Danfoss EFET 535 Installation Manual

INT
INT
EFET 535
Installation Manual
Danfoss Heating
This manual is only to be used by a
Warning!
professional installer to install and
set up the thermostat properly.
It is not intended for the end-user!
2
Congratulations with…
... your Danfoss floor heating system Your property has been installed with a Danfoss electric floor heating system. Danfoss is Europe’s leading floor heating manufacturer, with over 45 years experience. We are confi­dent that you will be satisfied with your new system.
Danfoss brings you…
An Invisible heating solution - A concealed heat source opens up greater opportunities for decorating and furnishing. Optimum comfort - Danfoss brings you the luxury and comfort of a warm floor as well as a pleasant room tempera­ture. Floor heating is the most comfortable type of heating because it is based on the fact that warmth travels upwards; pleasant warmth for your feet, body and head.
Low running costs – Thanks to the precise Danfoss thermo­stat and the placement of the heating elements right under the floor surface the heat can be controlled optimally in order for you to have the comfort you desire with minimal energy use. Moreover electric floor heating is practically maintenance free, in total keeping down the running costs.
A long lasting solution - We back-up our floor heating solu­tions with a ten year guarantee on all our mats and cables, and a two year warranty on our thermostats. Practically speaking you can count on Danfoss heating cables and mats lasting as long as the house in which they are installed – and that is without having to maintain them.
Hygiene - As Danfoss produce floor heating systems, only very gentle air is circulating, and the amount of travelling dust particles is reduced considerably; a great relief for people with allergies or asthma. There are also no dangerous fumes such as carbon monoxide generated by the system.
INT
3
Table of content
Table of content
Install & configure the thermostat . . . . . . . . . . . . . . . . . . . . . .4
Placement of EFETTM 535 ...........................4
Installation of EFETTM 535 ..........................5
User’s guide to EFETTM 535 . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Introduction .................................... 10
Display, icons and buttons . . . . . . . . . . . . . . . . . . . . . . . 10
Increase / decrease preferred temperature. .......11
Using the timer function ......................... 12
Settings ......................................... 14
Setting the time ..............................16
Setting the weekday.......................... 17
Setting the timer periods ..................... 18
Setting the comfort temperature .............19
Setting the savings temperature .............. 19
Setting the minimum floor temperature limit.. 19
Special features.................................. 20
Childproof mode ............................. 20
Frost protection mode........................ 20
OFF mode.................................... 21
Restore timer default settings................. 21
Switching displayed temperature .............22
Trouble shooting ................................ 23
Technical Specifications ............................. 24
Disposal Instruction.................................. 25
The Danfoss Guarantee .............................. 26
4
Install & configure the thermostat
Placement of EFETTM 535
When EFETTM 535 is used as a room sensor, installation height should typically be between 80-150 cm.
In wet rooms it should be installed on an even surface, according to local building regula­tions.
At least 50 cm away from windows/doors that will be left open occasionally.
Not on a wall where it will be subjected to direct sunlight.
Not on the inner side of a wall facing the outside.
INT
5
Installation and connection
Installation of EFETTM 535
1. To remove the front cover, gently press the release tabs under the bottom of the thermostat with a screwdriver. Then remove the front.
Removing the front cover and pushing the installation button, is not intended to be done by anyone else but a qualified installer!
2. Connect the thermostat according to the connection diagram
Mains
180-250V~
N L
N
Load
Max. Load 15 A
N
L
L NTC
Load
Sensor
NO
CONNECT
The screen of the heating cable must be connected via a terminal strip to the earth wire of the supply cable.
6
Choose sensor combination
3. Choose sensor combination When installing the EFET™ 535 you need to choose the type of heating and thus which sensors should be used. You have three options:
Comfort heating: Constant temperature on the floor in bathrooms and other rooms where a comfortable warm surface is required. Install the Floor sensor and choose only the Floor sensor.
Total heating: Control of room temperature in living rooms etc. Install the Floor sensor and choose both Floor sensor and Room sensor.
No floor sensor: A floor sensor is not present, and cannot be installed. Choose Room sensor. (Not recommended).
Be aware that without a floor sensor, the temperature control can be less accurate, and overheating of the floor is of higher risk.
Danfoss recommends that a floor sensor is always installed.
When the thermostat is used to control a floor heating
element according to EN/IEC 60335-1 and
EN/IEC 60335-2-96, always use the floor sensor
and never set the temperature limit above 35°C.
INT
7
Configuration - sensor
Selection of sensor type Power on the thermostat.
With the front off, with a small screw­driver, pencil, or needle press the installation button.
Select the sensors to be used for the heating system: EFETTM 535 is able to use two sensors:
- a built-in room sensor
- an external sensor to be placed in the floor.
This gives 3 options:
floor sensor. room sensor.
both room and floor sensor.
Always use floor sensor or a room
+ floor sensor combination when
used to control floor heating
The default is To change this setting, press and
use the arrow buttons ▲▼ to select your choice. Press to accept your choice.
If you have selected room sensor only, the installation procedure is complete. Press installation button to accept. (Go to page 9). If you have selected floor sensor or a combination of room- and floor sen-
sor press ▲▼ for the next setting.
8
Configuration - Max. floor temp.
Maximum floor temperature. When selecting either floor sensor or floor and room sensors, next screen is maximum floor temperature.
Default setting is 35°C.
To change this setting, press and use the arrow buttons ▲▼ to select your choice. Press to accept your choice. If you have selected a combination of room and floor sensor, the installa­tion procedure is complete. Press installation button to accept. (Go to page 9) If you have selected floor sensor only press ▲▼ for the next setting.
When the thermostat is used to control a floor heating
element according to EN/IEC 60335-1 and
EN/IEC 60335-2-96, always use the floor sensor
and never set the temperature limit above 35°C.
Notice:
The floor temperature is measured where the sensor is placed. The temperature of the bottom of a wooden floor can be up to 10 degrees higher than the top. Floor manu­factures often specify the max. temperature on the top surface of the floor. Please contact your floor supplier for maximum surface temperature.
INT
9
Configuration - Scale
Scale
If you select EFETTM 535 to only use a floor sensor, mode , you have to select the display type. The choice is either numerical scale 1-6 or Celcius scale 5° to 45°.
Default is Celcius scale. When select­ing Celcius, the display will show the actual temperature at the floor sensor.
To change this setting, press and use the arrow buttons ▲▼ to select your choice.
Press to accept your choice. The installation procedure is now finished.
You can use the ▲▼ for going back or forward through the settings.
Otherwise: Press the installation pinhole to exit installation mode.
4. Put the frame and front back on.
Initially mains supply the thermostat for 15 hours to
fully charge the battery. The current time and day
is then kept for 80 days if mains supply is off.
All other settings are stored permanently.
Loading...
+ 19 hidden pages