Danfoss ECiceguard 18 Data sheet

Danfoss ECiceguard 18 Data sheet

Data Sheet

YEAR

WARRANTY Product

Product specifications

ECiceguard 18 Ready-made

The ECiceguard is readymade self-limiting parallel heating cable that is used for ice and snow melting on roofs, in gutters and downpipes (UV-resistant).

ECiceguard heating cables should not be in direct contact with bitumen.

The self-limiting capability of the cable ensures that the output of the cable increase or decrease according to ambient temperature.

The heating cable is flexible and easy to install as it can be cut to length at site and installed directly on to the roof and gutter system.

All self-limiting heating cables must be over-temperature protected by a thermostat, as the output will decrease, but never be zero, and be protected by a RCD with a maximum trip current of 30 mA.

Benefits

Nominal voltage

230 V AC

 

• Easy to install

Nominal output

18 W/m @ 10 °C

 

• Cut to length on site

 

 

 

Output tolerance (min-max)

19 - 25 W/m @ 10 °C

 

• Ready-made lengths

 

 

 

Maximum permissible use temperature

65 °C, powered

 

 

 

 

85 °C, unpowered

Approvals:

Minimum installation temperature

-5 °C

 

 

 

Cable dimensions

13,2 X 6,1 ± 0,3 mm

 

 

 

 

 

 

 

 

Outer sheath

Black UV protected, TPE

 

 

 

 

 

 

 

 

Minimum braid coverage

70%

 

 

 

 

 

 

 

 

Standard compliance:

Maximum resistance protective braid

10 Ω/Km

 

 

Cold lead

5 m DTCL, 3G 1,5mm²

 

• SS 4242411

 

 

 

Bending Ø, min.

64 mm (Ø to the inside of the cable)

 

 

 

 

 

 

 

 

 

 

 

IP Class

IPX7

 

 

 

 

 

Types: ECiceguard 18 Ready-made

Item no.

Cable length

Nominal output @ 10 °C

Cold lead

EAN no.

 

 

 

 

 

088L6575

2 m

36 W

5 m

5703466247020

 

 

 

 

 

088L6576

4 m

72 W

5 m

5703466247037

 

 

 

 

 

088L6577

6 m

108 W

5 m

5703466247044

 

 

 

 

 

088L6578

8 m

144 W

5 m

5703466247051

 

 

 

 

 

088L6579

10 m

180 W

5 m

5703466247068

 

 

 

 

 

088L6580

15 m

270 W

5 m

5703466247075

 

 

 

 

 

088L6581

23 m

414 W

5 m

5703466247082

 

 

 

 

 

088L6582

30 m

540 W

5 m

5703466247099

 

 

 

 

 

088L6583

50 m

900 W

5 m

5703466247105

 

 

 

 

 

Construction

Over jacket

 

 

 

Nickel plated copper bus wires

Screen

Radiation Cross-Linked Semiconductive Heating Matrix

Radiation Cross-Linked Primary Dielectric Insulation

 

Insulation

Tinned copper braid

 

Polyolefin over jacket

 

Self limiting heating element

 

Bus wires, 1,25 mm²

Electrical heating · ©Danfoss

AI281660310070en-010106

Maximum heating circuit length on a pipe, with circuit breaker with C-characteristic*

Switch on

Power W/m

 

 

ECiceguard 18

 

 

temperature

10 A

16 A

20 A

25 A

32 A

 

10 °C

20

55

88

110

135

135

0 °C ice water

36

40

64

80

100

105

-10

°C

42

36

58

72

90

100

-20

°C

48

33

52

65

81

100

-30

°C

54

29

46

57

71

90

-40

°C

61

25

40

50

62

80

* Maximum length in ice water or for roof applications is 2 times lower.

Power output characteristic

Output of heating cable installed and measured on a pipe.

 

 

 

W/m

 

 

 

 

 

 

 

40

 

 

 

 

 

 

 

35

 

ECiceguard 18 Ready-made

 

 

 

 

 

DEVIiceguard™ 18 (G) Ready-made

 

 

 

 

30

 

 

 

 

 

 

 

25

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

0

 

 

 

 

-60

-40

-20

0

20

40

60

80

Pipe temperature (°C)

Electrical heating · ©Danfoss

AI281660310070en-010106

Loading...