Danfoss ECflex Operating guide

MAKING MODERN LIVING POSSIBLE
Installation Guide
ECflex Heating Applications
EFSIC EFTPC
www.EH.danfoss.com
Danfoss A/S is not liable or bound by warranty if these instructions are not adhered to during installation or service.
The English language is used for the original instructions. Other languages are a translation of the original instructions. (Directive 2006/42/EC)
© 2012 Copyright Danfoss A/S
Installation Guide ECflex Heating Applications

Table of Contents

1 Introduction ............................................. 3
1.1 Safety Instructions ...................................... 5
1.2 Installation Guidelines .................................... 7
1.3 System Overview ....................................... 8
1.4 Functional Overview ..................................... 8
2 Installation Step by Step ...................................... 9
2.1 Fastening Methods ...................................... 9
2.2 Calculating C-C Distance ................................... 10
2.3 Planning the Installation ................................... 11
2.4 Preparing the Installation Area ............................... 11
3 Installing Elements ......................................... 11
3.1 Installing Heating Elements ................................. 12
4 Indoor Applications ........................................ 13
4.1 Floor Heating in Thin Beddings ............................... 14
4.2 Floor Heating in Joist Floor Constructions ......................... 15
4.3 Floor Heating with EFCI DRY ................................ 16
4.4 Floor Heating in Concrete Floors .............................. 17
5 Outdoor Applications ....................................... 19
5.1 Snow Melting on Ground Areas ............................... 20
5.2 Frost Protection of Pipes ................................... 21
6 Finalizing the Installation ..................................... 23
7 Optional Settings .......................................... 24
7.1 Floor Temperature Settings ................................. 24

1 Introduction

In this installation manual, the word “element” refers to heating cables.
For other applications please contact your local sales office.
The intended uses of the heating elements covered by this installation manual are shown in the follow­ing.
Danfoss Heating Solutions VIAMJ202
3
Installation Guide ECflex Heating Applications
Floor heating in thin beddings (<3 cm)
- see section 4.1.
Floor heating with EFCI DRY
- see section 4.3.
Floor heating in joist floor constructions
- see section 4.2.
Floor Heating in Concrete Floors (>3 cm)
- see section 4.4.
Snow and ice melting on ground areas
- see section 5.1.
4
Frost protection of pipe systems
- see section 5.2.
VIAMJ202 Danfoss Heating Solutions
Installation Guide ECflex Heating Applications

1.1 Safety Instructions

Elements must always be connected by an author­ised electrician using a fixed connection.
De-energize all power circuits before installation
and service. The connection to the power source must not
be directly accessible to the end user. Each heating cable screen must be earthed in
accordance with local electricity regulations and connected to a residual current device (RCD).
Recommended RCD trip rating is 30 mA, but
Never cut or shorten the heating element
Cutting the heating element will void the war-
ranty. Cold leads can be cut or shortened to suit re-
quirements, only.
may be up to 300 mA where capacitive leakage may lead to nuisance tripping.
Heating elements must be connected via a
switch providing all pole disconnection. The element must be equipped with a correctly
sized fuse or circuit breaker, e.g. 10/13 A for a
1.5 mm2 cold lead and 16/20 A for a 2.5 mm cold lead.
2
Elements must always be installed according to lo­cal building regulations and wiring rules as well as the guidelines in this installation manual
Any other installation may hamper element
functionality or constitute a safety risk, and will void the warranty.
Make sure that elements, cold leads, connection
boxes, and other electrical components do not come into contact with chemicals or flammable materials during or after installation.
Danfoss Heating Solutions VIAMJ202
5
Installation Guide ECflex Heating Applications
The presence of a heating element must
be made evident by affixing caution signs or
markings at the power connection fittings and/or frequently along the circuit line where clearly visible.
be stated in any electrical documentation fol-
lowing installation.
Never exceed the maximum heat density (W/m2) for the actual application.
1. Heating cable
2. Thermostat
3. Sensor
4. Screen
5. RCD
6. All-pole switch
7. Fuse
Connections
Phase - Black
Neutral - Blue
Earth - Screen
6
VIAMJ202 Danfoss Heating Solutions
Installation Guide ECflex Heating Applications

1.2 Installation Guidelines

Caution! Do not use M1 classified elements in
areas subject to high mechanical loads or im­pact. See section 1.3 for classification.
The product does not contain harmful substan-
ces.
Prepare the installation site properly by remov­ing sharp objects, dirt, etc.
Elements may not touch or cross themselves or other elements and must be evenly distributed on
Regularly measure ohmic resistance and insulation resistance before and during installation.
The elements and espe­cially the connection must be protected from stress and strain.
areas.
Store in a dry, warm place at temperatures be-
tween +5 °C to +30 °C.
Do not lay heating ele­ments under walls and fixed obstacles. Min. 6 cm air is required.
The element should be temperature controlled and not operate at ambi­ent temperature higher than 10°C in outdoor ap-
Keep elements clear of in­sulation material, other heating sources and ex­pansion joints.
A floor sensor is recom­mended in all floor heat­ing applications and mandatory under wood­en floors.
plications.
Danfoss Heating Solutions VIAMJ202
7
Installation Guide ECflex Heating Applications

1.3 System Overview

ECflex EFSIC EFTPC Mechanical Class (IEC 60800) M2 C (IEC60800: 1992) Floor heating in thin beddings (<3 cm) D D Floor heating in joist floor constructions - P Floor heating with EFCI DRY - P Floor heating in concrete floors (>3 cm) D P Snow and ice melting on ground areas D A Frost protection of pipe systems A P
M2, C For use in applications with higher risk of
mechanical damage.
P Primary recommendation for this applica-
tion.

1.4 Functional Overview

D Designed and approved for this application. A Applicable but there are better options.
- Not applicable! Do not use!
1. Element
2. C-C distance
3. Cold lead connection
4. Cold lead
5. Connection box (if any)
6. Sensor
7. Thermostat
8
VIAMJ202 Danfoss Heating Solutions
Installation Guide ECflex Heating Applications

2 Installation Step by Step

2.1 Fastening Methods

Danfoss TWISTCLIP
For use on reinforcement mesh.
EFCI Fast
For keeping exact C-C distance (2.5 cm steps) on even surfaces.
Cable ties
For use on reinforcement mesh. Do NOT fix the loop. The cable must be able to move.
Danfoss CLIP CC
For keeping exact C-C distance (1 cm steps) on even surfaces, UV resistant.
Tape or hotmelt glue
For fixing elements to hard, dry, even surfaces.
Danfoss Aluminium Tape
For ensuring efficient heat transfer.
Danfoss Heating Solutions VIAMJ202
9
Installation Guide ECflex Heating Applications

2.2 Calculating C-C Distance

For areas on roofs, grounds and fields, the C-C dis­tance is the distance in centimetres from the centre of one cable to the centre of the next.
C - C[cm] =
Area [m2]
Cable length [m]
For heating of pipes, refer to the number of cables per metre - see section 5.2.
or C - C[cm] = Cable output [W/m] x 100 cm
Heat density [W/m2]
Max. C-C distance Thin beddings (<3 cm) 10 cm Joist floor constructions 20 cm DEVIcellTM Dry Concrete floors (>3 cm) 15 cm Ground areas 15 cm
W/m² @ 220V/380V
C-C [cm] 6 W/m 10 W/m 15 W/m 17 W/m 18 W/m 20 W/m
5 110 183 274 311 - -
7,5 73 122 183 207 220 244
10 55 91 137 156 165 183
12,5 44 73 110 124 132 146
15 37 61 91 104 110 122
W/m² @ 230V/400V
C-C [cm] 6 W/m 10 W/m 15 W/m 17 W/m 18 W/m 20 W/m
5 120 200 300 340 - -
7,5 80 133 200 227 240 267
10 60 100 150 170 180 200
12,5 48 80 120 136 144 160
15 40 67 100 113 120 133
x 100 cm
20 cm
W/m² @ 240V/415V
C-C [cm] 6 W/m 10 W/m 15 W/m 17 W/m 18 W/m 20 W/m
5 131 218 327 370 - -
7,5 87 145 218 247 261 290
10 65 109 163 185 196 218
12,5 52 87 131 148 157 174
15 44 73 109 123 131 145
10
VIAMJ202 Danfoss Heating Solutions
Installation Guide ECflex Heating Applications

2.3 Planning the Installation

Draw a sketch of the installation which shows
element layout
cold leads and connections
junction box/cable well (if applicable)
sensor
connection box
thermostat
Save the sketch
Knowing the exact location of these compo-
nents makes subsequent troubleshooting and repair of faulty elements easier.

2.4 Preparing the Installation Area

Bear in mind the following:
Observe all guidelines in section 1.1 .
Observe correct C-C distance (heating cables
only) - see section 2.2. Observe required installation depth and possi-
ble mechanical protection of cold leads. When installing more than one element, never
wire elements in series but route all cold leads in parallel to the connection box.
Two or more elements may be installed in
the same room but a single element is not to be installed across two or more rooms.
All heating elements in the same room
must have the same heat density (W/m2) unless they are connected to separate floor sensors and thermostats.
For single conductor cables, both cold leads
must be connected to the connection box.
Remove all traces of old installations, if applica-
ble. Ensure that the installation surface is even, sta-
ble, smooth, dry and clean.
If necessary, fill out gaps around pipes,
drains, or walls or apply foil covering
There must be no sharp edges, leaves, dirt or
foreign objects.

3 Installing Elements

It is not recommended to install elements at tempera­tures below -5 °C.
At low temperatures, heating cables can become rig­id. After rolling out the element, briefly connect it to the mains supply to soften the cable before fastening.
Danfoss Heating Solutions VIAMJ202
Measuring Resistance
Measure, verify and record element resistance during installation.
After unpacking
After fastening the elements
After the installation in finalized
11
Installation Guide
If ohmic resistance and insulation resistance are not as labelled, the element must be replaced.
The ohmic resistance must be within -5 to +10
% of the value labelled. The insulation resistance should read >20 MΩ at
min. 500 V, preferably 2.5 kV.

3.1 Installing Heating Elements

ECflex Heating Applications
Observe all instructions and guidelines in section 1.1 and 1.2.
Heating Cables
Position the heating element so that is at least
half the C-C distance from obstacles. Elements must always be in good contact with
the heat distributor (roof, sand, soil, concrete, pipe, etc.) - see section 4 and 5 for details.
Observe correct C-C distance - see section 2.2.
Position the heating cable so that it is at least
half the C-C distance from obstacles. Heating cable bending diameter must be at
least 6 times cable diameter. Heating cables have meter markings to aid you
during installation The actual cable length may vary +/- 2 %.
Extending cold leads
Avoid extending cold leads if possible. Wire cold
leads to e.g. junction boxes or cable wells. Max. 5 % loss of potential power in the whole
length of the cold cable. Extra length of cold lead will increase capacitive
leakage current which means that RCD trip rat­ing may need to be higher.
Sensors
Sensors are live (230 V) components and must
be wired inside plastic conduit Sensors can be extended using installation ca-
ble. See section 4 for specific applications.
Floor sensors (indoor applications only)
Mandatory under wooden floors or in wooden
sub floors. Shall be placed in an appropriate place.
Where not exposed to sunlight or draft
from door openings In between >2 cm from two heating ca-
bles The conduit should be flush with the floor
surface.
It may be necessary to countersink
the conduit to achieve this.
Route the conduit to the connection box.
12
VIAMJ202 Danfoss Heating Solutions
Installation Guide ECflex Heating Applications

4 Indoor Applications

Sub floor Thin beddings* (<3
cm)
Wood Concrete
Joist floor construc-
tions
Max. 10 W/m and 100 W/m Max. 20 W/m and 225 W/m
EFCI DRY Concrete floors (>3
2
2
Floor type Wood, par-
Max. 100 W/m
2
Max. 80 W/m
2
Max. 100 W/m
2
Max. 150 W/m quet, lami­nate
Carpet, vinyl,
Max. 100 W/m
2
- -
Max. 150 W/m linoleum, etc.
Tiled floors in
bath-
100 - 200 W/m
2
- -
100 - 200 W/m
rooms, conser-
vatories, cellars,
etc.
Tiled floors in
kitchens,
living
100 - 150 W/m
2
- -
100 - 150 W/m
rooms, halls,
etc.
* May be up to 225 W/m2 in rim zones e.g. under large windows
On concrete sub floors and under tiles, only
If connected to a separate floor sensor and ther-
mostat
cm)
2
2
2
2
Danfoss Heating Solutions VIAMJ202
13
Installation Guide ECflex Heating Applications
Wooden floor coverings
Wood shrinks and swells naturally depending on the relative humidity (RH) in the room. The optimal range is 30-60% RH.
Avoid beech and maple in multilayered floor
coverings unless press dried. Install a vapour barrier for sub floors <95% RH
and a damp proof membrane >95%.

4.1 Floor Heating in Thin Beddings

New tiles floor in wet rooms
New floor covering in dry rooms
Ensure 100% contact between element and
floor materials above (no air pockets). Install the heating system in the whole floor
area at 15°C surface temperature. Always install a floor sensor to limit the floor
temperature. See section 7.1 for further informa­tion.
1. New tiles
2. Tile adhesive
3. Damp proof membrane (in wet rooms)
4. Self-levelling compound
5. ECflex heating cable
6. Primer
7. Existing tiles or concrete floor
1. New tiles, wooden floor, laminate, or carpet
2. Vapour barrier and noise absorption mat (wooden floor / laminate)
3. Latex based compound/tile adhesive
4. ECflex heating cable
5. Primer
6. Existing concrete or wooden floor
Wooden sub floors must be properly anchored
Apply floor plaster before laying the heating el-
ement if necessary.
Additional insulation (tile backer boards)
Can be applied between existing sub floor and
heating element.
Polystyrene (XPS) with high compressive
strength >300 kN/m2. Concrete or foil faced without cracks.
Must be installed as prescribed by the manufac-
turer. Floor sensor must be installed above insulation.
Output max. 10 W/m and 150 W/m2.
Damp proof membrane
Apply in wet rooms above the heating cables.
Apply only if not already installed in existing
floor.
14
VIAMJ202 Danfoss Heating Solutions
Tile adhesive or self-levelling compound
Prime the sub floor as specified by the supplier.
The heating element should be securely fas-
tened before applying. The heating element must be fully embedded
and at least 5 mm.
Required tools
Hammer.
Chisel.
Glue gun.
Installation Guide ECflex Heating Applications
Cut out a wall groove and fix cable ducts and connection box. Chisel off a groove for the sensor conduit and cold cable. Fix the sensor con-
Roll out the cable and attach it to the sub floor by means of Danfoss CLIP fastening accessories or simi­lar.
duit e.g. with a glue gun.

4.2 Floor Heating in Joist Floor Constructions

The sub floor construction must be well insulated
Insulate thermal bridges and close vents, e.g.
between the floor construction and walls/roofs.
The heating cables may not touch the insulation or woodwork
The distance between the heating cable and the
planks and joists should be at least 30 mm. The optimal distance between the heating ca-
bles and the floor covering is 3-5 cm. The heating cable must be fastened to the wire/
foil at 30 cm intervals.
Apply flexible self-levelling com­pound, damp proof membrane, and/or tile adhesive, depending on the floor finish.
1. Wooden floor covering.
2. Floor joists.
3. ECflex Heating Cable .
4. Chicken wire and/or aluminium foil.
5. Insulation.
6. Sub floor construction.
Heating cables may cross a joist
Through a 50 mm recess lined with aluminium
tape Make sure the cable is never in contact with the
joist Only one cable in each recess
Required tools
Compass saw.
Aluminium tape.
Danfoss TWISTCLIP or similar.
Danfoss Heating Solutions VIAMJ202
15
Installation Guide ECflex Heating Applications
Apply chicken wire or similar onto the insulation.
Cut a 50 mm recess and cover with aluminium tape where cables cross a joist.

4.3 Floor Heating with EFCI DRY

Attach the cable and sensor proper­ly with Danfoss TWISTCLIP , cable ties, or heat resistant tape.
1. Timber / parquet /laminate.
2. Noise absorption mat / rag felt.
3. ECflex EFTPC .
4. EFCI DRY .
5. Damp proof membrane.
6. Existing floor construction (e.g. concrete, gyp­sum, polystyrene)
1. Linoleum / vinyl, carpet.
2. Pressure distribution board (e.g. plywood).
3. Noise absorption mat / rag felt.
4. ECflex EFTPC .
5. EFCI DRY .
6. Damp proof membrane.
7. Existing wooden floor construction.
Installation under carpets, linoleum or vinyl
Must be separated from cables by at least 5 mm
of pressure distribution board. Observe the insulation value above the pressure
distribution board.
R < 0.10 m2K/W corresponding 1 Tog or a thin carpet.
16
Required tools
Compass saw.
File.
Glue gun.
Aluminium tape.
VIAMJ202 Danfoss Heating Solutions
Installation Guide ECflex Heating Applications
Cut out a hole for the warm/cold cable connection and the floor sensor conduit and file any sharp edges. Fix the conduit to the sub floor with glue or screws.
See the installation manual for the EFCI product for further information.

4.4 Floor Heating in Concrete Floors

Heated tiles in bathrooms
New floor in dry rooms
Install the ECflex heating cable. Make sure that the ca­ble, end termination, and warm/cold cable connection are in contact with the aluminium plate or aluminium tape at all times.
1. New tiles.
2. Tile adhesive.
3. Damp proof membrane.
4. Concrete.
5. ECflex heating cable.
6. Mesh reinforcement.
7. XPS insulation.
8. Concrete slab.
1. Wooden floor, laminate or carpet.
2. Noise absorption mat / rag felt (under wood).
3. Vapour barrier.
4. Concrete.
5. ECflex heating cable.
6. Concrete slab or foil.
7. XPS insulation.
8. Sand and soil.
Danfoss Heating Solutions VIAMJ202
17
Installation Guide ECflex Heating Applications
Other combinations of floor covering and existing floor construction are also possible.
The heating cables may not touch the insulation
The heating cable must be separated by mesh
reinforcement, concrete slab or foil.
Embedding in concrete, mortar or screed
The bedding must not contain sharp stones
Must be sufficiently wet, homogeneous, free of
air voids
Apply reinforcement mesh, con­crete slab or foil onto the insula­tion.
Roll out the cable and attach it to the sub floor or mesh reinforcement by means of Danfoss CLIP fastening ac­cessories or similar.
Pour at a moderate delivery speed to
avoid displacement of the element Avoid excessive use of rakes, shovels, vi-
brators, and rollers
The heating element must be fully embedded
and at least 5 mm Allow a drying time of approximately 30 days
for concrete and 7 days for moulding com­pounds.
Pour at a moderate delivery speed to avoid displacement of the element.
18
VIAMJ202 Danfoss Heating Solutions
Installation Guide ECflex Heating Applications

5 Outdoor Applications

Observe following heat densities (W/m2) for the actual application.
Design temperature Snow and ice melting on ground areas Frost protection of pipe systems
[°C] [W/m2] [W/m2]
0 to -5 200 See table below.
-6 to -15 300
-16 to -25 400
-26 to -35 500
Frost protection of pipe systems [W/m]
Δt [K] Insulation [mm] Pipe diameter DN [mm]
15 20 25 32 40 50 65 80 100 125 150 200
10 8 9 11 14 16 19 24 29 36 44 - - 20 5 6 7 8 9 11 14 16 19 24 28 36
20
30
40
30 4 5 5 6 7 8 10 12 14 17 19 25 40 4 4 5 5 6 7 8 9 11 13 15 19 50 3 4 4 5 5 6 7 8 9 11 13 16 10 12 14 17 20 24 29 37 44 - - - - 20 8 9 10 12 14 17 20 24 29 35 42 - 30 6 7 8 9 11 12 15 18 21 25 29 37 40 5 6 7 8 9 10 12 14 17 20 23 29 50 5 6 6 7 8 9 11 12 14 17 19 24 10 15 19 22 27 32 39 49 - - - - - 20 10 12 14 16 19 22 27 32 39 47 - - 30 8 9 11 12 14 17 20 23 28 33 39 50 40 7 8 9 10 12 14 16 19 22 26 31 39 50 6 7 8 9 10 12 14 16 19 22 26 32
Danfoss Heating Solutions VIAMJ202
19
Installation Guide ECflex Heating Applications

5.1 Snow Melting on Ground Areas

Free constructions, e.g. platforms, steps, bridges, and terraces
1. Top layer of concrete slab.
2. ECflex heating cable.
3. Danfoss CLIP fastening accessory or mesh rein­forcement.
4. Underlying free construction.
5. Insulation
Ground areas, e.g. ramps and car parks
1. Top layer of concrete slab or asphalt concrete.
2. Sand bed or concrete.
3. ECflex heating cable.
4. Danfoss CLIP fastening accessory or mesh rein­forcement.
5. Supporting layer of crushed stones/concrete /old asphalt.
6. Insulation (optional, ensure supporting layer is suitable).
7. Soil.
Ground areas, e.g. driveways, walkways, and pavements
20
VIAMJ202 Danfoss Heating Solutions
1. Top layer of pavement blocks or concrete slab
2. Sand bed
3. ECflex heating cable
4. Danfoss CLIP fastening accessory or mesh rein­forcement
5. Supporting layer of crushed stones
6. Insulation (optional, ensure supporting layer is suitable)
7. Soil
Installation Guide ECflex Heating Applications
Ground thermostat is mandatory
In sand bed: mat output from 250 W/m2 and ca­ble output from 25 W/m.
In concrete bed: cable output from 30 W/m with
a heat density > 500 W/m2 (C-C < 6 cm).
Limited power supply
Reduce the area to be heated, e.g. by heating
tire tracks instead of the whole driveway. Divide and prioritise the area into 2 zones by
means of ECtemp 850 . Install less W/m² than recommended. Snow
melting performance will be reduced. Do not in­stall less W/m2 than recommended in areas of drainage, e.g. in front of heated steps.
Do not install cables in sand only
The heating cables must be protected by a hard
top layer. Otherwise contact your local sales office.
Prepare installation surface with Danfoss CLIP fastening accessories and/or mesh reinforcement. Fix con­duit for sensor cable and sensor tube/dummy for ECtemp 850 sensor, if any.
Extend cold leads with shrink tubes, and place connections in a dry place. Seal all penetrations through walls or similar structures. Apply caution tape above cold leads.
Embedding in concrete, mortar or screed
The bedding must not contain sharp stones.
Must be sufficiently wet, homogeneous, free of
air voids:
Pour at a moderate delivery speed to
avoid displacement of the element. Avoid excessive use of rakes, shovels, vi-
brators, and rollers.
The heating element must be fully embedded
and at least 5 mm. Allow a drying time of approximately 30 days
for concrete and 7 days for moulding com­pounds.
After laying blocks or pouring concrete/asphalt, install external sensor(s), and extend sensor ca­ble(s) according to sensor man­ual.

5.2 Frost Protection of Pipes

Pipe tracing
1. Sensor.
2. ECflex heating cable.
3. Insulation.
4. Fitting.
5. Valve.
Danfoss Heating Solutions VIAMJ202
21
Installation Guide ECflex Heating Applications
Subsurface pipe tracing
1. Concrete breeze block (optional) and/or XPS in­sulation (optional).
2. ECflex heating cable.
3. Sand bed.
4. Soil.
5. Sensor (not shown).
The required output [W/m]is found in the table on page 19 and depends on:
λ W/mK Thermal conductivity for insulation ≈
0.04 used in table
Δt K Temp. diff. between media/surround-
ings D mm Outer insulation diameter d mm Outer pipe diameter
Cables wrapped around pipes are at­tached as shown for every 20-30 cm of pipe with aluminium tape. Straight ca­bles must be fitted as shown at 5 or 7
Apply aluminium tape below (mandatory for plastic pipes) and on top of pipe for the whole
length of cable. o’clock. In-pipe cables are fitted direct­ly in the pipe with compression gland.
The number of cables n
Relation between required output and cable
output Number of cables per metre in the length direc-
tion Min. 2 for DN125-200
Integer = straight cables (easier installation)
Decimal = wrapped around pipe
For plastic pipes:
Cable output max. 10 W/m.
Apply aluminium tape below and on top on the
whole length of the cable.
Extend cold leads/terminate ca­bles, and place connections in a dry place. Mount connection box on or close to pipe, and install thermostat next to pipe.
22
VIAMJ202 Danfoss Heating Solutions
Installation Guide ECflex Heating Applications

6 Finalizing the Installation

Connecting cables
Connect all cold leads and the sensor to the connec­tion box.
See the installation manual for the thermostat.
See wiring diagram and other important infor-
mationin section 1.1. Observe that the total Amps do not exceed the
capacity of the thermostat. Otherwise install a contactor.
Final check and documentation
Make sure that the heat distributor (e.g. floor,
pipe) can withstand the heat from the element. This is particularly important if the element is connected to a thermostat that does not allow
configuration of maximum temperature. See section 4 for details.
This is particularly important if the ele-
ment is connected to a thermostat that does not allow configuration of maximum temperature.
Document the following using text, drawings, or
photos:
cable type, spacing, depth, layout, circuit
ID, sensors. location of connections between cold lead
and heating element. location of end caps (twin conductors
only). location of expansion joints, if any.
Complete the warranty form.
Instruct the end-user or the daily supervisor in
the operation and maintenance of the heating system.
Before every period of continuous use, check for
faults in the distribution board, thermostat, and sensors.
Re-check and compare the ohm rating and
insulation resistance.
Danfoss Heating Solutions VIAMJ202
23
Installation Guide ECflex Heating Applications

7 Optional Settings

If the element is connected to a thermostat such as a ECtemp , configure basic settings according to the ta­ble below and as described in the thermostat installa­tion manual.
Thermo-
Floor heating in general Snow and ice melting
stat Max. load
ECtemp
16 A Room temp. 20-22 °C
13x
ECtemp
330/610 ECtemp
16/10 A On < +3 °C On < +5 °C
15A - -
Floor Temp.: see section
7.1
53x
ECtemp
16A - -
550
Danfoss
15A (FT) - -
LINK
ECtemp
2 x 15A - Melting < +3 °C, Standby
850
If applicable, adjust the temperature limit in accord­ance with the manufacturer’s recommendations in order to prevent damage to e.g. the floor or the pipe.

7.1 Floor Temperature Settings

According to ISO 13732-2, the comfortable floor tem­perature depends on the floor covering material.
Concrete floor (tiles) 26 - 28,5°C Soft wood (pine) 22,5 - 28°C Hard wood (oak) 24,5 - 28°C Textiles (rugs, carpets) 21 - 28°C
on ground areas
systems
- -
-
< -3 °C
Frost protection of pipe
For most wooden floor products, the tempera-
ture is usually around 27 °C.
All floor temperature settings must be a few degrees higher to compensate for the heat resistance in the floor covering.
24
VIAMJ202 Danfoss Heating Solutions
Installation Guide ECflex Heating Applications
Thermal resist-
Examples of flooring Details Approximate setting
ance [m2K/W]
0.02 15 mm tile Stone or ceramic 26°C
0.05 8 mm HDF based laminate
0.10 14 mm beech parquet
0.13 22 mm solid oak plank
<0.17 Max. carpet thickness suitable for floor heat-
>800 kg/m
650 - 800 kg/m
>800 kg/m
acc. to EN 1307 34°C
3
3
ing
0.18 22 mm solid fir planks
450 - 650 kg/m
The floor temperature must be increased slowly dur­ing the first week to allow the new floor to settle. This is also recommended at the beginning of a heating season.
for 25°C floor temper-
ature
28°C
3
31°C 32°C
3
35°C
Danfoss Heating Solutions VIAMJ202
25
Installation Guide ECflex Heating Applications
26
VIAMJ202 Danfoss Heating Solutions
Installation Guide ECflex Heating Applications
Danfoss Heating Solutions VIAMJ202
27
Installation Guide ECflex Heating Applications
Danfoss A/S Electric Heating Systems Ulvehavevej 61 7100 Vejle Denmark Phone:+45 7488 8500 Fax: +45 7488 8501 Email: EH@danfoss.com www.EH.danfoss.com
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss Heating Solutions and the Danfoss Heating Solutions logotype are trademarks of Danfoss A/S. All rights reserved.
088L0802 & VIAMJ202 Produced by Danfoss Heating Solutions © 01/2012
Loading...