User Guide | Media temperature controller, EKC 361
Application examples
ICS/PM
ISC/PM with CVQ is a pilot-operated and pressure-dependent
valve for controlling media temperature.
The ICS or PM must be equipped with a CVQ pilot valve in order
to position ICS or PM. The CVQ valve is operated by the EKC 361
controller.
Please notice that a power failure will cause the CVQ pilot valve to
fully open ICS/PM. If it is required that ICS/PM must close at power
failure, the pilot valve type EVM-NC can be installed.
If the Digital Input is ON, it releases the ICS/PM for controlling
temperature. If the Digital Input is OFF, if stops controlling PM/ICS,
but EKC 361 will maintain a CVQ minimum temperature. (Parameter n02)
Please see separate literature for ICS/PM
ICS : DKRCI.PD.HS0.APM : DKRCI.PD.HL0.A-
ICM
ICM is a direct activating and pressure independent valve for controlling media temperature.
When ICM is selected, the ICM is positioned directly via the analog
output 0/4-20mA output from the EKC 361.
If the Digital Input is ON, it releases the ICM for controlling temperature. If the Digital Input is OFF, the ICM is forced to close.
The opening degree OD 0-100 % can be limited by parameter n32
and n33.
Please see separate literature for ICM
ICM : DKRCI.PD.HT0.A-
General for ICS/PM and ICM
The EKC 361 can also operate a solenoid valve in the liquid line
(Digital output on terminal 9 and 10). It will follow the status of
Digital Input, however if a low temperature alarm is detected (A2
alarm) the solenoid valve in the liquid line will be closed.
The EKC 361 can also operate a fan (Digital output on terminal 8
and 10). It will follow the status of Digital Input.
The Parameter (r12) must be ON in order to ensure general operation. If Parameter (r12) is OFF, EKC 361 will operate corresponding
to if Digital Input is OFF
As media temperature sensor is S
can also be used to control liquid.
is used. Please observe that S
air
air
As option an auxiliary temperature sensor Saux can be installed
but only for monitoring.
S
can both be shown as running display value selected by
air/Saux
parameter o17. The selected sensor (S
out on the Analog Output as 0/4-20 mA.
air
or S
) will be sent
aux
Temperature scaling with parameter o27 and o28. Please observe
by ICM the Analog Output is not available for sending temperature
signals (S
It is normally recommended, on a aircooler, to install S
evaporator air outlet side.
air
or S
).
aux
, at the
air
Extra options
• PC operation
The controller can be provided with data communication, so
that it may be hooked up with other products in the ADAPKOOL® range of refrigeration controls. Operation, moni toring
and data collection can then be performed from a PC - either in
situ or at a service company.
User Guide | Media temperature controller, EKC 361
Function
Very accurate temperature control
With this system where controller, pilot valve and main valve have
been adapted for optimum use in the refrigerating plant, the refrigerated products may be stored with temperature uctuations
of less than ±0.25°C.
High air humidity
As the evaporating temperature is constantly adapted to the
refrigeration needs and will always be as high as possible with a
very small temperature uctuation, the relative air humidity in the
room will be kept at a maximum.
Drying-out of the products will in this way be reduced to a mini-
mum.
Temperature is quickly attained
With the built-in PID control and the possibility of choosing between three transient phenomena, the controller can be adapted
to a kind of temperature performance that is optimum for this
particular refrigerating plant. See parameter (n07).
• Fastest possible cooling
• Cooling with less underswing
• Cooling where underswing is unwanted.
Regulation ICS/PM with CVQ
The controller receives signals from room sensor S
sensor must be placed at the air outlet from the evaporator to
. This room
air
obtain the best possible regulation. The controller sees to it that
the required room temperature is maintained.
Built-in between the controller and the actuator is a so-called
inner control loop which constantly checks the temperature (pressure) in the actuator’s pressure vessel. In this way a very stable
control system is obtained.
If there is a deviation between the required and the registered
temperature the controller will immediately send more or fewer
pulses to the actuator to counteract the error. A change of the
number of pulses will act on the temperature and hence the
pressure in the pressure vessel. As the charging pressure and the
evaporating pressure p0 follow each other, a changed charging
pressure will produce the eect that the valve’s opening degree is
also changed. The ICS/PM with CVQ system maintains the pressure
in the evaporator whatever pressure changes there may be on the
suction side (on the ICS/PM valve’s outlet).
Evaporating pressure limitation (p0 limitation)
The inner control loop mentioned above also causes the evaporating pressure to stay within a xed limit. In this way the system is
safeguarded against a too low supply air temperature.
It oers the following advantages:
- High-temperature systems can be connected to low-tempera ture
compressor units
- Protection against icing on evaporator
- Frost protection of liquid coolers
The allowed temperature in the actuator determines the evapora ting pressure
Actuator temperature
Regulation with ICM
When using ICM as selected valve the system will still control ICM
in order to maintain S
This system does not include any inner control loop.
according to entered setpoint.
air
It is a direct operating and pressure independent valve for controlling media temperature. (S
User Guide | Media temperature controller, EKC 361
Survey of functions
FunctionPara-
meter
Normal display
Parameter by operation via data communication
Normally S
S
aux
(017=Air) will be shown as running display value. If lower button is activated
air
will be displayed for 5 sec, and then return to S
air
If (017=Au) Saux will be shown as running display value. If lower button is activated
Sair will be displayed for 5 sec, and then return to Saux
If ICM has been selected (n03=6)
If (017=Air) S
(u24) will be displayed for 5 sec, and then return to S
If (017=Au) OD (u24) will be shown as running display value. If lower button is activated S
be displayed for 5 sec, and then return to OD (u24)
(017=Air) will be shown as running display value. If lower button is activated OD
air
.
air
air
will
Reference
Setpoint
Regulation is performed based on the set value provided that there is no external contribution
(o10).
(Push both buttons simultaneously to set the setpoint).
Temperature unit
Here you select whether the controller is to indicate the temperature values in °C or in °F. If indication in °F is selected, other temperature settings will also change over to Fahrenheit, either as
absolute values or as delta values.
External contribution to the setpoint
This setting determines how large a contribution (in °C/°F) is to be added to the set setpoint
when the input signal is max. (20 mA).
Correction of signal from S
(Compensation possibility through long sensor cable).
Correction of signal from S
(Compensation possibility through long sensor cable).
air
aux
Start/stop of refrigeration
With this setting refrigeration can be started and stopped. Start/stop of refrigeration can also be
accomplished with the external switch function. See also appendix 1.
Alarm
The controller can give alarm in dierent situations. When there is an alarm all the light-emitting
diodes (LED) will ash on the controller front panel, and the alarm relay will cut in.
Alarm for upper deviation
The alarm for too high S
active when the S
+ r06) can be seen in u02).
temperature is set here. The value is set in Kelvin. The alarm becomes
air
temperature exceeds the actual reference plus A01. (The actual reference (SP
air
Alarm for lower deviation
The alarm for too low S
active when the S
ture alarm is detected (A2 alarm) the solenoid valve in the liquid line (Digital output on terminal
temperature is set here. The value is set in Kelvin. The alarm becomes
air
temperature drops below the actual reference minus A02. If a low tempera-
air
9 and 10) will be closed
Alarm delay
If one of the two limit values is exceeded, a timer function will commence. The alarm will not
become active until the set time delay has been passed. The time delay is set in minutes.
Control parameters
Actuator’s max. temperature
Set the temperature (°C) the actuator is to have at the limit of the regulating range. The setting
ensures that the actuator will not become superheated and work itself away from the regulating
range. Due to tolerances in the actuator the value must be set 10K higher than indicated in the
curves on page 11.
Actuator’s min. temperature
Set the temperature (°C) the actuator will have at the limit of the regulating range. The setting
ensures that the actuator will not become too cold and work itself away from the regulating
range. Due to tolerances in the actuator the value must be set 10K lower than indicated in the
curves on page 11.
Air temp.
-SP Temp.
r05Temp unit
°C=0,
°F=1
(In AKM only °C is displayed whatever the
setting)
r06Ext. Ref.o set (°C/°F)
r09Adjust S
r10Adjust S
(°C/°F)
Air
(°C/°F)
Aux
r12Main Switch
A01Upper deviation
A02Lower deviation
A03Temp alarm delay
With data communication the importance
of the individual alarms can be dened.
Setting is carried out in the “Alarm destinations” menu. See also page 10.