Stainless steel drinking water storage tanks for storage charging systems ThermoDual®, ThermoClean® -Combi, charging by external heat exchanger.
Technical Data
Surface Treatment Tank completely pickled and passivated
Certificate According internal factory norm and PED – Pressure Equipment Directive (2014/68/EU)
Material Stainless steel, MN 1.4571/1.4404
Maximum permissible operating temperature: 95 °C
Maximum permissible operating pressure: 10 bar
© Danfoss | 2018.04
VD.BO.A7.02 | 1
Data sheet Drinking Water Storage Tanks Stainless Steel
General technical data: Thermal insulation / heat loss data and tilt dimensions
Volume acc.
ErP 812/2014
[l] 105,0 895 1,19 1,66 1,30 2 100 - ­201,0 1625 1,47 2,06 1,39 1 200 200 ­289,0 1790 1,68 2,36 1,58 1 300 300 ­345,0 1755 1,77 2,48 1,84 2 350 350 350 411,0 1800 1,85 2,06 2,05 2 400 400 ­490,0 1800 2,00 2,80 2,36 2 500 500 500 646,0 1875 2,19 3,07 2,70 2 650 650 ­756,0 2085 2,30 3,22 2,89 2 750 750 750 890,0 1950 2,45 3,44 3,18 2 900 900 ­990,0 2095 2,54 3,57 3,36 2 1000 1000 1000
1215,0 2055 2,75 3,86 3,40 2 1250 - ­1415,0 2300 2,94 4,13 3,89 2 1500 - ­1975,0 2635 3,26 4,58 4,31 3 2000 - -
All the heat loss values are valid for dTK = 40K; determined according EN 12897, e.g. room temperature = 20° and tank temperature = 60°C.
Tilt
dimension
[mm]
Limit acc. ErP 814/2014 Data Type of tank
Category B
kWh/24h
Category C
kWh/24h
Real value
kWh/24h
Number of pieces
Shell
SE SES SEK-LK
Type SE 100
1 Domestic water (cold) R ¾“ 2 Domestic water (hot) R ¾“ 3 Circulation (inlet) ISO ¾“ 22 Pocket for sensor
10 × 1,0 mm 23 Drain Rp ½“ 25 Inspection opening
Rp 2“ with plug
1
3, 25
222
D
d
H1
H2
23
85
Type
SE
100 100 810 733 590 450 ¾“ ¾“ ½“ 36 640U4900
Thermal insulation
Volume
Liter
H1
mm
H2
mm
D
mm
d
mm
High-qualit y thermal insulation (CFC-free) made of EPS with laminated fleece for optimum tight on the tank
Connections
3
0
°
Weight
app. kg Code1,2 R 3 Rp 23 Rp
and to avoid convection and chimney effects. Insulation thickness 50/20 = 70mm, thermal conductivity λ = 0,032 / 0,038 W / (m * K), with polystyrene cover, color blue RAL 5000. Completely assembled, fire resistance class B2 according to DIN 4102 T1, with hand hole cover and rosettes for all connections. Floor insulation insert made of 50mm fleece. Thermal insulation with hook strip, completely removable. Energy efficiency class „C“ according to ErP Directive 812 + 814/2013 (Eco-design and Label Regulation).
2 | © Danfoss | 2018.04
VD.BO.A7.02
Data sheet Drinking Water Storage Tanks Stainless Steel
Type SE 200 ... 1000
1 Domestic water (cold) 2 Domestic water (hot) 3 Circulation (inlet)
29
21 Thermometer Rp ½“ 22 Thermostat, STM,
STL, sensor Rp ¾“ 23 Drain Rp ¾“ 25 Inspection 120/180 mm 29 Air-vent Rp ¾“
22 37
2
25**
21
37 Heat exchanger G 1½“ 38 Charging group G 1¼“ 40 Muff for bracket Rp 1“,
* Tolerance: 0 ... +10 mm
** 2´nd inspection hole only
for tanks SE 900 & SE 1000
660
H*
170
100
70*
3
α
40
22
25
22
1, 2338
H5
H2H1*
H3
H4
β
38 23
70(78)
Connections
Type SE
Volume
LiterH mm
H1
mm
H2
mm
H3 mmH4
mm
H5
mmD mmd mm α ß
1,2 Rp3
Rp
200 200 1595 230 1000 700 600 270 650 450 31,6° 75° 1½“ ¾“ 44
300 300 1760 240 1150 850 750 435 700 500 30,8° 75° 1½“ ¾“ 50
350 350 1725 250 1150 840 740 435 750 550 30,1° 75° 1½“ ¾“ 57
400 400 1745 260 1140 830 730 435 800 600 29,4° 65° 1½“ 1“ 62
500 500 1765 270 1140 820 720 435 850 650 28,8° 65° 1½“ 1“ 70
650 650 1830 300 1160 860 760 435 950 750 27,6° 60° 2“ 1“ 100
750 750 2045 300 1390 1090 990 450 950 750 27,6° 60° 2“ 1“ 115
900 900 1900 300 1220 860 760 435 1050 850 26,6° 60° 2“ 1“ 120
1000 1000 2045 300 1400 1090 990 450 1050 850 26,6° 60° 2“ 1“ 135
* Weight without thermal insulation
D
d
45°
1
70
Weight
app. kg* Code
640U4901
640U4902
640U4903
640U4904
640U4905
640U4906
640U4907
640U4908
640U4909
200
Thermal insulation
VD.BO.A7.02
High-qualit y thermal insulation (CFC-free) made of EPS with laminated fleece for optimum tight on the tank and to avoid convection and chimney effects. Insulation thickness 80/20 = 100mm, thermal conducti­vity λ = 0,032 / 0,038 W / (m * K), with polystyrene cover, color blue RAL 5000. Completely assembled, fire resistance class B2 according to DIN 4102 T1, with hand hole cover and rosettes for all connections. Floor insulation insert made of 50mm fleece. Thermal insulation with hook strip, completely removable. Energy efficiency class „C“ according to ErP Directive 812 + 814/2013 (Eco-design and Label Regulation).