtnieulav
.ffatsdeniartyllaicepsybdegnahcebylnodluohseulavehT
61nmiDVKA
pu-tratsgnirudytefaslangiS
gninepos’evlavehtrofeulavtratssaeulavehtsesunoitcnuflortnocehT
ylsuounitnocrellortnocehtlortnocevitpadayB.nituctatsomrehthcaetaeerged
.eulavwenasetaluclac
.ffatsdeniartyllaicepsybdegnahcebylnodluohseulavehT
71n%DOtratS
taehrepusfonoitalugerrofrotcafytilibatS
ehtfonoitautculfretaergawollalliwnoitcnuflortnocehteulavrehgihahtiW
.degnahcsiecnereferehterofebtaehrepus
.ffatsdeniartyllaicepsybdegnahcebylnodluohseulavehT
81nytilibatS
gnisolcdecroF
.NO.sopnitessinoitcnufehtnehwesolclliwevlavVKAehT
.)desigrene-edsitupni"NOtcejnI"ehtnehwesolcoslalliwtI(
63nesolCtcejnI
8 Manual RS.8C.K3.02 © Danfoss 09-2003 EKC 414A
lortnocnaF lortnocnaF
asadeppotseboslayamsnafehttsorfedgnirudsnoitcnufnafehtotnoitiddanI
itareporosserpmocehtfonoitcnuf.noitcnufroodayrassecenfidnano
tuotucrosserpmocnopotsnaF
sirosserpmocehtnehwdeppotsebtsumnafehtrehtehwtcelesnacuoyereH
.tuotuc
10FocpotsnaF
tuotucsirosserpmocnehwpotsnafdeyaleD
yalednacuoytuotucsirosserpmocehtnehwnafehtpotsotnesohcevahuoyfI
.yaledemitehttesuoyereH.deppotssahrosserpmocehtretfapotsnafeht
20Foc.lednaF
erutarepmetpotsnaF
edivorptonlliwyehttahtos,noitautisrorrenanisnafehtspotsnoitcnufehT
nahterutarepmetrehgihasretsigerrosnestsorfedehtfI.ecnailppaehtotrewop
wolebK2tatrats-ereblliwerehT.deppotseblliwsnafeht,erehtesenoeht
.gnitteseht
-VKAehtfiro,tsorfedaretfapu-trats,tsorfedagnirudevitcatonsinoitcnufehT
.detpurretnisilangisNO
.detpurretnisinoitcnufehtC°05+gnitteshtiW
40F.pmeTpotSnaF
suoenallecsiM suoenallecsiM
pu-tratsretfalangistuptuofoyaleD
tahtosdeyaledebnacsnoitcnufs’rellortnocehteruliafrewoparopu-tratsretfA
ehttesnacuoyereH.dediovasikrowtenylppusyticirtceleehtfognidaolrevo
.yaledemit
10o.ptuOfOyaleD
lortnoctupnilatigiD
gniwollofehtfoenorofdesuebnachcihw”ID“tupnilatigidasahrellortnocehT
:snoitcnuf
)1 DooehtnehwretsigerlliwrellortnocehtdnahctiwsroodatcennoC.mralar
rood”noitcnufehtwollalliwrellortnoceht,yltneuqesbuS.nepositupniID
.”mrala
)2 lliwrellortnocehT.dettifsignirpsmruterhtiwnoitcnuftcatnocA.tsorfeD
tsorfedatratsnehtlliwrellortnocehT.detavitcasitupniIDehtnehwretsiger
tahttnatropmisitisrellortnoclarevesybdeviecerebotsilangisehtfI.elcyc
.)DNGotDNGdnaIDotID(yawemasehtdetnuomerasnoitcennocLLA
eblliwereht,nitucsihctiwsehtnehW.hctiwsatcennoC.noitarepothgiN)3
.noitarepothgin
)4 dna,detiucric-trohssitupniehtnehwtuodeirracsinoitalugeR.hctiwsniaM
.FFO.sopnitupsitupniehtnehwdeppotssinoitaluger
)5 fI(.margaidgniriweeS.snoitcennocelbachtiwtsorfeddetanidrooC
ebtontsum5gnittes,desusinoitacinummocatadaivtsorfeddetanidrooc
.)desu
)0 desutonsitupniIDehtnehw)FFO(0ebdluohsgnitteS
20ogifnoC1iD
sserddA
naevahtsumti,noitacinummocatadhtiwkrowtenaotnitliubsirellortnocehtfI
ehtdna,sserdda wonknehttsumnoitacinummocatadehtfoyawetagretsam
.sserddasiht
saheludomnoitacinummocatadanehwedamebylnonacsgnittesesehT
noitacinummocatadehtfonoitallatsniehtdnarellortnocehtnidetnuomneeb
.detelpmocneebsahelbac
.”C.A8.CR“tnemucodetarapesanidenoitnemsinoitallatsnisihT.
06dna1neewtebtessisserddaehT 30o
NO.sopnitessiunemehtnehwyawetagehtottnessisserddaehT 40o
edocsseccA
nacuoyedocsseccanahtiwdetcetorpeboterarellortnocehtnisgnittesehtfI
noitcnufehtlecnacnacuoy,tonfI.001dna0neewtebeulavlaciremunates
.FFOgnitteshtiw
50o
EKC 414A Manual RS.8C.K3.02 © Danfoss 09-2003 9
epytrosneS S(=)5S,4S,3S(
niS,tuo
S,
fed
)
oslayamuoytuB.desusiycaruccalangistaerghtiwrosnes0001tPayllamroN
noitautislaicepsni)0001=52R(rosnesCTPaesu.
60ogifnoCrosneS
0=tP
1=CTP
ycneuqerF
.ycneuqerftenehtteS
21ozH06/05
)1=06,0=05(
snoitcennoceriwhtiwtsorfeddetanidrooC
.21egapnodebircsedsaedamebtsumrellortnocehtotsnoitcennoC
snoitcennoceriwhtiwtsorfeddetanidroocoN:ffO
1 )retsamebnacpuorgehtnirellortnocenoylno(retsaM:
2 evalS:
.0ebtsumgnitteseht,desutonsi)OD(tuptuofI
lliwsiht,rellortnocniamehtnitesgniebotroirpevalsehtnitessinoitcnufehtfI
ehterofebrellortnocniamehtgnittesybdediovaebnacsihT.tsorfedatrats
.tupniIDehttagnittesehtnodnepedrevewohlliwtI.evals
31ogifnoC1OD
0=desutoN
1=retsaM
2=evalS
sorfeddetanidroocretfaemitybdnats.xaM t
tahtsllethcihwlangisaroftiawlliwtitsorfedadetelpmocsahrellortnocanehW
ronosaerenorofraeppaotsliaflangissihtfI.demuserebyamnoitaregirfereht
emitybdnatssihtnehwnoitaregirferehttratsflestilliwrellortnoceht,rehtona
.despalesah
61oemitdloHxaM
yalpsidehtroflangisrosnestceleS
3Sehtwohsdluohsyalpsidehtrehtehwtesnacuoyeulav%ahtiW
.owtehtfoerutximaroerutarepmet4Seht,erutarepmet
.nwohssierutarepmet3Sehtylno,%0gnitteshtiW
.nwohssierutarepmet4Sehtylno,%001gnitteshtiW
71o%tuoS.psiD
stuptuofolortnoclaunaM
nactuptuolatigidehtdnastuptuoyalerlaudividniehtecivreshtiwnoitcennocnI
.NO.sopotdegnahceb
edirrevooN:ffO
NOsiyalerrosserpmoC:1
NOsiyalertsorfeD:2
NOsiyalernaF:3
FFOsiyalermralA:4
deriuqersitsorfedtahtsrellortnocevalsotlangiS:5
NOsituptuoVKAehT:6
nOsiyalerthgiL:7
.detanimretsilortnocdecrofnehwFFOotnoitcnufehtteserotrebmemeR
81o
egnargnikrows’rettimsnarterusserP
siegnargnikrownevigahtiwrettimsnarterusserpaerusserpehtotgnidroccA
.)rab21ot1–.g.e(rellortnocehtnitesebtsumegnargnikrowsihT.desu
eulav.niM 020sserPsnarTniM
eulav.xaM 12osserPsnarTxaM
sgnittes"NOtcejnI"
tupni"NOtcejnI"ehtnehwevitcaeboterasnoitcnufhcihwenifeduoyereH
:NO.sopnitupsi”63n”nehwroslangiseviecertonseod
.gnirotinommralasierehT.detavitcasiyalernafehT:1
.gnirotinommralasierehT.detavitcatonsiyalernafehT:2
.gnirotinommralaonsierehT.detavitcatonsiyalernafehT:3
.gnirotinommralaonsierehT.detavitcasiyalernafehT:4
lliwssergorpnitsorfedyna(detratsebtonnactsorfedatahtseilppa4dna3roF
.)yawlamronehtnidetanimreteb
.8ro7,6,5otdetcelesebtsumgnittesehtderiwtonsitupni”notcejnI“ehtfI
.).cte,5=1(.4-1rednudenoitnemsasinoitcnufehT
92ogfC.lCtcejnI
gnittestnaregirfeR
esoohcyamuoY.denifedebtsumtnaregirfereht,detratssinoitaregirfererofeB
stnaregirfergniwollofehtneewteb
.32R=8.1b31R=7.31R=6.717R=5.205R=4.a431R=3.22R=2.21R=1
.722R=51.23R=41.denifedresU=31.b241R=21.411R=11.305R=01.005R=9
.A704R=12.C704R=02.A404R=91.A204R=81.705R=71.A104R=61
.a006R=72.006R=62.092R=52.071R=42.A014R=32.B704R=22
A714R=03.0721R=92.447R=82
.rosserpmocehtotegamadesuacyamtnaregirferfonoitcelesgnorW:gninraW
03otnaregirfeR
10 Manual RS.8C.K3.02 © Danfoss 09-2003 EKC 414A
ecivreS ecivreS
noitautisecivresaniesurofdetnirpebnacseulavrellortnocforebmunA
S(5SehttaerutarepmetehtdaeR
fed
)eulavdetarbilac(rosnes)90uC°.pmetfedS
IDtupnifosutatsdaeR 01usutats1ID
detelpmoctsalehtfonoitarudehtrotsorfedgniognoehtfonoitarudehtdaeR
.tsorfed
11u”ehtnidetcipeD(emittsorfeD
)noitartsulli”lortnoctsorfeD
S(3SehttaerutarepmetehtdaeR
ni
)eulavdetarbilac(rosnes)21upmetrianiS
)ffo/no:noitarepothgin(noitarepothgin/-yadehttasutatsdaeR 31u”ehtnidetcipeD(dnoCthgiN
)noitartsulli”lortnoctatsomrehT
tupniNOehttasutatsdaeR 41uNOtcejnI
tuptuoODehttasutatsdaeR 51usutats1OD
S(4SehttaerutarepmetehtdaeR
tuo
)eulavdetarbilac(rosnes)61u.pmeTriAtuoS
etalugernoitcnuftatsomrehtehthcihwotgnidroccaerutarepmetehtdaeR 71uria.rehT
tsalehtfonoitarudehtrotatsomrehtehtrofemitnitucgniognoehtdaeR
nitucdetelpmoc
81u”ehtnidetcipeD(emitnur.rehT
)noitartsulli”lortnoctatsomrehT
rosnes2SehttaerutarepmetehtdaeR 02u.pmet2S
taehrepusdaeR 12unoitcejnI”ehtnidetcipeD(HS
)noitartsulli”lortnoc
ecnerefertaehrepuslautcas’lortnocehtdaeR 22unoitcejnI”ehtnidetcipeD(.ferHS
)noitartsulli”lortnoc
eergedgninepolautcas’evlavehtdaeR 32u%DOVKA
rabnierusserpgnitaropaveehtdaeR 52u0P.serp.pavE
seergednierusserpgnitaropaveehtdaeR 62u0T.pmet.pavE
yalerrosserpmoC
.sutatsyalerehtdaernacuoyereH
yalertsorfeD
.sutatsyalerehtdaernacuoyereH
yalernaF
.sutatsyalerehtdaernacuoyereH
yalermralA
.sutatsyalerehtdaernacuoyereH
yalerthgiL
.sutatsyalerehtdaernacuoyereH
gnittesyrotcaF
ekiltiod,seulavtes-yrotcafehtteserdnarellortnocehttesorezotdeenuoyfI
emasehttanidehsupsnottubhtobpeekegatlovylppusehtffohctiws:siht
.egatlovylppusehttcennoceruoysaemit
lortnoclaunaM
ehtnopuerehwFFO.sopniteS
-ecrofebnactuptuoderiuqer ehtteserotrebmemeR.dellortnoc
.FFOotnoitcnuf
tes%DOVKA
tesmralA
tes.pmoC
testsorfeD
tesnaF
testhgiL tes1OD
egassemtluaF txetmralA
ehtnos’DELehtnoitautisrorrenanI61AKEeblliwyalerehtdnahsalflliw2
mralaehteesnacuoynoitautissihtninottubpotehthsupuoyfI.detavitca
.yalpsidehtnitroper
gnirudgnirruccomralanaebrehtienacti-stroperrorrefosdnikowteraerehT
.noitallatsniehtnitcefedaebyamerehtro,noitarepoyliadeht
.deripxesahyaledemittesehtlitnuelbisivemocebtonlliwsmrala-A
.sruccororreehttnemomehtelbisivemoceblliw,dnahrehtoehtno,smrala-E
.)mralaEevitcanasierehtsagnolsaelbisivebtonlliwmralaAnA(
laudividniehtfoecnatropmiehT
ahtiwdenifedebnacsmrala
unemehtni)3ro2,1,0(gnittes
.snoitanitsedmralA MKAeeS
.erutaretil
Hhgimralaerutarepmet 1Aria.pmeThgiH
mralaerutarepmetwoL 2Aria.pmetwoL
EKC 414A Manual RS.8C.K3.02 © Danfoss 09-2003 11
mralarooD 4AmralarooD
tsorfeddetanidroocagniruddetavitcasinoitcnuf”61o”ehT 5AemiTdloHxaM
melborplortnoC 01A.borp.tcejnI
detcelestnaregirferoN 11A.les.gfRoN
erutarepmetno,detnawsa,fodaetsniemitnodesabdeppotstsorfeD -emiT.feDxaM
rellortnocnitluaF 1Etluaf.rtnoC
etcennocsidrosnestsorfeDd 4ErorrefedS
detiucric-trohSosnestsorfedr 5ErorrefedS
kcolckcehcdnayrettabegnahC 6E-
detcennocsidrosnes)tuoS(4S 7ErorretuoS
rosnes)tuoS(4Sdetiucric-trohS 8ErorretuoS
detcennocsidrosnes)niS(3S 9ErorreniS
rosnes)niS(3Sdetiucric-trohS 01ErorreniS
detcennocsidrosnes2S 51Erorre2S
rosnes2Sdetiucric-trohS 61Erorre2S
rorrerettimsnarterusserP 02Erorre.pni0P
sutatsgnitarepO
( )tnemerusaeM
gnitiawtsujsitierehwsnoitautisgnitalugeremoshguorhtseogrellortnocehT
”gnineppahgnihtonsiyhw“esehtekamoT.noitalugerehtfotnioptxenehtrof
gnitarepoehT(.yalpsidehtnosutatsgnitareponaeesnacuoy,elbisivsnoitautis
.)mralaEroAevitcanasierehtfi,revewoh,neesebtonnacsutats
:gniwollofehtsnaemrebmunsutatsehT
etatsCKE
daerebnacsutatsgnitarepoehT(
fineve,emmargorpMKAehtni
.)mralaEroAevitcanasiereht
tsorfeddetanidroocehtfodnerofgnitiaW 1S1
.setunimxtsaeltarofnurtsumtignitareposirosserpmocehtnehW 2S2
.setunimxtsaeltarofdeppotsniamertsumti,deppotssirosserpmocehtnehW 3S3
tuonurotemitehtrofstiawdnaffospirdrotaropaveehT 4S4
pots/tratslanretxerolanretniehtybdeppotsnoitaregirfeR 01S01
tuo-tucsitatsomrehT 11S11
ssergorpnitsorfeD.ecneuqestsorfeD 41S41
tuonurotemitehtrofstiawnafehT.ecneuqestsorfeD 51S51
noitalugerdeppotsrotupniNOnepooteuddeppotsnoitaregirfeR 61S61
nepositupniID.neposirooD 71S71
detpurretnisinoitaregirfeR.ssergorpninoitcnuftleM 81S81
lortnoctatsomrehtgnitaludoM 91S91
rorrerosnesoteudgniloocycnegremE 02S02
degrahcgniebrotaropavE.2esahppu-tratS 22S22
lortnocevitpadA 32S32
dellortnocsisrosnesmorfytilibailerlangiS.1esahppu-tratS 42S42
stuptuofolortnoclaunaM 52S52
detcelestnaregirferoN 62S62
pu-tratsgnirudstuptuonoyaleD non0
12 Manual RS.8C.K3.02 © Danfoss 09-2003 EKC 414A
Connection
Cable length between an external display and EKC 414A must be max. 15 m
Coordinated defrost via cable connections
Coordinated defrost via data communication
12 4 12 412 4
AKS 32R: 1= Black 2= Blue 3= Brown
EKC 414A Manual RS.8C.K3.02 © Danfoss 09-2003 13
Necessary connections
11 - 12 Pt 1000 ohm sensor. Refrigeration outlet (S2) 13 - 14 Air temperature sensor before evaporator (S3) 15 - 16 Air temperature sensor after evaporator (S4)
It is application determined whether S3 or S4 or both has to be mounted.
S3, S4 and S5 may either be Pt 1000 ohm or Ptc 1000 ohm, but they must all be of the same type.
20 - 22 Signal from pressure transmitter type AKS 32R 23 - 24 Supply voltage 230 V 50/60 Hz 25, 26 Protective earth connection 27 - 28 Expansion valve type AKV (230 V d.c.) 40 - 41 230 V signal for start/stop of regulation
(the connection can be left out with setting in o29).
Application dependent connections
1 - 2 Output signal on terminal 2, if there is coordinated
defrost with cable connections
3 - 4 Input signal from a contact function or signal on
terminal 4, if there is coordinated defrost with cable connections
5 - 7 Possibility of connecting an external display type EKA
161
8 - 10 Possibility of connecting an external display with
operating knobs type EKA 162
17 -18 Defrost sensor on the evaporator (S5). (The sensor
can either be Pt 1000 ohm or Ptc 1000 ohm)
29 - 31 Alarm relay
There is connection between 29 and 31 in alarm
situations and when the controller is de-energised 32 - 33 Compressor relay 34 - 35 Defrost relay 36 - 37 Fan relay 38 - 39 Light relay
There is connection between 38 and 39
when control performed during day operation 43 - 44 Data communication
It is
important that the installation of the data commu­nication cable be done correctly. Cf. separate literature No. RC.8A.C... Gateway AKA 243B must be version 5.3x or newer version. The wire switch to the left of terminal 43 will termi­nate with 120 ohm in closed position.
Installation considerations
Accidental damage, poor installation, or site conditions, can give rise to malfunctions of the control system, and ultimately lead to a plant breakdown.
Every possible safeguard is incorporated into our products to prevent this. However, a wrong installation, for example, could still present problems. Electronic controls are no substitute for normal, good engineering practice.
Danfoss wil not be responsible for any goods, or plant components, damaged as a result of the above defects. It is the installer's responsibility to check the installation thor­oughly, and to fit the necessary safety devices.
Special reference is made to the necessity of signals to the controller when the compressor is stopped and to the need of liquid receivers before the compressors.
Your local Danfoss agent will be pleased to assist with further advice, etc.
Plug
The controller comes factory-mounted with one part of a plug connection. The other part is of the type Phoenix and AMP with the following type designations: ConnectionType 1-2: MC1,5/2-ST-3,81 3-4: "" Display: AMP ital mod 2, housing 280 359,
crimp contact 280 708-2 Display: "" S2: AMP ital mod 2, housing 280 358,
crimp contact 280 708-2 S3: "" S4: "" S5: "" 20-22: MC1,5/3-ST-3,81 23-25: MSTBT2,5/3-ST-5,08 26-28: "" 29-31: "" 32-33: MSTBT2,5/2-ST-5,08 34-35: "" 36-37: "" 38-39: "" 40-41: MC1,5/2-ST1-5,08 43-44: MC1,5/2-ST-3,81
The screw terminals (Phoenix plug) are not bypacked for some of the code numbers. Sensors and display supplied with plug.
14 Manual RS.8C.K3.02 © Danfoss 09-2003 EKC 414A
Operation of the controller can take place via data communication or from a separate display. Operation via data communication may be performed via the AKM programme and a text that can be seen in the earlier section ”Survey of functions”. Operation from EKA 162 is described below:
EKA 162
Operation
The buttons (EKA 162 only)
When you want to change a setting, the two buttons will give you a higher or lower value depending on the button you are pushing. But before you change the value, you must have access to the menu. You obtain this by pushing the upper button for a couple of seconds ­you will then enter the column with parameter codes. Find the parameter code you want to change and push the two buttons simultaneously. When you have changed the value, save the new value by once more pushing the two buttons simultaneously. Or briefly:
Gives access to the menu (or cutout an alarm)
Gives access to changes
Saves a change
Or examples put in another way:
Set the temperature
1. Push the two buttons simultaneously
2. Push one of the buttons and select the new value
3. Push both buttons again to conclude the setting
Set a menu
1. Push the upper button until a parameter is shown
2. Push one of the buttons and find the
parameter you want to change
3. Push both buttons simultaneously
until the parameter value is shown
4. Push one of the buttons and select the new value
5. Push both buttons again to conclude the setting
Examples of displays:
-d- Display going on
180 Sensor has not been mounted
Temperature setting
When it is the temperature setting you wish to change, do not enter the menu. Push both buttons simultaneously and you will be allowed to change the temperature reference when the display answers back by flashing.
Forced control
In addition to the normal way of operat­ing the controller you are now able to perform a number of forced control functions which you start, as follows:
- Cut out alarm relay / check alarm code
• Push the upper button
- Read the defrost stop temperature
• Push the lower button
- Manual start or stop of defrost
• Push the lower button for four seconds
EKA 161
Display with operating buttons and LED indication of relay functions:
Refrigeration
AKV valve
Defrost
Fan
Display for mounting on refrigeration appliance.
The showing in the display follows the showing in EKA 162
Examples of operations
Operating the two pushbuttons
Display
readout
What the controller does automatically
Resulting controller
setup
Normal
operation
Room
temp. 2
Normal operation (or alarm)
Known
codes
and settings
All parameter
settings
= factory
settings
Normal operation
Normal operation
Normal operation
Alarm relay
not
activated
Alarm
Room temp.
Room temp.
Set
value
Change
ChangeChange
Set
value
Room temp.
Room temp.
Power off
Power
on
Room temp.
Room
temp.
Room
temp.
Room
temp.
Room
temp.
Alarm code/
Fault code
Alarm code/
Fault code
Room temp.
Room temp.
Defrost operation
Defrost stop temp.
What to do
Initial
controller
setup
Read
or
change
room temp.
setting
Read or change parameter
codes
and
settings
Re-establish
all factory
settings
Read
defrost
stop
temp.
Manually
start of
a defrost
operation
Manually
stop of
a defrost
operation
Reset
alarm
relay
Read codes
cause of
alarm mode
Normal
operation
Room
temp. 1
Normal operation (or alarm)
Unknown
codes
and settings
Unknown
settings
Normal operation
or alarm
Normal operation
Defrost
operation
Alarm
relay
activated
Alarm relay
not
activated
Room temp.
Room temp.
Code
Room temp.
Room temp.
Room
temp.
Room temp.
Room temp.
Room temp.
EKC 414A Manual RS.8C.K3.02 © Danfoss 09-2003 15
noitcnuF-araP
retem
.niM.xaM
yalpsidlamroN
rosnesdetcelesehttaerutarepmetehtswohS
71OniweivenifeD
-C°
,erutarepmetpotstsorfeddetceleseesothsiwuoyfI
).ces1(hsupfeirbanottubrewolehtevig
detcelestonerutarepmetnopots=on
-C°
tatsomrehT
laitnereffiD10rK1.0K0.01
erutarepmetgnittess’tatsomrehtfonoitatimil.xaM20rC°94-C°05
erutarepmetgnittess’tatsomrehtfonoitatimil.niM30rC°05-C°94
)F°/C°(tinuerutarepmeT50rC°F°
S(4SmorflangisfonoitcerroC
tuo
)90rK0.01-K0.01
S(3SmorflangisfonoitcerroC
ni
)01rK0.01-K0.01
noitaregirferfopotS/tratS21rFFONO
noitarepothgingnirudtnemecalpsidecnerefeR31rK0.02-K0.02
noitcnuftatsomrehtenifeD
gnitaludoM=2,FFO/NO=1
41r1 2
tatsomrehtfo,elbacilppafi,gnithgiewdnanoitinifeD
srosnes
S(4S=%001
tuo
S(3S=%0,)
ni
.)
71UnineesebnacerutarepmettatsomrehtehT
51r%0%001
sdoireptlemneewtebemiT61rh0h01
sdoireptlemfonoitaruD71r.nim0.nim01
mralA
yaledemitmralA30A.nim0nim021
yaledemitmralarooD40A.nim0.nim09
gniloocgnirudyaledemiT21A.nim0nim042
timilmralahgiH31AC°05-C°05
timilmralawoL41AC°05-C°05
rosserpmoC
emit-NO.niM10cnim0nim05
emit-FFO.niM20cnim0nim05
tsorfeD
erutarepmetpotstsorfeD20d0 C°52
stratstsorfedneewteblavretnI30dFFOh84
noitarudtsorfed.xaM40d0 nim081
pu-tratsgnirudsni-tuctsorfedfotnemecalpsidemiT50d0 nim042
emitffo-pirD60d0 nim06
tsorfedretfayaledtratsnaF70d0 nim06
erutarepmettratsnaF80d51-C°0
)on/sey(tsorfedgnirudni-tucnaF90donsey
rosnestsorfeD
S(4S=0
tuo
S(5S=1,)
fed
emitnopotS.non=2,)
01d0 2
purewoptatsorfeD31donsey
)dellatsnifi(eludomCTR
snoitcurtsniCTRees
10t 61t
noitcnuflortnocnoitcejnI
ecnerefertaehrepusfoeulav.xaM90nK0.3K0.51
ecnerefertaehrepusfoeulav.niM01nK0.3K0.01
erutarepmetPOM11nC°0.05-ffo/C°51
doirepemits’evlavVKA
ffatsdeniartybFFOotdegnahcebylnodluohS
31n.ces3.ces6
lortnocevitpadA
ffatsdeniartybFFOotdegnahcebylnodluohS
41nFFONO
.noisnemidVKA–eergedgninepoegarevA
ffatsdeniartybdegnahcebylnodluohS
61n%01%57
s’eergedgninepO–pu-tratsgnirudytilibailerlangiS
.ffatsdeniartybdegnahcebylnodluohS.eulavtrats
71n%5%07
.lortnoctaehrepusrofrotcafytilibatS
ffatsdeniartybedamebylnodluohssegnahC
81n0 01
NO.sopnituhsevlavVKA..gnisolcdecroF63nFFONO
naF
tuotucrosserpmocnopotsnaF10Fonsey
tuotucsirosserpmocnehwpotsnafdeyaleD20Fnim0nim03
erutarepmet5SehtfispotsnafehT.noitcnufytefaS
eulavsihtsehcaer
40F0.05-ffo/0.05
suoenallecsiM
pu-tratsretfalangistuptuofoyaleD10o.ces0ces006
:ID(langistupnilatigidenifeD
,tratstsorfed=2,mralarooD=1,desuton=FFO
=5,pots/tratslanretxE=4,noitarepothgiN=3
snoitcennocelbachtiwtsorfeddetanidrooC
20oFFO5
)06-0=egnar(sserddakrowteN30o0 099
)egassemnip-ecivres(hctiwsFFO/NO40oFFONO
edocsseccA50oFFO001
)CTP/tP(5Sdna4S,3SrofepytrosnesdesU60otPctP
ycneuqerfegatlovylppusteS21ozH05zH06
:OD(langistuptuotlatigidenifeD
desuton=0
:snoitcennocelbachtiwtsorfeddetanidrooC
evalS=2,retsaM=1
31o0 2
tsorfeddetanidroocretfaemitybdnats.xaM61onim1nim03
S(%4SyalpsiD
tuo
)
S(3S=%0
ni
) S(4S=%001
tuo
)
71o%0%001
:stuptuofolortnoclaunaM
edirrevooN=FFO
NOsiyaerrosserpmoC:1
NOsiyalertsorfeD:2
NOsiyalernaF:3
FFOsiyalermralA:4
NOsituptuoOD:5
NOsituptuoVKA:6
NOsiyalerthgiL:7
tsumgnitteseht,detanimretsilortnoclaunamnehW
FFOotdegnahceb
81oFFO7
eulav.nim–egnargnikrowrettimsnarterusserP020rab1-rab5
eulav.xam–egnargnikrowrettimsnarterusserP120rab6rab63
noitinifedNO-tcejnI
sinoitaregirfertuotucsitupniNOehtnehW
.deppots
mralaehtdnayalernafehtwohenifeduoyereH
:tcaoteranoitcnuf
evitcagnirotinommrala,NO=yalernaF=1
evitcagnirotinommrala,FFO=yalernaF=2
gnirotinommralaon,FFO=yalernaF=3
gnirotinommralaon,NO=yalernaF=4
5 1sa=8 lanimretotnoitcennoctuohtiwtub,4
.14-04
92o1 8
gnittestnaregirfeR
.717R=5.205R=4.a431R=3.22R=2.21R=1
.305R=01.005R=9.32R=8.1b31R=7.31R=6
.23R=41.denifedresU=31.b241R=21.411R=11
.A204R=81.705R=71.A104R=61.722R=51
.B704R=22.A704R=12.C704R=02.A404R=91
.006R=62.092R=52.071R=42.A014R=32
A714R=03.0721R=92.447R=82.a006R=72
03o0 03
SW: 1.7x
Menu survey
16 Manual RS.8C.K3.02 © Danfoss 09-2003 EKC 414A
egapsuoiverpmorfdeunitnoC-araP
retem
ecivreS
retemarapgnignolebehtaivdemrofrepebnacstuodaergniwollofehT
S5SrosnestsorfeD
fed
90uC°
tupni-IDnosutatS01u
emittsorfeD11u.nim
S(3SerutarepmetriA
ni
)21uC°
)fforono(noitarepothginnosutatS31u
tupni-NOnosutatS41u
tuptuo-ODnosutatS51u
S(4SerutarepmetriA
tuo
)61uC°
erutarepmettatsomrehT71uC°
emitni-tuctatsomrehT81u.nim
2StaerutarepmeT02uC°
taehrepuS12uK
ecnerefertaehrepuS22uK
eergedgninepolautcas’evlavVKA32u%
erusserpgnitaropavE52urab
erutarepmetgnitaropavE62uC°
:segassemgniwollofehtevignacrellortnocehT
1E
gassemrorrEe
rellortnocnitluaF
4EdetcennocsidrosnestsorfeD
5ErosnestsorfeddetiucrictrohS
6EkcolckcehcdnayrettabegnahC
7ES(4S
tuo
detcennocsidrosnes)
8ES(4SdetiucrictrohS
tuo
)
9ES(3S
ni
detcennocsidrosnes)
01ES(3SdetiucrictrohS
ni
rosnes)
51Edetcennocsidrosnes2S
61Erosnes2SdetiucrictrohS
02EtluafR23SKA
1A
egassemmralA
mralaerutarepmethgiH
2AmralaerutarepmetwoL
4AmralarooD
5A
agniruddetavitca”61O”noitcnuF
tsorfeddetanidrooc
01AmelborplortnoC
11AdetcelestnaregirferoN
1S
egassemsutatS
tsorfeddetanidroocehtfodnerofgnitiaW
2SemitNOrosserpmocfodnerofgnitiaW
3SemitFFOrosserpmocfodnerofgnitiaW
4S
dnaffospirdrotaropavE.ecneuqestsorfeD
eripxeotemitehtrofstiaw
01S
rolanretniehtybdeppotsnoitaregirfeR
noitcnufpots/tratslanretxe
11StuotuctatsomrehT
41SssergorpnitsorfeD.ecneuqestsorfeD
51S
otemitrofgnitiawnaF.ecneuqestsorfeD
espale
61S tupniNOnepooteuddeppotsnoitaregirfeR
71SneposiIDtupnI.neposirooD
81S
noitaregirfer(ssergorpninoitcnuftleM
)detpurretni
91SlortnoctatsomrehtgnitaludoM
02S rorrerosnesoteudnoitaregirferycnegremE
22SdegrahcsirotaropavE.2esahppu-tratS
32SlortnocevitpadA
42S
ehtmorfytilibailerlangiS.1esahppu-tratS
dekcehcsisrosnes
52SstuptuofolortnoclaunaM
62SdetcelestnaregirferoN
nonpu-tratsgnirudstuptuonoyaledemiT
Factory setting If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep both buttons depressed at the same time as you reconnect the supply voltage
EKC 414A Manual RS.8C.K3.02 © Danfoss 09-2003 17
Data
ylppuS
egatlov
AV5,zH06/05,%51-/01+V032
srosneS
serutarepmettnaregirferrofmho0001tP
riarof)mho0001=52R(CTPromho0001tP
serutarepmet
rellortnoC
rosnes
metsys
egnargnirusaeMC°05+ot06-
ycaruccA
C°5.0±
=erutarepmetrosnesrof
C°05+ot53-
/yalpsiD
noitarepo
snottubgnitareporoyalpsidonsahrellortnocehT
.lenaptnorfno
detcennoc,etarapesaaivecalpsekatnoitarepO
noitacinummocatadaivroyalpsid
%1.0htiwsyalpsidowttcennocotelbissopsitI
:egnargnirusaemehtniycaruccagnidaer
stigideerht,DEL,161AKE
snottubgnitarepoowt,stigideerht,DEL,261AKE
latigid1
tupni
desuebnacri,detcennocsinoitcnuftcatnocafI
ronoitarepothgin,tratstsorfed,mralaroodrof
noitalugerehtfopots/trats
detanidrooc,detcennocerastinu414CKErehtofI
snoitcennocelbacaivdemrofrepebnactsorfed
latigid1
tuptuo
rofdesuebtupnilatigidehthtiwnoitcnujnocniyaM
snoitcennocelbacaivtsorfeddetanidrooc
tupniV032
eht,yalerrosserpmocehT.deppotsnoitaluger:V0
erayalerthgilehtdnayalernafeht,yalertsorfed
.tuotuc
noitaluger:.c.aV032
.)tuodetpoebnacnoitcnufehT(
rosneS
noitcennoc
gulpPMAhtiwsrosneS
VKA
noitcennoc
1.xaM
syaleR
yalerrosserpmoC
I,ONTSPS
.xam
/cimhoA6=
evitcudni*51CAA3
yalertsorfeD
I,ONTSPS
.xam
/cimhoA6=
evitcudni*51CAA3
yalerrotomnaF
I,ONTSPS
.xam
/cimhoA6=
evitcudni*51CAA3
yalerthgiL
I,ONTSPS
.xam
/cimhoA6=
evitcudni*51CAA3
yalermralA
I,TDPS
.xam
A3/cimhoA6=
evitcudni*51CA
-emnorivnE
stn
snoitarepogniruD,C°55+ot0
tropsnartgniruD,C°07+ot04-
desnednocton,hR%08-02
snoitarbiv/ecneulfnikcohsoN
gnitnuoMllawnoroliarNIDnO
ytisneD02PI
thgieWgk4.0
slavorppA
ersdnamedCMEdnaevitceriDegatloVwoLUE
.htiwdeilpmocgnikram-EC
9-2-03706NEdna1-03706NEot.ccadetset-DVL
2-28005NEdna1-18005NEot.ccadetset-CME
Ordering
noitpircseDepyT
.onedoC
htiwrellortnoclortnocnoitaregirfeR
ataddnasnoitcennocgulp
noitacinummoc
A414CKE
2008B480
tinuyalpsiD161AKE
9107B480
snottubgnitarepohtiwtinuyalpsiD261AKE
9307B480
,gulphtiwm2(tinuyalpsidrofelbaC
)scp42
9717B480
,gulphtiwm6(tinuyalpsidrofelbaC
)scp42
7907B480
kcolcemitlaeR271AKE
9607B480
noitpircseDepyTeesesaelP
lacinhcet/eugolatac
eruhcorb
0001tProsneserutarepmeT
gulpPMAhtiw
11SKA
G.Y0.KR
0001ctProsneserutarepmeT
gulpPMAhtiw
111SKE
rettimsnarterusserPR23SKA
evlavnoisnapxEVKAB.A8.DR/G.Y0.KR
Montage
Display type EKA 161 / 162
EKC 414A
IP 20
* AC 15 load acc. to EN 60947-5-1
References
When the unit is mounted on a wall, the two points on the DIN fastening are cut off.
Only for front mounting (IP 40) Only connection via plugs
18 Manual RS.8C.K3.02 © Danfoss 09-2003 EKC 414A
Data communication
Example
This page contains a description of a few of the possibilities you will have with data communication.
It is important that the installation of the data communication cable is carried out correctly. Please refer to separate literature No. RC.8A.C
The controller has been prepared for data commu­nication.
The data communication takes place via a two-core twisted cable.
Up to 60 controllers may be connected to one cable.
This cable is also connected to a gateway type AKA 243B.
This gateway will now control the communication to and from the controllers.
It will collect temperature values and it will receive alarms. When there is an alarm the alarm relay will be activated for two minutes.
The gateway can now be connected to a modem.
When an alarm occurs from one of the controllers, the gateway will - via the modem
- make a phone call to the service company.
At the service company a modem, gateway and PC with system software type AKM have been installed.
All the controllers’ functions can now be operated from the various menu displays.
The programme will for example upload all the collected temperature values once a day.
Example of menu display
• Measurements are shown
at one side and settings at the other.
• You will also be able to see
the parameter names of the functions on page 4-11.
• With a simple change-over the values can also be shown in a trend diagram.
• If you wish to check earlier temperature measure­ments, you can see them in the log collection.
Alarms
If the controller is extended with data communication, it will be possible to define the importance of the transmit­ted alarms. The importance is defined with the setting: 1, 2, 3 or 0. When the alarm then arises at some time, it will result in one of the following activi­ties:
1 = Alarm The alarm message is sent off with alarm status 1. This means that the gateway with address 125 in the system will have its alarm relay output activated for two minutes. Later, when the alarm ceases, the alarm text will be retransmitted, but now with status value 0.
2 = Message The alarm text is transmitted with status value 2. Later, when the “message” lapses, the alarm text is retransmitted, but now with status value 0.
3 = Alarm As “1”, but the master gateway’s relay output is not activated.
0 = Suppressed information The alarm text is stopped at the controller. It is transmit­ted nowhere.
EKC 414A Manual RS.8C.K3.02 © Danfoss 09-2003 19
20 Manual RS.8C.K3.02 © Danfoss 09-2003 EKC 414A
List of literature
Instructions RI.8G.R
Here you can see how controllers are mounted and programmed.
Installation guide for extended operation RC.8A.C
Here you can see how a data communication connection to ADAP-KOOL® can be established. Refrigeration controls with EKC LonWorks®.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.