Danfoss EKC 366 User guide

User Guide
Interface
EKC 366
The controller is used for regulating a valve in a refrigerating system - for example in connection with:
• Long-term storage of fruits and vegetables
• Refrigerating plant
• Brewery systems
• Processing plant
Application Here the controller has been specially
designed for the following functions:
Maintenance of a constant evaporating pressure
A temperature sensor in the valve’s actuator will regulate its temperature. This temperature is an indication of the pressure in the valve, and the interface module will keep this temperature constant.
The media temperature is regulated by a PLC or similar device
Here the interface module receives a variable signal from the PLC and will subsequently regulate the valve, so that the refrigeration will be as accurate as possible.
PLC
© Danfoss | DCS (ADAP-KOOL®) |2015-11
DKRCI.PS.RP0.C1.02 | 1
User Guide | Interface, EKC 366
System
The controller must always be used in conjunction with a pilot valve of the types shown here. The most commonly used one is pilot valve CVQ in conjunction with main valve PM3 (sketched out above).
Valve types:
- CVQ + PM
- KVQ
- TQ
- PHTQ
- TEAQ
- CVMQ
Function
The valve constantly receives feedback of the pressure in the evaporator. Whatever the variations in the suction pressure from the compressor, this feedback will produce the result that the evaporating pressure is kept constant.
In conjunction with the controller, an electronic constant-pressure valve is thus obtained.
Inserted between the controller and the actuator is a so-called inner regulating loop. This loop will - via an NTC resistance - con­stantly control the temperature in the actuator.
In an application where a PLC or similar device is used for regulat­ing a media temperature, the regulating system will in this way be supplied with an outer regulating loop - which will result in great regulating accuracy.
"Q valve"
PLC
© Danfoss | DCS (ADAP-KOOL®) | 2015-11
DKRCI.PS.RP0.C1.02 | 2
User Guide | Interface, EKC 366
Survey of functions
Function Para-
meter
Temperature regulation Actuator temperature
Display of valve temperature
The display constantly shows the valve's temperature. The display is ltered over a period of approx. 10 seconds
Valve’s basic temperature reference
This temperature setting is the valve’s basic setting. At this value no signal must be received from an external regulation. The setting value is taken from one of the curves shown and may be ne-adjusted lat­er when the valve has reached the temperature (read the manometer in the system). (Push both buttons simultaneously to set the menu)
Temperature unit Set here whether the controller is to show the temperature values in °C or in °F. If in­dication in °F is selected, other temperature settings will also change over to Fahren­heit, either as absolute values or as delta values.
Input signal’s temperature inuence
This setting determines how much the input signal has to raise the temperature in the valve. You should aim at selecting the value, so that the valve can close at the highest occurring evaporating pressure when the input signal is maximum (value to be set in Kelvin)
Reference The valve’s temperature is regulated on the basis of the basic setting plus the signal from the external regulation. (Reference = SP Temp + percentage of "r06".) The reference can be seen when you push the lower of the two buttons
Sundry congurations Miscellaneous
Parameter by operation via data communication
- Actuator temp.
- SP Temp.
r05 Temp. unit (°C=0, °F=1)
(In AKM only °C is displayed, whatever the setting).
r06 Ext.Ref.oset K
- Actuator Ref.
External signal
Here you set the signal that is to be connected to the controller. 0: no signal 1: 4-20 mA 2: 0-20 mA 3: 0-10 V 4: 2-10 V
Frequency
Set network frequency
Data communication
If the controller is built into a network with data communication, it must have an address, and the master gateway of the data communication must then know this address. These settings can only be made when a data communication module has been mounted in the controller and the installation of the data communication cable has been completed. This installation is mentioned in a separate document “RC.8A.C”.
The address is set between 1 and 60 o03
The address is sent to the gateway when the menu is set in pos. ON o04
Language
This setting is only required when data communication is connected to the controller. Settings: 0=English, 1=German, 2=French, 3=Danish, 4=Spanish, and 6= Swedish When the controller is operated via data communication, the texts in the right-hand column will be shown in the selected language. When you change the setting to an other language you must activate o04 before "the new language" can be visible from the AKM program.
Service
o10 AI Type
o12 50 / 60 Hz
o11 Language
(50=0, 60=1)
Following installation of a data com­munication module, the controller can be operated on a par with the other controllers in ADAP-KOOL® refrigera­tion controls.
The signal will be constantly updated. If you wish to follow the signal beyond the 20 seconds, the time-out period, push one of the two buttons before the time-out period expires
External current signal
Here you can read the value of the current signal received by the controller at its input
External voltage signal
Here you can read the value of the voltage signal received by the controller at its input
© Danfoss | DCS (ADAP-KOOL®) | 2015-11
u06 AI mA
u07 AI Volt
DKRCI.PS.RP0.C1.02 | 3
Loading...
+ 5 hidden pages