Danfoss EKC 326A User guide

Danfoss EKC 326A User guide

User Guide

Controller to regulate

CO2 gas pressure

EKC 326A

ADAP-KOOL® Refrigeration control systems

Introduction

 

 

 

 

 

 

Application

 

 

 

 

 

 

The controller can be used in systems with transcritical and sub-

 

 

critical cooling control systems where CO2 is used as a refrigerant.

 

 

The controller regulates the pressure in the gas cooler (condens-

 

 

er) so that the system achieves the optimal COP.

 

 

 

 

The controller covers the following:

 

 

 

 

 

• Transcritical CO2 refrigeration systems (booster, cascade, high

 

 

pressure)

 

 

 

 

 

 

• Transcritical CO2 heat pump systems

 

 

 

 

 

• Transcritical CO2 refrigeration systems with heat recovery

 

 

 

• Transcritical CO2 chiller systems

 

 

 

 

 

 

• Extra capacity in warm periods. An improvement in the system’s

 

 

cooling performance can be achieved by displacement of the

 

 

set point (“extra compressor")

 

 

 

 

 

 

Advantages

 

 

 

 

 

 

Maximum COP

 

 

 

 

 

 

The controller guarantees the system’s maximum performance

 

 

by maintaining the optimal pressure in the gas cooler when

 

 

 

regulation takes place in the transcritical range.

 

 

 

 

• The controller will always optimise to a subcritical state.

 

 

 

 

• Regulating the receiver pressure based on the receiver pressure

 

 

reading

 

 

 

 

 

 

• Heat recovery with adjustable reference pressure, 0-10 V

 

 

 

 

• Optimum heat pump operation

 

 

 

 

 

 

System

 

 

 

 

 

 

The pressure in the gas cooler is controlled by the valve. Regula-

 

 

tion must have inputs from both a pressure transmitter PGC and

 

 

a temperature sensor SGC. Both must be fitted in the outlet im-

 

 

mediately after the gas cooler.

 

 

 

 

 

 

The valve is an ICMTS valve, which has been specially developed

 

 

for the pressure conditions that exist in a transcritical CO2 system.

 

 

The motor section of the valve is an ICAD actuator and is control-

 

 

led by a 0-10 V signal from the controller.

 

 

 

 

 

If it is necessary to maintain a constant receiver pressure, a valve

 

 

(ETS, CCM or CCMT) and pressure transmitter (Prec) can be in-

 

 

 

stalled. The gas from the receiver bypasses to the inlet side of the

 

 

high pressure compressor.

 

 

 

 

 

 

Functions

 

 

 

 

 

 

Maximum COP control

 

 

 

 

 

 

The controller maintains optimum pressure in the transcritical

 

 

range based on a pressure and temperature reading.

 

 

 

 

The reference line is defined with a point at 100 bar. The desired

 

 

temperature can be set here.

 

 

 

 

 

 

Subcooling

 

 

 

 

 

 

d T subcooling can be used in the subcritical range.

 

 

 

 

Contents

 

 

 

 

Menu survey

10

Introduction........................................................................................................

 

 

 

2

Examples..............................................................................................................

 

 

 

4

Connections......................................................................................................

11

Survey of functions..........................................................................................

 

 

 

6

Data......................................................................................................................

13

Operation...........................................................................................................

 

 

 

10

Ordering.............................................................................................................

13

 

 

 

 

 

Appendix............................................................................................................

14

2

Manual 

RS8FM602 

© 

Danfoss 

02-2016

EKC 326A

Receiver control

 

 

 

 

 

 

The receiver pressure can be controlled so that it is kept at a set

 

 

reference point. This control requires the installation of an ETS

 

 

valve a (CCM valve) and a pressure transmitter.

 

 

 

 

If only monitoring and not control is required, the valve should

 

 

not be installed. Install the pressure transmitter only.

 

 

 

 

Ensuring that the receiver pressure is not too low

 

 

 

 

A limit value can be set, and if the pressure falls below this value,

 

 

the ICMTS valve will be opened. The valve will then open gradually

 

 

through the associated P band. Open to the value "n32" ( Vhp OD

 

 

Max).

 

 

 

 

 

 

Protecting against high receiver pressure

 

 

 

 

 

A limit value can be set, and if the pressure rises beyond this value,

 

 

the ICMTS valve will be closed. The valve will then close gradually

 

 

through the associated P band.

 

 

 

 

 

 

Extra refrigeration capacity (“extra compressor”)

 

 

 

 

This function improves the system’s refrigeration capacity by

 

 

 

increasing the reference pressure in the gas cooler with a offset

 

 

value.

 

 

 

 

 

 

It is activated via a switch function.

 

 

 

 

 

Heat recovery or heat pump

 

 

 

 

 

 

This function will increase the gas pressure to a set value. This

 

 

value will be equivalent to a specific temperature.

 

 

 

 

The value can either be fixed or can vary in accordance with an

 

 

input signal of 0-10 V as follows:

 

 

 

 

 

 

A signal of 1.5 V or above can activate the function and increase

 

 

the reference to Pgc HR Min.

 

 

 

 

 

 

If a variable reference is required, then a signal between 2-10 V

 

 

can be connected. The signal will increase the reference further.

 

 

This function works both in subcritical and transcritical ranges.

 

 

Output signal

 

 

 

 

 

 

The controller has a voltage output on 0-10 V. The signal is used to

 

 

control the ICMTS valve via the ICAD actuator.

 

 

 

 

Valves opening degree

 

 

 

 

 

 

The opening degree of both ICMTS and ETS valves (CCM valve)

 

 

can be narrowed if necessary.

 

 

 

 

 

 

PC-operation

 

 

 

 

 

 

The controller can be provided with data communication so that it

 

 

can be connected to other products in the range of ADAP-KOOL®

 

 

refrigeration controls. In this way operation, monitoring and data

 

 

collection can be performed from one PC – either on the spot or in

 

 

a service company.

 

 

 

 

 

 

Temperature reading

 

 

 

 

 

 

The temperature by the gas cooler must be measured using a Pt

 

 

1000 ohm sensor type AKS 21.

 

 

 

 

 

 

The sensor must be mounted immediately next to the gas

 

 

cooler outlet to produce a correct signal.

 

 

 

 

 

Pressure reading (bar)

 

 

 

 

 

 

The pressure by the gas cooler must be measured using a pressure

 

 

transmitter type AKS 2050.

 

 

 

 

 

 

The pressure transmitter must be mounted immediately next

 

 

to the gas cooler outlet to produce a correct signal.

 

 

 

 

Emergency cooling

 

 

 

 

 

 

The valve's average opening degree for the last six hours is

 

 

 

regularly saved. This opening degree is used if there is a need for

 

 

emergency cooling.

 

 

 

 

 

 

EKC 326A

Manual 

RS8FM602 

© 

Danfoss 

02-2016

3

Examples

Simple heat recovery system

Partial heat recovery system

Heat recovery system (or heat pump system)

4

Manual  RS8FM602  ©  Danfoss  02-2016

EKC 326A

Extra refrigeration capacity (“extra compressor”)

This function improves the system’s refrigeration capacity by increasing the reference pressure (Pgc Ref) in the gas cooler. The cooling performance increases to Q0+dh0.

The function also increases the load on the compressor motor as pressure increases. Power consumption increases to Qm+dQm.

Increasing pressure reference with heat recovery

The function will increase the gas pressure reference to the Pgc HR Min. value when it receives a signal.

The function is activated by an on/off signal at the voltage input.

Increasing pressure reference with heat recovery, variable reference

The function will increase the gas pressure reference to the value where it receives a signal.

The function is activated by a voltage signal between 0-10 V.

Between 0-2 V it is regulated normally

At 2 V the reference changes to the setting “Pc HR Min”

At 10 V the reference will increase further using the setting “Pgc HR offset”

Between 2-10 V the reference is variable.

EKC 326A

Manual  RS8FM602  ©  Danfoss  02-2016

5

Loading...
+ 11 hidden pages