Danfoss EKC 347 User Manual

Liquid level controller
EKC 347
Manual
Introduction
Application
The controller is used for regulation of the refrigerant level in:
• Pump reservoirs
• Separators
• Intermediate coolers
• Economisers
• Condensers
• Receivers
System
A signal transmitter will constantly measure the refrigerant liquid
level in the reservoir - the controller will receive the signal and
subsequently control the valve, in order to control the refrigerant liquid level according to liquid level setpoint.
Signaltransmitter
With the capacitive rod it is possible to set the refrigerant level
within a wide range.
EKC 347
The controller receive a signal and are then able to contol
low or high side applications. A analog input signal (voltage/ current) can displace the setpoint and then remote change of
setpoint is thus possible. EKC 347 does support 2 types of Danfoss expansion valves. (see below) One analog input is available as feed back from ICM in order to
indicate Opening degreee of the ICM.
Expansions valve
Two types of Danfoss expansion valves can be used ICM - ICM are direct operated motorized valves driven by digital stepper motor type ICAD AKV/A - AKVA or AKV are pulse-width modulating expansion
valves.
Functions
• Liquid level control
• Alarm if the set alarm limits are exceeded
• Relay outputs for upper and lower level limits and for alarm level
• Analog input signal which can displace the reference
• PI control
• Low or High side control
• When AKV/A is selected, a MASTER/SLAVE system can run up to 3 AKV/A with distributed Opening Degree
• Manual control of output
• Limitation of Opening degree possible
• ON/OFF operation with hysteresis
Extra options
• PC operation The controller can be provided with data communication, so that it may be hooked up with other products in the ADAP­KOOL® range of refrigeration controls. Operation, moni toring and data collection can then be performed from a PC - either in situ or at a service company.
LED's on front panel
All
Opening signal to valve
Indication of upper level limit
Indication of alarm level
EKC 347
2 Manual RS8AX702 DKRCC.ES.R1.A1.02/ 520H4020 © Danfoss 01-2011 EKC 347
Application examples
Pump reservoir
Modulating control of injection makes for a more stable liquid
level and suction pressure.
Separator on flooded evaporator
Modulating control and the valve’s large capacity range ensure a stable level - even under conditions of quickly changing loads.
Intermediate cooler
The level transmitter’s wide measuring range enables it to monitor the liquid at all levels of the reservoir - and hence to use the signal for safety functions in connection with the max. permissible level
Receiver / condenser
The control system’s short reaction time makes it very suited for high-pressure oat systems with small refrigerant charges.
EKC 347 Manual RS8AX702 DKRCC.ES.R1.A1.02/ 520H4020 © Danfoss 01-2011 3
Survey of functions
Function Para-
meter
Normal display Level control
The liquid level is indicated in % The % value is calculated on the basis of the input signal and the denition in ”o31”.
The valve’s actual opening degree can be displayed by giving the lower button a brief
push (1s). Cf. also o17.
Reference Set point
Regulation is based on the set value provided that there is no external contribution
(o10).
(Push both buttons simultaneously to set the setpoint).
External contribution to the reference
This setting determines how large a contribution is to be added to the set reference when the input signal is max (20 mA or 10 V. Cf. also o10). The value is set in %-points.
Start/stop of regulation
With this setting the level regulation can be started and stopped. Start/stop of level regulation can also be performed with the external contact function. Regulation is stopped if just one of them is OFF.
Alarm Level Alarms
The controller can give alarm in dierent situations. When there is an alarm the three lowest LED’s at the front of the controller will ash, and the alarm relay is cut in
Limit for upper level
Here you set the limit value for the upper level indication. The value is set in %. The relay for the upper level will become activated when the level exceeds the set value.
Limit for lower level
Here you set the limit value for the lower level indication. The value is set in %. The re­lay for the lower level will become activated when the level drops below the set level.
Time delay for upper level limit
When the limit value is exceeded a timer function will start. The relay will not become activated until the set time delay has been passed. The time delay is set in seconds.
Delay for lower limit level
When the limit value is exceeded a timer function will start.The relay will not become activated until the set time delay has been passed. The time delay is set in seconds.
Limit for alarm level
An alarm level can be set which when passed will activate the alarm relay- The value is set in %. Cf. also the denition in A18. If the limit alarm (A3) is not required, it can be avoided by means of the following set-
ting in A16:
100 : If the rising level denition has been chosen. (A18=0 or 2) 0: If the falling level denition has been chosen. (A18=1 or 3)
Time delay for alarm level
When the alarm level is exceeded a timer function will start. The relay will not become activated until the set time delay has been passed. The time delay is set in seconds.
Parameter by operation via data communication
- Liquid level
- OD %
- SP Liquid Level
r06 r06 Ext. Ref.oset
r12 r12 Main Switch
A01 A01 Upper Dev.
A02 A02 Lower Dev.
A03 A03 Upper Delay
A15 A15 Lower Delay
A16 A16 Limit Alarm
A17 A17 Limit Delay
4 Manual RS8AX702 DKRCC.ES.R1.A1.02/ 520H4020 © Danfoss 01-2011 EKC 347
Configuration of limit alarm (A3) level and lower limit alarm(A2) for pump cut-
A18 A18 Lim. LowMode
out.
To dene whether the limit alarm (A3) is linked to rising (A18=0) or falling level (A18=1). It is also possible to congurate the Relay for lower level limit when lower limit alarm (A2) is detected. Dedicated to switch o pumps at low level alarm.
0: Rising level. When liquid level is higher than A16, and time in A17 has expired, A3
alarm is generated.
1: Falling level . When liquid level is lower than A16, and time in A17 has expired, A3
alarm is generated.
2: Same function as if A18=0, but in addition (to that:
- When liquid level is higher than A02. No A2 alarm and Relay for lower level limit, gives ON signal (cut in) on terminal 8 and 10.
- When liquid level is lower than A02 and time in A15 has expired. A2 alarm is gener­ated and Relay for lower level limit, gives OFF signal (cut out) on terminal 8 and 10. 3: Same function as if A18=1, but in addition (to that:
- When liquid level is higher than A02. No A2 alarm and Relay for lower level limit, gives ON signal (cut in) on terminal 8 and 10.
- When liquid level is lower than A02 and time in A15 has expired. A2 alarm is gener­ated and Relay for lower level limit, gives OFF signal (cut out) on terminal 8 and 10.
Function Alarm relay when A1, A2 or A3 alarms are detected.
0: Alarm relay to be activated when A1 or A2 or A3 are detected. 1: Alarm relay only to be activated when A3 is detected.
A19 A19 Alarm type
(With setting = 0 the alarm is also
transmitted via the data communica­tion)
Alarm relay
The alarm relay will become activated if one of the set limits is exceeded or if the
controller loses the input signal from the level-measuring unit.
With data communication the impor­tance of the individual alarms can be dened. Setting is carried out in the “Alarm destinations” menu. See also
page 11.
Control parameters Injection Settings Definition of regulating principle
n35 n35 Low/High Pr.
Here you set whether the controller is to open or close the valve when the liquid level
is rising.
Low (0): Regulation on the low-pressure side. The valve closes when liquid level is
rising.
High (1): Regulation on the high-pressure side. The valve opens when liquid level is
rising.
Period time
n13 n13 AKV per.time An AKV/A valve is operated with pulses of a given length. The length depends on the opening degree required. If a large opening degree is required, the pulse will last for an entire period time. A period time will thus comprise both open and closed valve.
P - band
n04 n04 P-band If the value is reduced the regulating range will be reduced. (The P-band will be near
the reference).
I: Integration time Tn
n05 n05 Tn sec.
The I-link can be made passive by setting the value at max. (600s) (If the Tn value is increased the regulation becomes slower).
Neutralzone
n34 n34 Neutralzone The function is only active if the selected expansion valve is of type ICM
Min. opening degree
n33 n33 OD Min.
Here you can make a setting if you require a limitation of the valve’s working range.
Max. opening degree
n32 n32 OD Max. Here you can make a setting if you require a limitation of the valve’s working range.
EKC 347 Manual RS8AX702 DKRCC.ES.R1.A1.02/ 520H4020 © Danfoss 01-2011 5
Miscellaneous Miscellaneous Valve and output signal
o09
o09 AO type
The controller can control three types of expansion valves - ICM or AKV/A. With AKV/A up to three EKC 347 controllers can be linked up to a MASTER/SLAVE function (this function is only used if there is a need for several parallel AKV/A expan-
sion valves). The application is selected with one of the following settings: 1: ICM. AO: 4-20 mA 2: ICM. AO: 0-20 mA
3: AKV/A, AO: 4-20 mA 4: AKV/A, AO: 0-20 mA or, if the master/slave function is used:: 5: AKV/A, MASTER 6: AKV/A, SLAVE 1/1. AO:4-20 mA 7: AKV/A, SLAVE 1/1. AO:0-20 mA 8: AKV/A, SLAVE 1/2. AO:4-20 mA 9: AKV/A, SLAVE 1/2. AO:0-20 mA 10: AKV/A, SLAVE 2/2. AO:4-20 mA 11: AKV/A, SLAVE 2/2. AO:0-20 mA 12: AKV/A, SLAVE 1/1. AO:4-20 mA - AO always updated 13: AKV/A, SLAVE 1/1. AO:0-20 mA- AO always updated 14: AKV/A, SLAVE 1/2. AO:4-20 mA- AO always updated 15: AKV/A, SLAVE 1/2. AO:0-20 mA- AO always updated 16: AKV/A, SLAVE 2/2. AO:4-20 mA- AO always updated 17: AKV/A, SLAVE 2/2. AO:0-20 mA- AO always updated
With settings 1 and 2 the AO [mA] signal is dedicated for the motor valve ICM. With settings 3, 4, AO [mA] will be send out a signal for process indications. With settings 6, 7, 8, 9, 10 or 11, AO [mA] on EKC 347 SLAVE, will be send out a signal
for process indications.
With settings 12, 13, 14, 15, 16 or 17, AO will also be updated (active) when DI is OFF
Reference displacement
o10 o10 AI type If you wish to connect a signal that is to displace the controller’s control reference, the signal must be dened in this menu.
The signal is connected to terminals 19-21 or 20-21
0: No signal
1: 4 - 20 mA 2: 0 - 20 mA
3: 2 - 10 V 4: 0 - 10 V (The min. value will give no displacement. The max. value will displace the reference
with the value set in menu r06).
Input signal from the level-measuring unit
o31 o31 Levelsign.
The input signal for terminals 14-16 or 15-16 must be dened: 0: No signal
1: Current signal of 4-20 mA
2: Voltage signal. The voltage range must be set in the next two menus. (If the con­nections are a master/slave system and the signal to the master is 4 to 20 mA, the setting in the slave modules must also be selected to 1 – this must be done, even if
the signal is connected to the voltage input).
Voltage signal’s lower value
o32 o32 Lev. V. Low (only if the setting in 031 = 2).
Voltage signal’s upper value
o33 o33 Lev. V. High (only if the setting in o31 = 2)
Position signal
o34 o34 Valve feedb. If a ICM valve is selected it is possible to have ICM valve position as a [mA] feed back
signal
0: Not used 1: ICM mA feedback signal from connected ICAD. 2: Not used
Frequency
Set the net frequency.
o12 o12 50 / 60 Hz
(50=0, 60=1)
Address
If the controller is built into a network with data communication, it must have an address, and the master gateway of the data communication must then know this
address.
These settings can only be made when a data communication module has been mounted in the controller and the installation of the data communication cable has
Following installation of a data com­munication module, the controller can be operated on a par with the other controllers in ADAP-KOOL® refrigera-
tion controls.
been completed. This installation is mentioned in a separate document “RC8AC”..
The address is set between 1 and 60 o03 - The address is sent to the gateway when the menu is set in pos. ON
o04 ­(The setting will automatically change back to O after a few seconds.)
6 Manual RS8AX702 DKRCC.ES.R1.A1.02/ 520H4020 © Danfoss 01-2011 EKC 347
Language
This setting is only required when data communication is connected to the controller. Settings: 0=English, 1=German, 2=French, 3=Danish, 4=Spanish, 5=Italian, and 6=
Swedish
When the controller is operated via data communication, the texts in the right-hand column will be shown in the selected language. When you change the setting to an other language you must activate o04 before "the new language" can be visible from the AKM program.
Selection of parameter for displays and AO
The selection depends on the setting made in menu ”o34”. The selected value to display is also send to AO, except when ICM or AKV/A as MASTER, has been selected as valve type (o09=1 or 2 or 5)
If o34 has been set at 0, the subsequent setting of o17 will mean: 0: The liquid level will be shown in the ”normal display” 1: The valve’s opening degree OD will be shown in the ”normal display”
If o34 has been set at 1, the subsequent setting of o17 will mean: 0: The liquid level will be shown in the ”normal display” 1: The ICM valve position feed back signal [%] will be shown in the ”normal display”
The normal display has now been selected. If the other is requested, activate the con­trollers lowest button This will give a display showing of liquid level/opening degree
- or vice versa. After ve seconds the display will revert to the original mode.
Manual control of outputs
In connection wit service the individual relay outputs and the AKV/A output can be put in pos. ON. But not until regulation has been stopped. OFF: No override 1: Relay for upper level is ON 2: Relay for lower level is ON 3: AKV/A output is ON 4: Alarm relay is activated (terminals 12 and 13 will be connected)
Service Service
A number of controller values can be printed for use in a service situation Read liquid level u01 u01 Liquid level
Read the control reference
(Set reference + any contribution from external signal) Read valve’s opening degree u24 u24 OD % Read value of the external current signal (reference displacement) which is received
on terminals 19-21
Read value of the external voltage signal (reference displacement) which is received
on terminals 20-21 Read value of the current signal (level signal) received on terminals 15-16 u30 u30 Levelsign. mA Read value of the voltage signal (level signal) received on terminals 14-16 u31 u31 Levelsign. V Read value of the current signal (position signal from the valve) received on terminals
17-18 Read position signal from the valve. The value is converted into % of the total open-
ing degree Read value of the delivered current signal (terminals 2-5) u08 u08 AO mA Read status of input DI (start/stop input) u10 u10 DI
Operating status
Operating status of the controller can be called forth in the display. Push briey (1s) the upper button. If there is a status code, it will be shown on the dis­play. (Status codes have lower priority than alarm codes. In other words, you cannot see a status code, if there is an active alarm).
The individual status codes have the following meanings:
S10: Level regulation stopped by the internal or external start/ stop 10 S12: Liquid level had exceeded A01 limit or Liquid level is lower than A02 limit 12
o11 o11 Language
o17 o17 Display / AO
o18 -
u02 u02 Liq. Lev Ref
u06 u06 Ext. Ref. mA
u07 u07 Ext. Ref. V
u32 u32 Valve fb mA
u33 u33 Valve fb %
-- DO1 Limit alarm
Read status of alarm relay ON is operating status with alarm
-- DO2 Upper alarm
Read status of the relay for the upper
level limit
-- DO3 Lower alarm
Read status of the relay for the lower
level limit
EKC State
(0 = regulation)
EKC 347 Manual RS8AX702 DKRCC.ES.R1.A1.02/ 520H4020 © Danfoss 01-2011 7
Operation Menu survey
Display
The values will be shown with three digits, and after an opera-
tion the controller will return to its standard mode and show the
measured liquid level.
Light-emitting diodes (LED) on front panel
There are LED’s on the front panel which will light up when the
corresponding relay is activated.
The upper LED will indicate the valve’s opening degree. A short
pulse indicates a slow liquid ow and a long pulse a fast liquid
flow. The three lowest LED’s will ash, if there is an error in the regula­tion.
In this situation you can upload the error code on the display and cancel the alarm by giving the uppermost button a brief push.
The buttons
When you want to change a setting, the two buttons will give you a higher or lower value depending on the button you are push­ing. But before you change the value, you must have access to the menu. You obtain this by pushing the upper button for a couple of seconds - you will then enter the column with parameter codes. Find the parameter code you want to change and push the two buttons simultaneously. When you have changed the value, save the new value by once more pushing the two buttons simultane­ously.
Gives access to the menu
Gives access to changes
Saves a change
(or cutout an alarm)
Examples of operations
Set reference
1. Push the two buttons simultaneously
2. Push one of the buttons and select the new value
3. Push both buttons again to conclude the setting
Set one of the other menus
1. Push the upper button until a parameter is shown
2. Push one of the buttons and nd the parameter you want to
change
3. Push both buttons simultaneously until the parameter value is
shown
4. Push one of the buttons and select the new value
5. Push both buttons again to conclude the setting
Literature survey:
Manual for EKC 347 ..............................................................RS8AX---
Instruction for EKC 347 .......................................................RI8BY---
Installation guide, "Data communication link
for ADAP-KOOL® " .................................................................RC8AC---
Function
Normal display
Read the measured liquid level - % 50.0
If you wish to see the actual opening degree, give the lower button a brief push
If you wish to set the required setpoint you obtain ac­cess by pushing both buttons simultaneously
Level control
External contribution to the reference. Cf. also o10. Value is set in %-points.
Start / stop of level control r12 OFF/0 ON/1 1
Alarm
Upper level limit A01 0 % 100% 85
Lower level limit A02 0% 100% 15
Time delay for upper level limit A03 0 s 999 s 50
Time delay for lower level limit A15 0 s 999 s 10
Level alarm limit A16 0 % 100 % 20
Delay for level alarm A17 0 s 999 s 0 The level alarm is linked to:
0: Rising level (higher level than A16)
1: Falling level (lower level than A16) 2: Same function as if A18=0. When A2 alarm is gener­ated and Relay for lower level limit, gives OFF signal
(cut out).
3: Same function as if A18=1 When A2 alarm is gener­ated and Relay for lower level limit, gives OFF signal
(cut out).
Function for Alarm relay when A1, A2 or A3 alarms are
detected.
0: Alarm relay to be activated when A1 or A2 or A3 are
detected.
1: Alarm relay only to be activated when A3 is detected.
Regulating parameters
P - band n04 0%/O 200% 30
I: Integration time Tn n05 60
Period time (only if AKV/A valve is used) n13 3 s 10 s 6
Max. opening degree n32 0% 100% 100
Min. opening degree n33 0% 100% 0
Neutral zone (only for ICM valve) n34 2% 25% 2
Denition of regulating principle
Low: On the low-pressure side (valve closes when
liquid level is rising)
High: On the high-pressure side (valve opens when
liquid level is rising)
Miscellaneous
Controller's address o03* 0 60 0
ON/OFF switch (service-pin message) o04* OFF ON Dene valve and output signal:
1: ICM. AO: 4-20 mA 2: ICM. AO: 0-20 mA
3: AKV/A, AO: 4-20 mA 4: AKV/A, AO: 0-20 mA
Or if a master/slave function is used:
5: AKV/A, MASTER 6: AKV/A, SLAVE 1/1. AO:4-20 mA 7: AKV/A, SLAVE 1/1. AO:0-20 mA 8: AKV/A, SLAVE 1/2. AO:4-20 mA 9: AKV/A, SLAVE 1/2. AO:0-20 mA 10: AKV/A, SLAVE 2/2. AO:4-20 mA 11: AKV/A, SLAVE 2/2. AO:0-20 mA 12: AKV/A, SLAVE 1/1. AO:4-20 mA - AO always updated 13: AKV/A, SLAVE 1/1. AO:0-20 mA- AO always updated 14: AKV/A, SLAVE 1/2. AO:4-20 mA- AO always updated 15: AKV/A, SLAVE 1/2. AO:0-20 mA- AO always updated 16: AKV/A, SLAVE 2/2. AO:4-20 mA- AO always updated 17: AKV/A, SLAVE 2/2. AO:0-20 mA- AO always updated
SW = 1.1x
Pa­ram-
Min. Max.
eter
- % 0
- 0% 100% 100
r06 -100 100 0.0
A18 0 3 0
A19 0 1 0
n35 Low/0 Hig/1 0
o09 1 17 1
600/
O
Fac. set­ting
400
8 Manual RS8AX702 DKRCC.ES.R1.A1.02/ 520H4020 © Danfoss 01-2011 EKC 347
Continued from previous page
Dene the input signal on terminals 19, 20, 21 (external
reference displacement)
0: OFF
1: 4-20 mA 2: 0-20 mA
3: 2-10 V 4: 0-10 V
Language
0=English, 1=German, 2=Frensh, 3=Danish, 4=Spanish, 5=Italian, 6=Swedish. When you change the setting you must also activate o04.
Set supply voltage frequency o12
Selection of parameter for display and AO (except from when o09=1,2 or 5) If o34 = 0: 0: Liquid level is show 1: Valve’s opening degree OD will be shown If o34 = 1: 0: Liquid level is show 1: The ICM valve position feed back signal [%] will be
shown Manual control of outputs:
OFF: No manual control 1: Upper level relay put in pos. ON 2: Lower level relay put in pos. ON 3: AKV/A output put in pos. ON 4: Alarm relay activated (cut out)
Dene input signal (level signal) on terminals 14, 15, 16 0: OFF
1: 4-20 mA
2: 0-10 V (also set the voltage values in the next two
menus) Read functional description if the connection used is a master/slave function.
Dene input signal’s lower value for terminal 14, if required
Dene input signal’s upper value for terminal 14, if required
Dene input signal on terminals 17-18 0: Not used 1: ICM mA feedback signal from ICAD connected 2: Not used
Service
Read liquid level u01 %
Read liquid level reference u02 %
Read external contribution to the reference u06 mA
Read external contribution to the reference u07 V
Read current signal on the analog output u08 mA
Read status of input DI u10
Read valve’s opening degree u24 %
Read level signal u30 mA
Read level signal u31 V
Read signal from ICM/ICAD u32 mA
Read signal from ICM/ICAD converted into % u33 %
*) This setting will only be possible if a data communication module has been
installed in the controller.
o10 0 4 0
o11* 0 6 0
0/50 Hz1/60
o17 0 1 0
o18 OFF 4 0
o31 0 2 1
o32 0.0 V 4.9 V 4.0
o33 5.0 V 10 V 6.0
o34 0 2 0
0
Hz
Error messages
The controller can give the following messages:
E1
E12
Error message
E21 Level signal outside the range 1)
E22 Signal from ICM/ICAD outside the range
A1
Alarm message
A2 Lower level limit reached
A3 Alarm level limit reached
1) If E21 is detected. EKC 347 will force the valve to close or open the valve depending af n35
If Low pressure has been selected. (n35=0) The valve is forced to fully closed, however if Min. Opening Degree (n33) is higher
than 0 the valve will open to the value of n33
If High pressure has been selected. (n35=1) The valve is forced to fully open, however if Max. Opening Degree (n32) is lower than
100 the valve will open to the value of n32
Errors in the controller
The external reference contribution is outside
the range
Upper level limit reached
Ordering
Type Function Code No.
EKC 347 Liquid level controller 084B7067
EKA 174
Level transmitter/controller: .............Kindly refer to catalogue RK0YG
AKV / AKVA Valves: ................................Kindly refer to catalogue RK0YG
ICM and ICAD................ ..........................Kindly refer to DKRCI.PD.HT0.A
Data communication module
(accessories), (RS 485 module)
with galvanic separation
084B7124
Factory setting If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep both buttons depressed at the same time as you recon nect the supply voltage
EKC 347 Manual RS8AX702 DKRCC.ES.R1.A1.02/ 520H4020 © Danfoss 01-2011 9
Data
24 V a.c. +/-15% 50/60 Hz, 60 VA
Supply voltage
Power consumption
Input signal
* Ri =
0(4)-20mA:100 ohm
0(2)-10 V: 100 kohm
Relay output 2 pcs. SPST
Alarm relay 1 pcs. SPST
Current output
Valve connection
Data communication
Environments
Enclosure IP 20
Weight 300 g
Mounting DIN rail
Display LED, 3-digits
Terminals max. 2.5 mm
Approvals
(the supply voltage is galvanically separated from
the input and output signals. Input/output are not individual galvanic isolated)
Controller
20 W coil for AKV
Level signal * 4-20 mA or 0-10 V
Reference displace­ment *
ICM valve feedback
signal *
Contact function start/stop of regulation
0-20 mA or 4-20 mA
Max. load: 500 ohm
ICM - via current output
AKV/A- via 24 a.c. Pulse-Width Modulating output
Possible to connect a data communication
module
-10 - 55°C, during operation
-40 - 70°C, during transport
20 - 80% Rh, not condensed
No shock inuence / vibrations
EU Low Voltage Directive and EMC demands re CE-marking complied with. LVD-tested acc. to EN 60730-1 and EN 60730-2-9 EMC-tested acc. to EN61000-6-3 and EN 61000-
6-2
2
multicore
5 VA 55 VA
4-20 mA, 0-20 mA, 2-10 V or 0-10 V
From ICAD 0/4-20 mA
AC-1: 4 A (ohmic) AC-15: 3 A (inductive)
Connections
Necessary connections
Terminals:
25-26 Supply voltage 24 V a.c. 15-16 Signal from level transmitter type AKS 41 or 14-16 Signal from transmitter 0-10 V 23-24 Expansion valve type AKV or AKVA or 2-5 Expansion valve type: ICM with ICAD
1-2 Switch function for start/stop of regulation. If a switch is
not connected, terminals 1 and 2 must be shortcircuited.
Application dependent connections
Terminal:
12-13 Alarm relay. See A19 and A18 8-10 Relay for lower level limit. See A18 for setting of ON (cut
in) or OFF (cut out) function
9-10 Relay for upper level limit. There is connection between
9 and 10 when the set value is passed
17-18 ICM valve feedback signal from ICAD 0/4-20 mA
19-21 Current signal or 20-21 Voltage signal from other regulation (for external refer-
ence displacement)
3-4 Data communication
Mount only, if a data communication module has been
mounted. It is important that the installation of the data communi-
cation cable be done correctly. Cf. separate literature No.
RC8AC...
Data communication
AKS 41/41U
AKV/AKVA Coil always 24 V a.c Max. 20 W.
Can also be a relay with coil 24 V a.c.
Fx EKC 347 5 VA 20 W coil for AKV 55 VA
10 Manual RS8AX702 DKRCC.ES.R1.A1.02/ 520H4020 © Danfoss 01-2011 EKC 347
Connections examples
EKC 347 – ON/OFF Application. Open/Close solenoid valve with coil 110 V
0-10V
Auxiliary relay, with coil : 24 V a.c
ON/OFF application Beside of modulating PI control EKC 347 does also support ON/ OFF operation with hysteresis.
To ensure this operation:
P.Band must be (n04)=0%//OFF Hysteresis is given by (n34) Setpoint as normal procedure. (pushing the upper/lower buttons simultaneously) Low or High side system. (n35)
Voltage : 110 V a.c
Solenoid with coil :
110 V a.c
Low pressure system
EKC 347 Manual RS8AX702 DKRCC.ES.R1.A1.02/ 520H4020 © Danfoss 01-2011 11
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specications already agreed. All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
12 Manual RS8AX702 DKRCC.ES.R1.A1.02/ 520H4020 © Danfoss 01-2011 EKC 347
DE-BD
EKC 347 Manual RS8AX702 DKRCC.ES.R1.A1.02/ 520H4020 © Danfoss 01-2011 13
14 Manual RS8AX702 DKRCC.ES.R1.A1.02/ 520H4020 © Danfoss 01-2011 EKC 347
EKC 347 Manual RS8AX702 DKRCC.ES.R1.A1.02/ 520H4020 © Danfoss 01-2011 15
Loading...