11 Technical data ..................................................................17
VMIFI102
3
1 Important information
This appliance can be used by children aged from 8
⚠
years and above and persons with reduced physical,
sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision
or instruction concerning use of the appliance in a
safe way and understand the hazards involved.
Cleaning and user maintenance shall not be made by
children without supervision.
Children should be supervised to ensure that they
⚠
do not play with the appliance.
The installation must only be carried out by an
⚠
authorized installer with reference to applicable
rules and orders and these installation instructions.
This apparatus is not intended for persons (including
⚠
children) with reduced physical, sensory or psychological capacity, or who do not have knowledge or
experience, unless supervised or they have received
instructions on how the apparatus functions from a
safety qualified person.
The heat pump must be located in a frost-free envi-
⚠
ronment!
The floor must be able to support the gross weight
⚠
of the heating installation.
The heating installation must be placed on a stable
⚠
surface.
Before the heat pump is supplied with voltage you
⚠
must ensure that the heating system and coolant
system. incl. the heat pump. are filled and bled of
air otherwise the circulation pumps can be damaged.
If the electrician wishes to test his connections
⚠
before the above is carried out this should only
done when it has been checked that the heat
transfer fluid and coolant pumps have been disconnected.
When filling the coolant system the coolant pump
⚠
must be operating but one must ensure that the
compressor and the heat transfer pump cannot
start. The coolant pump can then be run manually
using a separate switch which is located on the
electrical cabinet.
When filling is complete the coolant pump must be
⚠
put in Auto mode.
The appliance is intended to be used by expert or
⚠
trained users in shops, in light industry and on farms
or commercial use by lay persons
⚠
Only spare parts approved by us may be used in this
appliance.
⚠
The power supply must be disconnected during
service and before changing parts in the appliance.
1 .1Refrigerant
The heat pump’s cooling system (refrigerant circuit) is
filled with R407C or R134a (depending on version) refrigerant.
Work on the refrigerant circuit must only be carried
out by a certified engineer!
Toxicity
In normal use and normal conditions the refrigerant has
low toxicity. However. although the toxicity of the refrigerant is low. it can cause injury (or be highly dangerous) in
abnormal circumstances or where deliberately abused.
The refrigerant vapour is many times heavier than air and
in enclosed spaces. below the level of the door for example. and in the event of leakage. large concentrations can
occur with the risk of suffocation because of lack of oxygen. Spaces in which heavy vapour can collect below the
level of the air must therefore be well ventilated.
Refrigerant exposed to a naked flame creates a poisonous irritating gas. This gas can be detected by
its odour even at concentrations below its permitted
levels. Evacuate the area until it has been sufficiently
ventilated.
Anyone with symptoms of poisoning from the vapour
must immediately move or be moved into the fresh air.
Work on the refrigerant circuit
When repairing the refrigerant circuit. the refrigerant
must not be
destroyed at a special plant. Draining and refilling must
only be carried out using new refrigerant (for the amount
of refrigerant see manufacturer’s plate) through the service valves. All warranties from Danfoss Heat Pump´s AB
are void if. when filling with refrigerant other than R407C
or R134a. it has not been notified in writing that the new
refrigerant is an approved replacement refrigerant
together with other remedies.
Scrapping
When the heat pump is to be scrapped the refrigerant
must be extracted for destruction. The local regulations
for treatment of refrigerant must be followed. See the
relevant Swedish Environmental Protection Agency refrigerant statutes.
released from the heat pump – it must be
1 .2Noise and vibrations
From the sound and vibration point of view it is important
that the pipe mountings in the ceiling and walls are made
with vibration damping fastenings and that the holes for
lead-ins in the walls are made as large as possible so that
sound and vibration do not spread.
If the house has poor acoustics. special care must be
taken so that the vibrations do not spread into the building.
In such cases no mountings may be made in the house
near the heat pump. All mountings must be in free standing constructions. which themselves are in vibration
damping material such as Solodyn.
In those cases where the coolant side must be mounted
to the building. flexible hoses should be used. although
not the same type as the heat transfer pipes. Flexible
hoses for the heat transfer and hot gas must be
long (600 mm or longer) and connected at 90°. If one
suspects that the floor on which the heat pump is located
may transfer vibration to the rest of the building. the heat
pump must be positioned on Solodyn pads. These pads
must be weight adapted. Always consult the representative from Danfoss Heat pump´s AB in these cases.
extra
VMIFI102
5
6
1.3 Electrical connection
The electrical installation must only be carried out by
⚠
an authorized electrician (and must follow applicable
local and national regulations). The electrical installation must be carried out using permanently routed
cables. It must be possible to isolate the power supply using an all-pole circuit breaker for the intended
current. For information regarding maximum load
for externally connected devices, see electrical installation instructions.
NOTE! The supplied language specific decal for electrical
connection must be adhered to the inside of the door
Electrical current!
The terminal blocks are live and can be highly dan-
⚠
gerous due to the risk of electric shock. The power
supply must be isolated before electrical installation
is started. The heat pump is internally connected at
the factory.
Important information
24 VAC 1 must not be connected together with:
⚠
• 24 VAC 2
• 24 VDC
• Other equipment that uses 0-10V control signal
• Signal ground GND
24 VAC 2 must only be used as power supply to:
⚠
• External equipment that requires 0-10V control
signal
• Auxiliary modules
The two separate 24 VAC circuits must never be con-
⚠
nected to each other or to protective ground.
The total power load on 24 VAC 1 respectively 24
⚠
VAC 2 must not exceed 50VA.
VMIFI102
7
VMIFI102
2 Heat pump information
21 Low pressure transmitter
2.1
1 Coolant out (from HP)
2 Heat return (return line)
3 Return line hot-gas exchanger
4 Supply line hot-gas exchanger
5 Heat supply (supply line)
6 Coolant in (to HP)
7 Lead-in for communication cable
8 Lead-in for incoming supply and sensor
9 Supply pipe sensor
10 Condenser with draining for prim. side.
When installing in confined spaces, pipe routing on the
rear of the heat pump can be facilitated by connecting the
pipes before the pump is put in position. See the figure
below for an example on how the pipes can be routed.
NOTE! Remember not to tighten the pipes in the
⚠
heat pump’s panel casing as this transfers vibrations
causing noise problems.
1. Coolant out (from HP)
2. Heat return (return line)
3. Return line hot-gas
exchanger
4. Supply line hot-gas
exchanger
5. Heat supply (supply line)
6. Coolant in (to HP)
300 mm
300 mm
50 mm
500 mm
600 mm
690 mm
600 mm
1490 mm (with
support legs at
highest level)
The figure above shows dimensions for one (1) installed
heat pump and the necessary service space.
Required service space when installing several heat
pumps in a row.
500 mm
2.3 Required service space
To facilitate installation and later tests and maintenance
there must be sufficient free space around the heat pump
according to the following dimensions:
When installing several heat pumps, the dimensions
behind the heat pumps may need to be increased if there
is not enough side space. The pumps must be set-up so
that the installation can be accessed from behind.
150 mm
500 mm
150 mm
150 mm
300 mm
VMIFI102
9
VMIFI102
3 Drilling holes for brine pipes
5
5
5
5
1
2
4 Unpacking and installation
• Make holes in the walls for the entry pipes (1) for the
coolant pipes. Follow the dimensions and connection
diagrams on pages 7-8.
• The output and input coolant pipes must have wall lead-ins.
• If there is a risk of infiltration by ground water, special
lead-ins must be used.
• Install the entry pipes (1) so that they incline slightly
wards. The incline should be at least 1 cm per 30 cm.
down-
Cut them at an angle (as illustrated) so that rain water
cannot get into the pipes.
• Ensure that the entry pipes are at the correct distance so
that there is room for the other installations.
• Insert the brine pipes (2) into the insert pipes in the
installation room.
• Fill in the holes in the wall with mortar (3).
• Ensure that the brine pipes (2) are centred in the insert
pipes (1) so that the insulation is distributed equally on
all sides.
• Seal the insert pipes (1) with a suitable sealant
(foam) (4).
The heat pump is packed in boxes and wrapped in cardboard and delivered on a wood pallet.
• Check that the delivery is complete and undamaged.
NOTE! When moving the heat pump, do not use the
⚠
protruding pipe connections to lift the heat pump.
The packaging should not be used to lift the heat
pump either.
• Move the heat pump to the installation site.
• Cut off the straps and remove the packaging.
• Lift the heat pump from the pallet.
• Install a condensation drain if required.
• Adjust using the adjustable legs (5) so that it stands
upright and level on the floor.
4.1 Removing the front cover
Remove the front cover plate as follows:
• Unscrew the screws (1).
• Slide the front cover (2) upwards and carefully lift it off
upwards and forwards.
• Place the front cover next to the heat pump.
10
VMIFI102
5 Piping installation
To prevent leaks ensure that there are no stresses in
⚠
the connecting pipes!
• Ensure that the pipe installation is carried out in accordance with the dimensions and connection diagrams.
NOTE! It is extremely important that the heating sys-
⚠
tem is completely bled.
NOTE! Bleed valves must be installed where necessary.
⚠
5.1 Safety valve
Radiator systems with closed expansion tanks must also
be supplied with approved pressure gauge and safety
valve.
NOTE! The heat pump must be connected to the
⚠
expansion tank and the safety valve according to
applicable regulations.
The connecting lines between the reservoir and the
safety valve must be routed in a continuous incline.
A continuous upwards slope means that the pipe
must not slope downwards from the horizontal at
any point.
5.2 Heating system supply pipe and return
pipe
• Install a filter (max mesh size 0.7 mm) in the heating
system’s return pipe to protect the unit against foreign
particles.
• Install the supply line with all the accompanying com-
ponents.
• Install a suitable circulation pump in the heating system
supply pipe and connect the pump’s control cable to
the relevant terminal block (see separate wiring diagram).
• Install the return line with all the accompanying compo-
nents.
• Insulate the supply and return pipes.
Brine
Additional shunt
(0-10V)
Heating system
TWC Communication
CW
HW
Hot water
HWC
HWHHWHHWHHWH
Hot gas circuit
TWC = Tap Water Control
CW = Cold water
HW = Hot water
HWC = Hot water circulation
HWH = Hot water heater
Example of system solution for DHP-R Eco with several water heaters.
11
VMIFI102
T1
E1
E2
F1
F2
F3
F100
F101
F102
K2
K1
F11
F10
X1
6 Electrical Installation
6.1 Electrical connection
The electrical installation must only be carried out by
⚠
an authorized electrician (and must follow applicable
local and national regulations). The electrical installation must be carried out using permanently routed
cables. It must be possible to isolate the power supply using an all-pole circuit breaker for the intended
current. For information regarding maximum load
for externally connected devices. see electrical installation instructions.
Electrical current!
The terminal blocks are live and can be highly dan-
⚠
gerous due to the risk of electric shock. The power
supply must be isolated before electrical installation
is started. The heat pump is internally connected
at the factory. The electrical installation therefore
mainly covers the following points:
Connection to the power supply
• Remove the front cover from the heat pump.
• Pull the power supply cable through the opening in the
rear of the heat pump to the terminal blocks.
• Connect the supply cable to the designated terminal
block.
See separate manual for the control system.
Note that the power supply cable must only be con-
⚠
nected to the intended terminal block. No other terminal blocks may be used!
Incoming cable control circuit
Incoming cable
Electrical cabinet layout
NOTE! The bridge is
removed in the event
of separate control
Bridged at delivery
circuit.
K1 Contactor compressor
K2 Contactor brine pump
F10 Over current relay compressor.
F11 Over current relay brine pump
F1 Fuse brine pump
F2 Control fuse regulation. overheating protection
compressor
F3 Control fuse condensation pump
F100 Fuse 24 VAC 1
F101 Fuse 24 VDC
F102 Fuse 24 VAC 2
X1 Terminal blocks for incoming supply and tempera-
ture sensor as well as terminal blocks for external
components
T1 Transformer 24 VAC 2x50 VA
E1 WM HPC
E2 HPC RM
6.2 Connecting pump hot gas
Pump hot gas
Connect the hot gas pump to the designated terminal
block. The voltage is 230 VAC. The pump is designed to be
placed outside the heat pump casing and must be connected with flexible hoses.
This pump runs in parallel with the compressor.
6.3 Connecting sensor for outside temperature
Sensor outdoor
PT1000
Position the outdoor sensor on the north or north west
facing side of the house. away from direct sunlight. The
outdoor sensor should not be placed on reflective panel
walls. The sensor must be positioned at least 1 m from
openings in the walls that emit hot air.
If the sensor cable is connected through a pipe. the pipe
must be sealed so that the sensor is not affected by outgoing indoor air.
• Remove the rear piece from the heat pump.
• Route the outdoor sensor’s connecting cable through
the opening in the rear of the heat pump up to the connecting block.
• Connect the sensor to the designated terminal block.
See separate manual for the control system.
Note that the outdoor sensor is connected with
⚠
extra low protection voltage.
Also follow the applicable installation instructions for out-
door sensors!
12
6.4 Connecting hot water sensor
Hot water sensor
PT1000
Connect the hot water sensor to the designated terminal
block. The sensor should be positioned a third way up
from the bottom in the water heater which is supplied with
incoming cold water.
See separate manual for the control system.
6.5 Connecting sensor for system supply
temperature
Sensor system sup-
ply temperature
PT1000
The system supply sensor must always be installed on the
system’s supply pipe after the auxiliary heater. The sensor
must be positioned so that the heated water has been able
to mix properly.
See separate manual for the control system.
Potential free connection between terminal blocks 127128 that start the brine pump. This function can be used
for passive cooling from the brine circuit. Connect to the
incoming brine pipe.
See separate manual for the control system.
• Auxiliary modules
The two separate 24 VAC circuits must never be con-
Connect the pressure and/or flow switch for the brine side
to the intended terminal block 123-124 at the same time
as removing the bridge. When using both the pressure and
flow switch. these must be connected in series.
See separate manual for the control system.
6.10 Connecting start/stop auxiliary heater
Any Start/
stop auxiliary
heater
Start/stop auxiliary heating connected to terminal block
133-134 (24 VAC)
See separate manual for the control system.
6.11 Connecting external buzzer
Any external
buzzer 24 VAC
6.7 Connecting exchange valve for hot
water
Exchange valve
See separate manual for the control system.
6.8 Connecting room sensor (option)
Sensor room 0-10 V
(option)
• Remove the front cover from the heat pump.
• Route the room sensor’s connecting cable through the
opening in the rear piece up to the connecting block.
• Connect the sensor to the designated terminal block.
See separate manual for the control system.
Note that the room sensor’s connecting voltage is
⚠
extra low protection voltage. Also note that this is an
active sensor supplied with 24 VAC.
24 VAC 1 must not be connected together with:
⚠
• 24 VAC 2
• 24 VDC
• Other equipment that uses 0-10V control signal
• Signal ground GND
24 VAC 2 must only be used as power supply to:
⚠
• External equipment that requires 0-10V control
signal
Active alarm produces 24 VAC out on terminal block 135-
136.
See separate manual for the control system.
6.12 Connecting system pump
System pump
Start/stop of the house system pump 24 VAC.
See separate manual for the control system.
6.13 Connecting control signal for auxiliary
heater
Analogue control
signal for auxiliary
heater
See separate manual for the control system.
24 VAC 1 must not be connected together with:
⚠
• 24 VAC 2
• 24 VDC
• Other equipment that uses 0-10V control signal
• Signal ground GND
24 VAC 2 must only be used as power supply to:
⚠
• External equipment that requires 0-10V control
signal
• Auxiliary modules
The two separate 24 VAC circuits must never be con-
⚠
nected to each other or to protective ground.
The total power load on 24 VAC 1 respectively 24
⚠
VAC 2 must not exceed 50VA.
VVMIFI102
13
VMIFI102
6.14 Locations of the switches
7 Brine installation
7.1 Brine pipes and expansion tank
• Install a filter (max mesh size 0.7 mm) in the input coolant pipe to protect the unit against foreign particles.
• Install the input coolant pipe with all the accompanying
components.
• Install the output coolant pipe with all the accompanying components.
• Supply both the pipes with diffusion sealed condensation insulation.
• The expansion vessel for the coolant is sized according
to the manufacturer’s instructions.
• Max operating pressure heat source (see manufacturer’s
When reading the resistance of the sensors, the sensor
leads must first be disconnected from the control equipment.
First measure the sensor including the cable.
Then measure the sensor only.
7.2 Filling the coolant system
WARNING! Ethylene glycol and ethanol must be han-
⚠
dled according to the instructions on the packaging!
1
3
6
4
5
1 Connect the hose from the filler pump to valve 1.
2 Connect the return hose to valve 2.
3 Close valve 3.
4 Open valves 1 and 2.
5 Mix coolant in container 4.
6 Ensure that the heat pump is not powered.
7 Start filling pump 5.
8 When the coolant flows out of the return hose the
internal coolant pump is bled inside the heat pump.
9 Set switch marked S1 in position Off. (Compressor
Auto/Off)
10 Switch on the heat pump’s safety switch.
11 Set switch marked S2 in position Manual. (Brine pump
Auto/Off/Manual)
12 Then let both the pumps operate until there is no air
mixture left in the circuit.
2
13 Stop both the pumps and immediately close valve 1
and 2.
14 Open valve 3 and disconnect the filling hoses.
15 Open valve 6 and pressurise the system, and vent via
valve 1. Pressurise to max 1.5 bar.
16 Close valve 6.
17 Set switch S1 and S2 to Auto
(compressor and brine pump).
18 Clean the strainers after filling.
8 Start up
The installation may only start operation if the heat-
⚠
ing system, any hot water tanks and the coolant
circuit are filled. Otherwise the pumps can be damaged.
In addition, the following points must be checked before
starting operations:
• Check the rotation direction of the coolant pump. This is
most easily done by setting switch S2 to manual. There
is an indicator lamp, under the cover of the coolant
pump connection terminal box, which lights when the
rotation direction is correct.
• Check that all connections are sealed.
• Check the compressor’s direction of rotation by start-
ing the compressor and feel by hand if the pressure line
(upper pipe) is warm and the suction line (lower pipe) is
cold.
• If this is not the case, two of the phases in the power
supply must be switched (for example L1 and L3).
• Adapt the factory settings to the customer requirements.
8.1 Installing the front cover
Take care not to damage the front cover!
⚠
2
1
Install the front cover as follows:
• Align the upper section of the front cover (2) in both the
side channels on the unit and slide it carefully downwards until it covers the entire front side.
• Tighten the screws (1).
14
VMIFI102
9 Handover
9.1 Installation and commissioning carried out by:
As user please ensure that the installer fills in the following information to facilitate servicing.
PIPE INSTALLATION
Date ............................ Company ........................................................................
Name ........................... Tel. No............................................................................
ELECTRICAL INSTALLATION
Date ............................ Company ........................................................................
Name ........................... Tel. No............................................................................
SYSTEM ADJUSTMENT
Date ............................ Company ........................................................................
Name ........................... Tel. No............................................................................
VMIFI102
15
10 Troubleshooting
Alarm
In the event of an error message try restarting the installation using the reset button on the control panel.
If restarting the heat pump does not help try rectifying the problem using the table below.
MessageMeaningCauseRemedy
LOW PRESS
ERROR
HIGH PRESS
ERROR
MOTOR P
ERROR
Low pressure
error - The compressor stops
and there is no
hot water production.
High pressure
error - The compressor stops
and there is no
hot water production.
Motor protection error - (Over
current relay
compressor or
brine pump).
The compressor
stops and there
is no hot water
production.
Not enough anti-freeze in the
coolant system. Air in the brine
system. Blocked filter in the
brine system.
Coolant pump has stopped or
is running at slow speed.
Ice build up in the coolant
system.
Underfilled cooling system or
any leaks.
Blocked or filled drying filter in
the cooling circuit.
Insufficiently opened radiator/
floor loop thermostats. Air in
the heating system. Blocked
strainer in the heating system,
located in the heat pump
return.
Overfilled refrigerant circuit.Draining the refrigerant circuit and
Heat transfer fluid pump has
stopped or is running at slow
speed.
Phase drop or blown fuse.Check the fuses and cable terminals
Poorly tightened electrical
connections.
Too low network voltage.Measure the voltage to the heat
Fill the refrigerant with the correct
percentage of anti-freeze and bleed
using the safety valve on the volume
container. Check if the strainer needs
cleaning.
Take temperature difference
readings between incoming and
outgoing coolant. The difference
should be between approximately
3-5°C.
Measure the amount of anti-freeze
in %, wait until the ice melts, which
affects the low pressure switch not
contacting the wiring.
Drain and leak trace as well as filling
new refrigerant. No refilling of drained medium.
Measure the temperature difference
of the filter – max 2°C.
Open radiator / floor loop thermostats. Fill and bleed the heating
system. Measure delta over the
heat pump supply and return lines.
Temperature difference.
refilling with new refrigerant, according to the instructions.
Check the heart transfer fluid pump.
(power supply to the compressor or
brine pump).
Check the electrical connections.
pump’s electrical connection.
Other alarms;
See separate manual for the control system.
16
VMIFI102
11 Technical data
DHP-R Eco22263342
RefrigerantTypeR410AR410AR410AR410A
CompressorTypeScrollScrollScrollScroll
Electrical data
3-N
PerformanceCOP
Nominal flow
External available
pressure drop
Internal pressure dropCondenser
Maximum system pressureBrine
Min/max temperature
Pressure switchesLow pressure
Sound power level
Anti freeze mediaEthanol+water solution -17°C ± 2
Weightkg244260281290
The meas urements are pe rformed on a li mited number o f heat pumps whi ch
can caus e variations i n the results. Tole rances in the me asuring metho ds can
also cause variations.
2
4
5
7
Amountkg3.83.94.54.6
Test pressureMPa4.54.54.54.5
Design pressureMPa4.34.34.34.3