User Guide
Interface
EKC 366
The controller is used for regulating a valve in
a refrigerating system - for example in
connection with:
• Long-term storage of fruits and vegetables
• Refrigerating plant
• Brewery systems
• Processing plant
Application Here the controller has been specially
designed for the following functions:
Maintenance of a constant
evaporating pressure
A temperature sensor in the valve’s actuator will
regulate its temperature. This temperature is
an indication of the pressure in the valve, and
the interface module will keep this temperature
constant.
The media temperature is regulated
by a PLC or similar device
Here the interface module receives a variable
signal from the PLC and will subsequently
regulate the valve, so that the refrigeration will
be as accurate as possible.
PLC
© Danfoss | DCS (ADAP-KOOL®) |2015-11
DKRCI.PS.RP0.C1.02 | 1
User Guide | Interface, EKC 366
System
The controller must always be used in conjunction with a pilot
valve of the types shown here.
The most commonly used one is pilot valve CVQ in conjunction
with main valve PM3 (sketched out above).
Valve types:
- CVQ + PM
- KVQ
- TQ
- PHTQ
- TEAQ
- CVMQ
Function
The valve constantly receives feedback of the pressure in the
evaporator. Whatever the variations in the suction pressure from
the compressor, this feedback will produce the result that the
evaporating pressure is kept constant.
In conjunction with the controller, an electronic constant-pressure
valve is thus obtained.
Inserted between the controller and the actuator is a so-called
inner regulating loop. This loop will - via an NTC resistance - constantly control the temperature in the actuator.
In an application where a PLC or similar device is used for regulating a media temperature, the regulating system will in this way be
supplied with an outer regulating loop - which will result in great
regulating accuracy.
"Q valve"
PLC
© Danfoss | DCS (ADAP-KOOL®) | 2015-11
DKRCI.PS.RP0.C1.02 | 2
User Guide | Interface, EKC 366
Survey of functions
Function Para-
meter
Temperature regulation Actuator temperature
Display of valve temperature
The display constantly shows the valve's temperature.
The display is ltered over a period of approx. 10 seconds
Valve’s basic temperature reference
This temperature setting is the valve’s basic setting. At this value no signal must be
received from an external regulation.
The setting value is taken from one of the curves shown and may be ne-adjusted later when the valve has reached the temperature (read the manometer in the system).
(Push both buttons simultaneously to set the menu)
Temperature unit
Set here whether the controller is to show the temperature values in °C or in °F. If indication in °F is selected, other temperature settings will also change over to Fahrenheit, either as absolute values or as delta values.
Input signal’s temperature inuence
This setting determines how much the input signal has to raise the temperature in
the valve. You should aim at selecting the value, so that the valve can close at the
highest occurring evaporating pressure when the input signal is maximum (value to
be set in Kelvin)
Reference
The valve’s temperature is regulated on the basis of the basic setting plus the signal
from the external regulation. (Reference = SP Temp + percentage of "r06".)
The reference can be seen when you push the lower of the two buttons
Sundry congurations Miscellaneous
Parameter by operation via data
communication
- Actuator temp.
- SP Temp.
r05 Temp. unit (°C=0, °F=1)
(In AKM only °C is displayed, whatever
the setting).
r06 Ext.Ref.oset K
- Actuator Ref.
External signal
Here you set the signal that is to be connected to the controller.
0: no signal
1: 4-20 mA
2: 0-20 mA
3: 0-10 V
4: 2-10 V
Frequency
Set network frequency
Data communication
If the controller is built into a network with data communication, it must have an
address, and the master gateway of the data communication must then know this
address.
These settings can only be made when a data communication module has been
mounted in the controller and the installation of the data communication cable has
been completed.
This installation is mentioned in a separate document “RC.8A.C”.
The address is set between 1 and 60 o03
The address is sent to the gateway when the menu is set in pos. ON o04
Language
This setting is only required when data communication is connected to the controller.
Settings: 0=English, 1=German, 2=French, 3=Danish, 4=Spanish, and 6= Swedish
When the controller is operated via data communication, the texts in the right-hand
column will be shown in the selected language.
When you change the setting to an other language you must activate o04 before "the
new language" can be visible from the AKM program.
Service
o10 AI Type
o12 50 / 60 Hz
o11 Language
(50=0, 60=1)
Following installation of a data communication module, the controller can
be operated on a par with the other
controllers in ADAP-KOOL® refrigeration controls.
The signal will be constantly updated. If you wish to follow the signal beyond the
20 seconds, the time-out period, push one of the two buttons before the time-out
period expires
External current signal
Here you can read the value of the current signal received by the controller at its input
External voltage signal
Here you can read the value of the voltage signal received by the controller at its
input
© Danfoss | DCS (ADAP-KOOL®) | 2015-11
u06 AI mA
u07 AI Volt
DKRCI.PS.RP0.C1.02 | 3