Danfoss Eco Data sheet

Data sheet
Actuators for modulating control
AME 130, AME 140, AME 130H, AME 140H
Description
Ordering
AME 130, AME 140
Typ e
AM E 130
AME 14 0 12 082H8045
AM E 130H 24 082H8046
AME 14 0H 12 082H8047
Supplyvoltage Speed
(V AC) (s/mm)
24 082H8044
24
Code No.
AME 130, AME 140, AME 130H and AME 140H actuators are used with:
• VZL DN 15, 20 with stem extension plug or
• AHQM (DN 15-32) valves.
The actuator can be used with fan coil units, induction units, small reheaters, recoolers, and zone applications in which hot/cold water is the controlled medium.
Main data:
• Modulating control
• Force switch-off at stem down position prevents overload of actuator and valve.
• No tools required for mounting
• Maintenance free during lifetime
• Low noise operation
• Self-positioning process
• Supplied with 1.5 m cable
Spare parts
Typ e Code No.
Cable (5 m) 082H8052
Technical data
© Danfoss | 2017.03
Typ e AME 130, AME 130H AME 140, AME 140H
Power supply V 24 AC; +10 to –15%
Power consumption VA 1.3
Frequency Hz 50/60
Control Input Y
Closing force N 200
Max. stroke mm 5.5
Speed s/mm 24 12
Max. medium temperature inside the pipe
Ambient temperature 0 … 55
Storage and transport temperature –40 … 70
Ambient humidity 95 % r.h., non-condensing
Protection Class III safet y extra-low voltage
Grade of enclosure IP 42
Weight kg 0.3
- marking in accordance with standards
V
mA
°C
Low Voltage Directive (LVD) 2014/35/EU: EN 60730-1, EN 60730-2-14 Electromagnetic Compatibility Directive (EMC) 2014/30/EU: EN 61000-6-2, EN 61000-6-3
0-10 (2-10) [Ri = 200 k Ω]
0-20 (4-20) [Ri = 500Ω]
130
VD.KG.Z4.02 | 1
Data sheet AME 130, AME 140, AME 130H, AME 140H
Installation
Disposal The actuator must be dismantled and the
elements sorted into various material groups before disposal.
Wiring
Mechanical
The actuator should be mounted with the valve stem in either horizontal position or pointing upwards.
The actuator is fixed to the valve body by means of a mounting ring which requires no tools for mounting. The ring should be tightened by hand.
Electrical
Important: It is strongly recommended that the mechanical installation is completed before the electrical installation.
Each actuator is supplied with the connecting cable for the controller.
Commissioning
Installation procedure
The factory setting of the spindle is the fully stem up position because of easier mechanical connection of the actuator on the valve.
1 Check the valve’s neck. The actuator should
be in steam up position (factory setting). Ensure that the actuator is mounted securely on valve body.
2 Energise the actuator according to the wiring
diagram 2.
3 The direction of stem movement can be
observed on the positon indicator.
position indicator
2 | VD.KG.Z4.02
© Danfoss | 2017.03
Data sheet AME 130, AME 140, AME 130H, AME 140H
DIP Switch Setting (for service purposes only)
The actuator has a function selection DIP switch under the removable cover.
The switch provides the following functions:
• SW1: Reset
Changing this switch position will cause the
actuator to go through a self stroking cycle.
• SW2: 0/2 - Input signal range selector
If set to OFF position, the input signal is in
the range from 2 -10 V (voltage input) or from 4-20 mA (current input). If set to ON position, the input signal is in the range from 0-10 V (voltage input) or from 0-20 mA (current input).
• SW3: D/I - Direct or inverse acting selector
If set to OFF position, the actuator is direct
acting (stem lowers as voltage increases). If the actuator is set to ON position, the actuator is inverse acting (stem raises as voltage increases).
• SW4:
---/Seq - Normal or sequential mode selector:
If set to OFF position, the actuator is working
in range 0(2)-10V or 0(4)-20mA. If set to ON position, the actuator is working in sequential range; 0(2)-5 (6)V or (0(4)-10 (12)mA) or (5(6)-10V) or (10(12)-20mA).
• SW5:
0 … 5 V/5 … 10 V - Input signal range in sequential mode:
If set to OFF position, the actuator is working
in sequential range 0(2)-5 (6)V or 0(4)-10 (12) mA.
If set to ON position, the actuator is working in sequential range; 5(6) -10V or 10(12)-20mA.
• SW6: U/I - Input signal type selector
If set to OFF position, voltage input is
selected. If set to ON position, current input is selected.
Manual override (for service purposes only)
Caution: Do not manually operate the drive under power!
AME 130, AME 140
1 Remove the cover.
2 Insert the Allen key 6 into the spindle.
3 Press and hold the button (on the bottom side
of the actuator) during manual override.
4 Pull out the tool.
5 Place cover back on the actuator.
Remark:
A ”click” sound after energizing the actuator means that the gear wheel has jumped into normal position.
If manual override has been used, then Y signal is not correct until the actuator reaches it’s end position. If this is not accepted, reset the actuator.
➋➌
Allen key 6mm
push
© Danfoss | 2017.03
VD.KG.Z4.02 | 3
Danf already on order pro All trademarks in this material are property of the respec
Data sheet AME 130, AME 140, AME 130H, AME 140H
Manual override (continuous)
Actuator - valve combinations
AME 130H, AME 140H
1 Press and hold the button (on the bottom side
of the actuator) during manual override.
Remark:
A ”click” sound after energizing the actuator means that the gear wheel has jumped into normal position.
Remark: VZL valves with stem e xtension plug
Dimensions
AME 130(H)/140(H)
+ VZ 2 / VZL 2
88
AME 130, AME 140
AME 130(H)/140(H)
+ VZ 3 / VZL 3
5092
74
AME 130(H)/140(H)
+ VZ 4 / VZL 4
94
AME 130H, AME 140H
AME 130(H)/140(H)
+ AHQM (DN 15-32)
92
74
50
oss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
vided that such alterations can be made without subsequential changes being necessary eady agreed.
4 | VD.KG.Z4.02
tive companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
© Danfoss | DHS-SRMT/SI | 2017.03
Loading...