Installation guide
ELIMINATOR® Hermetic filter drier
Type DMT
Refrigerant R744 (CO2)
023R9546
Flare / flare o-ring / flare NPT
copper plated solder versions
Connection: All sizes
Maximum working pressure
Refrigerant temperature
CCMT
DMSC
DMSC
GC
CCMT
AKVP
MT
AKVP
LT
PS/MWP: 140 bar/2030 psig
T
: -40 °C / -40 °F
min.
T
: 100 °C / 212 °F
max.
DMT
023R9546
Min. 5% Ag
Keep flames away
from body
Customer best practice will still be needed:
1. Use wet wrap when installing.
5
3
2
1
6
X2
Paint
4
Danfoss
23Z91
2. Braze the joints.
3. Let them cool down.
4. Clean the welding area after the installation (remove remaining flux with a brush).
This is an important operation and needs to be done with great care to remove all remaining flux.
5. Paint / Anti-corrosive needs to cover all open steel parts, areas where the black original paint has been burnt due to brazing and at least
3 cm approx of the copper.
6. Paint the joints twice.
© Danfoss | Climate Solutions | 2019.10 AN142486434962en-000302