Capacity controller
EKC 331
REFRIGERATION AND AIR CONDITIONING
Manual
Introduction
Application
The controller is used for capacity regulation of compressors or condensers in small refrigerating systems.
Advantages
•Patented neutral zone regulation
•Sequential or cyclic operation
Functions
• Regulation
Regulation with up to four relay outputs can be carried out. Regulation takes place with a set reference which is compared to a signal from a pressure transmitter.
• Relay module
It is possible to use the controller as relay module, so that the relays are cut in or out by means of an external voltage signal.
• Alarmfunction
A relay becomes activated when the set alarm limits are exceeded.
• Digital input
The digital input can be used for:
-night operation where the suction pressure is raised
-heat recovery where the condensing pressure is raised
-external start/stop of the regulation.
Function
Capacity regulation
The cut-in capacity is controlled by signals from the connected pressure transmitter and the set reference.
Outside the reference a neutral zone is set where the capacity will neither be cut in nor out.
Outside the neutral zone (in the hatched areas named +zone and -zone) the capacity will be cut in or out if the regulation registers a change of pressure “away” from the neutral zone. Cutin and cutout will take place with the set time delays.
If the pressure however “approaches” the neutral zone, the controller will make no changes of the cut-in capacity.
The size of the +zone and -zone is identical and defined to be constantly 0.7 times the set value of the neutral zone.
If regulation takes place outside the hatched area (named ++zone and --zone), changes of the cut-in capacity will occur somewhat faster than if it were in the hatched area. The set time delays will here be reduced by factor 0.3.
Cutin of steps can be defined for either sequential or cyclic operation.
Relay module |
|
|
|
|
|
|
The controller can also be used as a relay module where the relays |
|
|
||||
in the module will then be controlled by the received voltage |
|
|
|
|||
signal. |
|
|
|
|
|
|
Depending on the definition of the signal and the number of |
|
|
|
|||
relays used, the relays will be “distributed” over the signal. |
|
|
|
|
||
A hysteresis around the individual cutin and cutout points will |
|
|
|
|||
ensure that the relay will not cut in or out when it is not called for. |
|
|
||||
2 |
Manual |
RS.8A.G2.02 |
© |
Danfoss |
10-2000 |
EKC 331 |
Survey of functions
Function |
Para- |
Parameter by operation via data |
|
meter |
communication |
|
|
|
Normal display |
|
|
|
|
|
Normally the signal from the pressure transmitter is shown. If the controller is used as |
|
Pressure |
relay module, Uin will appear on the display. |
|
|
|
|
|
Pressure regulation |
|
Reference |
|
|
|
Regulation reference |
- |
Press. set point |
Regulation is based on the set value. |
|
|
(Push both buttons simultaneously to set the menu.) |
|
|
|
|
|
Neutral zone |
r01 |
Neutral zone |
There is a neutral zone around the reference. See also page 2. |
|
|
|
|
|
Displacement of reference |
r13 |
Pressure o set |
The set reference may be displaced with a fixed value when a signal is received at the |
|
|
DI input. Regulation will then be based on the set reference plus the value set here. |
|
|
The total reference can be seen when you push the lower of the two buttons. (Cf. also |
|
|
Definition of DI input). |
|
|
|
|
|
Reference limitation |
|
|
The controller’s setting range for the reference can be narrowed down, so that you |
|
|
cannot accidentally set a too high or too low value - that may result in damage to the |
|
|
system. With these settings the reference can only be set between the two values. |
|
|
|
|
|
Max. permissible reference value. |
r02 |
Max. set point |
|
|
|
Min. permissible reference value. |
r03 |
Min. set point |
|
|
|
Pressure unit |
r05 |
Unit |
Here you can select whether the controller is to indicate the pressure in bar or psig. |
|
bar=0 |
(When psig is selected, the settings must also be in psig). |
|
psig=1 |
|
|
(In AKM only bar is used, whatever the |
|
|
setting). |
Alarm |
|
Alarm settings |
The controller can give alarm in di erent situations. When there is an alarm all the |
|
|
light-emitting diodes (LED) will flash on the controller front panel, and the alarm relay |
|
|
will cut in. |
|
|
|
|
|
Upper deviation |
A10 |
Max. pressure |
Here you set when the alarm at high pressure is to enter into e ect. The value is set as |
|
|
an absolute value. |
|
|
See also emergency procedure page 5. |
|
|
|
|
|
Lower deviation |
A11 |
Min. pressure |
Here you set when the alarm at low pressure is to enter into e ect. The value is set as |
|
|
an absolute value. |
|
|
See also emergency procedure page 5. |
|
|
|
|
|
Alarm delay |
A03 |
Alarm delay |
If one of the two limit values is exceeded, a timer function will commence. The alarm |
|
|
will not become active until the set time delay has been passed. The time delay is set |
|
|
in seconds. |
|
|
|
|
|
Give the top button a brief push to zeroset the alarm and to have the message shown |
|
Reset alarm |
on the display. |
|
The function zerosets all alarms when |
|
|
set in pos. ON. |
|
|
|
|
|
Alarm relay |
|
|
Here you can read the status of the |
|
|
alarm relay. |
|
|
(ON indicates operation with alarm). |
|
|
|
|
|
With data communication the impor- |
|
|
tance of the individual alarms can be |
|
|
defined. Setting is carried out in the |
|
|
“Alarm destinations” menu. See also |
|
|
page 8. |
|
|
|
EKC 331 |
Manual RS.8A.G2.02 © Danfoss 10-2000 |
3 |