Danfoss EKC 302A, EKC 302B Installation guide [da]

INSTRUCTIONS
EKC 302A EKC 302B
084R8034
t
= 0 - +55°C
amb
230 V a.c.
50/60 Hz
2.0 VA
084R8034
Type: Pt 1000 (1000 Ω /0°C ) /
Ptc 1000 (1000 Ω /25°C ) / NTC-M2020 (5000 Ω / 25°C)
( o06)
10 V < U < 256 V
IEC 60730
DO1 *
DO2 *
DO3 *
DO4 **
* EKC 302: DO1 are 20 A relays. DO2 and DO3 are 16 A relays. DO4 are 10 A relays. The max. load listed above must be observed when connecting without zero­crossing control. When connecting with zero-crossing control, the load must be increased to the value indicated by 2) ** Gold plating ensures make function with small contact loads
1) With external relay (c70=ON) (zero-crossing control disabled)
2) Without external relay (c70=OFF) (zero-crossing control enabled)
10 (6) A & (5 FLA, 30 LRA) 1) 16 (8) A & (10 FLA, 60 LRA) 2) 6 (3) A & (3 FLA, 18 LRA) 1) 10 (6) A & (5 FLA, 30 LRA) 2) 6 (3) A & (3 FLA, 18 LRA) 1) 10 (6) A & (5 FLA, 30 LRA) 2) 4 (1)A Min. 100 mA**
Data communication LON RS 485 / MOD-bus:
MOD-bus
LON
RI8PK153 08-2011
EKC 302A
*) AU:
Guld, Gold or Oro l = max. 15 m
EKC 302B
*) AU:
Guld, Gold or Oro l = max. 15 m
*)
*)
*)
2 Instructions RI8PK153 © Danfoss 08/2011 EKC 302A, B
Knapperne
Dansk
Indstille en menu
1. Tryk på den øverste knap til der vises en parameter
2. Tryk på øverste eller nederste knap og find hen til den parameter, du vil indstille
3. Tryk på den midterste knap indtil vær­dien for parameteren vises
4. Tryk på øverste eller nederste knap og find den nye værdi
5. Tryk igen på den midterste knap for at fastlåse værdien.
Indstille temperaturen
1. Tryk på den midterste knap til tempera­turværdien vises
2. Tryk på øverste eller den nederste knap
og find den nye værdi
3. Tryk på den midterste knap for at af-
slutte indstillingen.
Aflæse temperaturen ved S5 føleren
• Kort tryk på den nederste knap
Manuel start eller stop af en afrimning
• Tryk på den nederste knap i 4 sekunder.
Lysdioder
= køling = afrimning = ventilator i gang
Blinker hurtigt ved alarm
Udkoble alarmrelæ / se alarmkode
• Kort tryk på den øverste knap
Opstart:
Reguleringen starter, når spændingen tilsluttes.
1 Se oversigten over fabriksindstillinger igennem. — Foretag de nødvendige ændringer i de respektive parametre 2 Ved netværk. Indstil adressen i o03 og send derefter adressen til gatewayen/systemenheden med indstillingen o04.
Parametre Regulator Min.-
Funktion Koder
Normal drift
Temperatur (setpunkt) --- -50°C 50°C 2°C
Termostat
Differens r01 0,1 K 20 K 2 K Max. begrænsning af setpunktsindstilling r02 -49°C 50°C 50°C Min. begrænsning af setpunktsindstilling r03 -50°C 49°C -50°C Justering af temperaturvisning r04 -20 K 20 K 0.0 K Temperaturenhed (°C/°F) r05 °C °F °C Korrektion af signalet fra Sair r09 -10 K 10 K 0 K Manuel service (-1), Stop regulering(0), Start regulering(1) r12 -1 1 1 Referenceforskydning under natdrift r13 -10 K 10 K 0 K Aktivering af referenceforskydningen r40 r39 OFF on OFF Værdi for referenceforskydning (kan aktiveres af r39 eller DI) r40 -50 K 50 K 0 K
Alarm
Forsinkelse på temperaturalarm A03 0 min 240 min 30 min Forsinkelse på døralarm A04 0 min 240 min 60 min Forsinkelse på temperaturalarm efter afrimning A12 0 min 240 min 90 min Høj alarmgrænse A13 -50°C 50°C 8°C Lav alarmgrænse A14 -50°C 50°C -30°C Alarm forsinkelse DI A27 0 min 240 min 30 min Høj alarmgrænse for kondensatortemperatur (o70) A37 0°C 99°C 50°C
Kompressor
Min. ON-tid c01 0 min 30 min 0 min Min. OFF-tid c02 0 min 30 min 0 min Kompressorrelæ skal koble modsat (NC-funktion) c30 0 / OFF 1 / On 0 / OFF Eksterne relæer (Nulgennemgangsstyring - kun EKC 302) Skal være ON ved tilslutning til eksterne relæer
Afrimning
Afrimningsmetode (ingen/EL/gas) d01 no Gas EL Afrimnings-stoptemperatur d02 0°C 25°C 6°C Interval mellem afrimningsstarter d03 0 hours 48 hours 8 hours Max. afrimningsvarighed d04 0 min 180 min 45 min Tidsforskydning på afrimningsindkoblingen ved opstart d05 0 min 240 min 0 min Afdrypningstid d06 0 min 60 min 0 min Forsinkelse på ventilatorstart efter afrimning d07 0 min 60 min 0 min Ventilator-starttemperatur d08 -15°C 0°C -5°C Ventilator indkoblet under afrimning
0: stoppet 1: Kører 2: Kører under pump down og afrimning
Afrimningsføler (0=tid, 1=S5, 2=Sair) d10 0 2 0 Max. opsummeret køletid imellem to afrimninger d18 0 hours 48 hours 0 hours Behovstyret afrimning - S5 temperaturens tilladte variation ved isopbygning. På central­anlæg vælges 20 K (=off)
Ventilator
Ventilatorstop ved udkoblet kompressor F01 no yes no Forsinkelse af ventilatorstop F02 0 min 30 min 0 min Ventilatorstop temperatur (S5) F04 -50°C 50°C 50°C
Realtidsur
Seks starttidspunkter for afrimning. Indstilling af timer. 0=OFF Seks starttidspunkter for afrimning. Indstilling af minutter. 0=OFF Ur - Timeindstilling t07 0 timer 23 timer 0 timer
t01-t06 0 timer 23 timer 0 timer
t11-t16 0 min 59 min 0 min
EKC
EKC
302A
c70 OFF On On
d09 0 2 1
d19 0 K 20 K 20 K
værdi
302B
Max.­værdi
Fabriks-
indstil-
ling
SW = 1.0x
Aktuel indstil-
ling
EKC 302A, B Instructions RI8PK153 © Danfoss 08/2011 3
Ur - Minutindstilling t08 0 min 59 min 0 min Ur - Indstilling af dato t45 1 31 1 Ur - Indstilling af måned t46 1 12 1 Ur - Indstilling af år t47 0 99 0
Diverse
Forsinkelse af udgangssignaler efter opstart o01 0 s 600 s 5 s Indgangssignal på DI. Funktion: (0=ikke anvendt, 1=status på DI. 2=dørfunktion med alarm ved åben. 3=døralarm ved åben. 4=afrimningsstart (pulstryk). 5=ekstern hovedafbryder. 6=natdrift. 7=skift reference (r40 aktiveres). 8=alarmfunktion ved sluttet. 9=alarmfunktion ved åben. 10=møbelrengøring (pulstryk). 11=Inject off ved åben.) Netværksadresse (0=off) o03 0 240 0 On/Off omskifter (Service Pin meddelelse) o04 OFF ON OFF Adgangskode 1 (samtlige indstillinger) o05 0 100 0 Anvendt følertype (Pt /PTC/NTC) o06 Pt ntc Pt Display step = 0.5 (normal 0.1 ved Pt føler) o15 no yes no Max holdetid efter koordineret afrimning o16 0 min 60 min 20 Konfiguration af lysfunktionen (relæ 4) 1=ON under dagdrift. 2=ON / OFF via datakommunikation. 3=ON følger DI-funktionen, når DI er valgt til dørfunktion eller døralarm Aktivering af lysrelæ (kun hvis o38=2) o39 OFF ON OFF Møbelrengøring. 0= ingen møbelrengørring 1= kun ventilatorer. 2 Alle udgange er OFF o46 0 2 0 Adgangskode 2 (delvis adgang) o64 0 100 0 Overskriv regulatorens fabriksindstillinger med de nuværende indstillinger o67 OFF On OFF Evt. anden anvendelse for S5 føleren (bibehold indstillingen til 0, hvis den anvendes til afrimningsføler, ellers er 1=produktføler, og 2=kondensatorføler med alarm) Vælg anvendelsen for relæ 4: 1=afrimning , 2= alarm o72 Afr. /
Service
Temperaturen målt med S5 føleren u09 Status på DI indgangen. on=sluttet u10 Status på natdrift (on eller off) on=sluttet u13 Aflæse den øjeblikkelige reguleringsreference u28 Status på relæet til køling. (Kan styres manuelt, men kun når r12=-1.) u58 Status på relæet tll ventilator. (Kan styres manuelt, men kun når r12=-1.) u59 Status på relæet til afrimning. (Kan styres manuelt, men kun når r12=-1.) u60 Temperaturen målt med Sair føleren u69 Status på relæ 4 (alarm, afrimning, lys). (Kan styres manuelt, men kun når r12=-1.) u71
o02 0 11 0
o38 1 3 1
o70 0 2 0
1 2 2
Alarm
Fabriksindstilling Hvis du får behov for at vende tilbage til de fabriksindstillede værdier, kan det ske således:
- Afbryd forsyningsspændingen til regulatoren
- Hold den øverste og nederste knap inde samtidig med at du igen tilslutter forsyningsspændingen.
Visning af fejlkode Visning af alarmkode Visning af statuskode
E1 Fejl i regulator A 1 Høj-temperatur alarm S0 Der reguleres E6 Batteriet skal skiftes + kontroller ur A 2 Lav-temperatur alarm S1 Venter på at den koordinerede afrimning
E 27 S5 føler fejl A 4 Dør-alarm S2 ON-tid Kompressor E 29 Sair føler fejl A 5 Max. Hold time S3 OFF-tid kompressor
A 15 DI 1 alarm S4 Afdrypningstid A 45 Standby mode S10 Køling stoppet af hovedafbryder A 59 Møbelrengøring S11 Køling stoppet af termostat A 61 Kondensator alarm S14 Afrimningssekvens. Afrimer
afsluttes
S15 Afrimningssekvens. Ventilatorforsinkelse S16 Køling stoppet pga. åben DI indgang S17 Dør åben (åben DI indgang) S20 Nødkøling S25 Manuel regulering af udgange S29 Møbelrengøring S32 Forsinkelse af udgange ved opstart non Temperaturen kan ikke vises. Føleren er ikke
monteret
-d- Afrimningen er igang / Første nedkøling efter afrimning
PS Password er påkrævet. Indstil password
4 Instructions RI8PK153 © Danfoss 08/2011 EKC 302A, B