Installation guide ECL Portal – 5-step instructions
The ECL Comfort 296 / 310 must be connected to the Internet via an Ethernet cable to Internet gateway.
Go to <Common controller settingsSystem→ Ethernet> menu in the ECL Comfort 296 / 310. Configure its network settings to use DHCP IP address type instead of Static.

Activate the ECL Portal in ECL 296 / 310

The ECL Portal feature is activated in the ECL Comfort 296 / 310 menu <SystemPortal config.>.
You will need the serial number and access code to be able to register it to your user account. This information is found in the <SystemPortal info> menu.

Create your user account

Create your personal user account on the ECL Portal website:
http://ecl.portal.danfoss.com
Click the <New user> button and follow the instructions.

Register the ECL 296 / 310

Register the ECL Comfort 296 / 310 to your user account via the <ECLRegister new ECL> menu.
The serial number and access code of the ECL Comfort 296 / 310 is needed. (See step 2).

Remote control and monitor it

You are now ready to remote control and monitor the heating installation.
Settings of the ECL Comfort 296 / 310 can be changed, temperatures and energy consumption can be monitored and you can be alarmed via e-mail.
______________________________________________________________________________
© Danfoss | 2018.08 VI.HX.G2.02 | 1
Installation guide, ECL Portal – 5-step instructions
_______________________________________________________________________________
*087H9183* *VIHXG202*
______________________________________________________________________________
© Danfoss | 2018.08 VI.HX.G2.02 | 2
Loading...