Installation guide

ELIMINATOR® Hermetic filter drier

Type DMSC

<![if ! IE]>

<![endif]>023R9523

(CO2 for sub-critical application)

 

PS/MWP: 52 bar / 754 psig

 

Refrigerant R744 (CO2 )

 

Media Temperature range: -30 °C – 17 °C / -22 °F – 63 °F

 

 

 

 

 

 

Pure copper:

Keep flames away

 

Customer best practices will still be

 

Size: 1/4, 3/8, 1/2,

from body

 

needed:

 

6 mm, 8 mm, 12 mm

 

 

• Use wet wrap when installing.

 

Steel:

 

 

Braze the joints

 

 

 

• Let them cool down

 

Size: 1/4, 3/8, 1/2

 

 

• Clean the welding area after the

 

 

 

 

 

installation (remove remaining flux

 

 

 

 

 

with a brush)

 

 

 

 

This is an important operation and

 

 

 

 

 

needs to be done with great care to

 

 

 

 

 

remove all remaining flux.

 

 

 

 

• Paint/Anti-corrosive needs to cover all

 

 

 

 

 

open steel parts, areas where the black

 

 

 

 

 

original paint has been burnt due to

 

 

 

<![if ! IE]>

<![endif]>Danfoss 23Z7016.10

 

brazing and at least 3 cm approx of the

 

 

 

 

copper tube

 

 

 

 

 

 

 

 

 

• Paint the joints twice

 

Flare steel connectors

Applies compatible oil on the steel connector (threads)

 

 

 

<![if ! IE]>

<![endif]>Dan 9G8

 

 

 

 

 

Pure copper extended connectors

 

 

 

 

 

 

When applying the torque wrench to the filter drier fix it so there is no movement.

 

 

Also avoid movement in the tubing when installing.

<![if ! IE]>

<![endif]>023R9523

© Danfoss | Climate Solutions (nb) | 2021.06