Danfoss DHP-R Eco Installation Instructions Manual

Installation instructions
Danfoss heat pump
DHP-R Eco
VMIFI102
Danfoss A/S is not liable or bound by warranty if these instructions are not adhered to during installation or service.
The English language is used for the original instructions. Other languages are a translation of the original instructions. (Directive 2006/42/EC)
© Copyright Danfoss A/S
Table of contents
DHP-R Eco
1 Important information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 Refrigerant..............................................................................5
1.2 Noise and vibrations ....................................................................5
1.3 Electrical connection ....................................................................6
2 Heat pump information ..........................................................7
2.1 Components ............................................................................7
2.2 Pipe connections........................................................................8
2.3 Required service space ..................................................................8
3 Drilling holes for brine pipes .....................................................9
4 Unpacking and installation .......................................................9
4.1 Removing the front cover................................................................9
5 Piping installation ..............................................................10
5.1 Safety valve ............................................................................10
5.2 Heating system supply pipe and return pipe ............................................10
6 Electrical Installation............................................................11
6.1 Electrical connection ...................................................................11
6.2 Connecting pump hot gas..............................................................11
6.3 Connecting sensor for outside temperature .............................................11
6.4 Connecting hot water sensor ...........................................................12
6.5 Connecting sensor for system supply temperature ......................................12
6.6 Connecting external start brine pump (passive cooling option) . . . . . . . . . . . . . . . . . . . . . . . . . .12
6.7 Connecting exchange valve for hot water ...............................................12
6.8 Connecting room sensor (option).......................................................12
6.9 Connecting pressure and/or flow switch (option)........................................12
6.10 Connecting start/stop auxiliary heater ..................................................12
6.11 Connecting external buzzer ............................................................12
6.12 Connecting system pump ..............................................................12
6.13 Connecting control signal for auxiliary heater ...........................................12
6.14 Locations of the switches...............................................................13
6.15 Conversion table for sensors............................................................13
7 Brine installation ...............................................................13
7.1 Brine pipes and expansion tank.........................................................13
7.2 Filling the coolant system...............................................................13
8 Start up ........................................................................14
8.1 Installing the front cover................................................................14
9 Handover ......................................................................15
9.1 Installation and commissioning carried out by: .........................................15
10 Troubleshooting ...............................................................16
11 Technical data ..................................................................17
VMIFI102
3
1 Important information
This appliance can be used by children aged from 8
years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Cleaning and user maintenance shall not be made by children without supervision.
Children should be supervised to ensure that they
do not play with the appliance.
The installation must only be carried out by an
authorized installer with reference to applicable rules and orders and these installation instructions.
This apparatus is not intended for persons (including
children) with reduced physical, sensory or psycho­logical capacity, or who do not have knowledge or experience, unless supervised or they have received instructions on how the apparatus functions from a safety qualified person.
The heat pump must be located in a frost-free envi-
ronment!
The floor must be able to support the gross weight
of the heating installation.
The heating installation must be placed on a stable
surface.
Before the heat pump is supplied with voltage you
must ensure that the heating system and coolant system. incl. the heat pump. are filled and bled of air otherwise the circulation pumps can be dam­aged.
If the electrician wishes to test his connections
before the above is carried out this should only done when it has been checked that the heat transfer fluid and coolant pumps have been discon­nected.
When filling the coolant system the coolant pump
must be operating but one must ensure that the compressor and the heat transfer pump cannot start. The coolant pump can then be run manually using a separate switch which is located on the electrical cabinet.
When filling is complete the coolant pump must be
put in Auto mode.
The appliance is intended to be used by expert or
trained users in shops, in light industry and on farms or commercial use by lay persons
Only spare parts approved by us may be used in this appliance.
The power supply must be disconnected during
service and before changing parts in the appliance.
1 .1 Refrigerant
The heat pump’s cooling system (refrigerant circuit) is filled with R407C or R134a (depending on version) refrig­erant.
Work on the refrigerant circuit must only be carried out by a certified engineer!
Toxicity
In normal use and normal conditions the refrigerant has low toxicity. However. although the toxicity of the refriger­ant is low. it can cause injury (or be highly dangerous) in
abnormal circumstances or where deliberately abused. The refrigerant vapour is many times heavier than air and in enclosed spaces. below the level of the door for exam­ple. and in the event of leakage. large concentrations can occur with the risk of suffocation because of lack of oxy­gen. Spaces in which heavy vapour can collect below the level of the air must therefore be well ventilated.
Refrigerant exposed to a naked flame creates a poi­sonous irritating gas. This gas can be detected by its odour even at concentrations below its permitted levels. Evacuate the area until it has been sufficiently ventilated.
Anyone with symptoms of poisoning from the vapour must immediately move or be moved into the fresh air.
Work on the refrigerant circuit
When repairing the refrigerant circuit. the refrigerant must not be destroyed at a special plant. Draining and refilling must only be carried out using new refrigerant (for the amount of refrigerant see manufacturer’s plate) through the serv­ice valves. All warranties from Danfoss Heat Pump´s AB are void if. when filling with refrigerant other than R407C or R134a. it has not been notified in writing that the new refrigerant is an approved replacement refrigerant together with other remedies.
Scrapping
When the heat pump is to be scrapped the refrigerant must be extracted for destruction. The local regulations for treatment of refrigerant must be followed. See the relevant Swedish Environmental Protection Agency refrig­erant statutes.
released from the heat pump – it must be
1 .2 Noise and vibrations
From the sound and vibration point of view it is important that the pipe mountings in the ceiling and walls are made with vibration damping fastenings and that the holes for lead-ins in the walls are made as large as possible so that sound and vibration do not spread.
If the house has poor acoustics. special care must be taken so that the vibrations do not spread into the build­ing.
In such cases no mountings may be made in the house near the heat pump. All mountings must be in free stand­ing constructions. which themselves are in vibration damping material such as Solodyn.
In those cases where the coolant side must be mounted to the building. flexible hoses should be used. although not the same type as the heat transfer pipes. Flexible hoses for the heat transfer and hot gas must be long (600 mm or longer) and connected at 90°. If one suspects that the floor on which the heat pump is located may transfer vibration to the rest of the building. the heat pump must be positioned on Solodyn pads. These pads must be weight adapted. Always consult the representa­tive from Danfoss Heat pump´s AB in these cases.
extra
VMIFI102
5
6
1.3 Electrical connection
The electrical installation must only be carried out by
an authorized electrician (and must follow applicable local and national regulations). The electrical instal­lation must be carried out using permanently routed cables. It must be possible to isolate the power sup­ply using an all-pole circuit breaker for the intended current. For information regarding maximum load for externally connected devices, see electrical instal­lation instructions.
NOTE! The supplied language specific decal for electrical connection must be adhered to the inside of the door
Electrical current!
The terminal blocks are live and can be highly dan-
gerous due to the risk of electric shock. The power supply must be isolated before electrical installation is started. The heat pump is internally connected at the factory.
Important information
24 VAC 1 must not be connected together with:
• 24 VAC 2
• 24 VDC
• Other equipment that uses 0-10V control signal
• Signal ground GND
24 VAC 2 must only be used as power supply to:
• External equipment that requires 0-10V control
signal
• Auxiliary modules
The two separate 24 VAC circuits must never be con-
nected to each other or to protective ground.
The total power load on 24 VAC 1 respectively 24
VAC 2 must not exceed 50VA.
VMIFI102
7
VMIFI102
2 Heat pump information
21 Low pressure transmitter
2.1
1 Coolant out (from HP)
2 Heat return (return line) 3 Return line hot-gas exchanger 4 Supply line hot-gas exchanger 5 Heat supply (supply line) 6 Coolant in (to HP) 7 Lead-in for communication cable 8 Lead-in for incoming supply and sensor 9 Supply pipe sensor 10 Condenser with draining for prim. side.
Components
6
5
4
7
8
3
2
1
9
10
18
13
21
21
2
10
11
14
16
15
17
19
12
Evaporator
11 12
Return sensor
12
13 Compressor 14 Instrument panel 15 Electrical cabinet 16 De-superheater 17 Drying filter 18 Expansion valve 19 Condenser circulation pump 20 Coolant pump
8
2.2 Pipe connections
Connection diameter
Brine Heat De-superheater
DHP-R Eco 22
DHP-R Eco 26
DHP-R Eco 33
DHP-R Eco 42
35 28 28
35 28 28
42 35 28
42 35 28
When installing in confined spaces, pipe routing on the rear of the heat pump can be facilitated by connecting the pipes before the pump is put in position. See the figure below for an example on how the pipes can be routed.
NOTE! Remember not to tighten the pipes in the
heat pump’s panel casing as this transfers vibrations causing noise problems.
1. Coolant out (from HP)
2. Heat return (return line)
3. Return line hot-gas exchanger
4. Supply line hot-gas exchanger
5. Heat supply (supply line)
6. Coolant in (to HP)
300 mm
300 mm
50 mm
500 mm
600 mm
690 mm
600 mm
1490 mm (with support legs at highest level)
The figure above shows dimensions for one (1) installed heat pump and the necessary service space.
Required service space when installing several heat pumps in a row.
500 mm
2.3 Required service space
To facilitate installation and later tests and maintenance there must be sufficient free space around the heat pump according to the following dimensions:
When installing several heat pumps, the dimensions behind the heat pumps may need to be increased if there is not enough side space. The pumps must be set-up so that the installation can be accessed from behind.
150 mm
500 mm
150 mm
150 mm
300 mm
VMIFI102
9
VMIFI102
3 Drilling holes for brine pipes
5
5
5
5
1
2
4 Unpacking and installation
• Make holes in the walls for the entry pipes (1) for the
coolant pipes. Follow the dimensions and connection diagrams on pages 7-8.
• The output and input coolant pipes must have wall lead-ins.
• If there is a risk of infiltration by ground water, special
lead-ins must be used.
Install the entry pipes (1) so that they incline slightly wards. The incline should be at least 1 cm per 30 cm.
down-
Cut them at an angle (as illustrated) so that rain water cannot get into the pipes.
• Ensure that the entry pipes are at the correct distance so
that there is room for the other installations.
• Insert the brine pipes (2) into the insert pipes in the
installation room.
• Fill in the holes in the wall with mortar (3).
• Ensure that the brine pipes (2) are centred in the insert
pipes (1) so that the insulation is distributed equally on all sides.
• Seal the insert pipes (1) with a suitable sealant
(foam) (4).
The heat pump is packed in boxes and wrapped in card­board and delivered on a wood pallet.
• Check that the delivery is complete and undamaged.
NOTE! When moving the heat pump, do not use the
protruding pipe connections to lift the heat pump. The packaging should not be used to lift the heat pump either.
• Move the heat pump to the installation site.
• Cut off the straps and remove the packaging.
• Lift the heat pump from the pallet.
• Install a condensation drain if required.
• Adjust using the adjustable legs (5) so that it stands
upright and level on the floor.
4.1 Removing the front cover
Remove the front cover plate as follows:
• Unscrew the screws (1).
• Slide the front cover (2) upwards and carefully lift it off
upwards and forwards.
• Place the front cover next to the heat pump.
10
VMIFI102
5 Piping installation
To prevent leaks ensure that there are no stresses in
the connecting pipes!
• Ensure that the pipe installation is carried out in accord­ance with the dimensions and connection diagrams.
• Pipeinstallationmustbecarriedoutbyanauthor­ized installer.
NOTE! It is extremely important that the heating sys-
tem is completely bled.
NOTE! Bleed valves must be installed where necessary.
5.1 Safety valve
Radiator systems with closed expansion tanks must also be supplied with approved pressure gauge and safety valve.
NOTE! The heat pump must be connected to the
expansion tank and the safety valve according to applicable regulations. The connecting lines between the reservoir and the safety valve must be routed in a continuous incline. A continuous upwards slope means that the pipe must not slope downwards from the horizontal at any point.
5.2 Heating system supply pipe and return pipe
• Install a filter (max mesh size 0.7 mm) in the heating
system’s return pipe to protect the unit against foreign particles.
• Install the supply line with all the accompanying com-
ponents.
• Install a suitable circulation pump in the heating system
supply pipe and connect the pump’s control cable to the relevant terminal block (see separate wiring dia­gram).
• Install the return line with all the accompanying compo-
nents.
• Insulate the supply and return pipes.
Brine
Additional shunt
(0-10V)
Heating system
TWC Communication
CW
HW
Hot water
HWC
HWH HWH HWH HWH
Hot gas circuit
TWC = Tap Water Control CW = Cold water HW = Hot water HWC = Hot water circulation
HWH = Hot water heater
Example of system solution for DHP-R Eco with several water heaters.
11
VMIFI102
T1 E1 E2
F1
F2 F3 F100 F101 F102
K2 K1
F11 F10
X1
6 Electrical Installation
6.1 Electrical connection
The electrical installation must only be carried out by
an authorized electrician (and must follow applicable local and national regulations). The electrical instal­lation must be carried out using permanently routed cables. It must be possible to isolate the power sup­ply using an all-pole circuit breaker for the intended current. For information regarding maximum load for externally connected devices. see electrical instal­lation instructions.
Electrical current!
The terminal blocks are live and can be highly dan-
gerous due to the risk of electric shock. The power supply must be isolated before electrical installation is started. The heat pump is internally connected at the factory. The electrical installation therefore mainly covers the following points:
Connection to the power supply
• Remove the front cover from the heat pump.
• Pull the power supply cable through the opening in the
rear of the heat pump to the terminal blocks.
• Connect the supply cable to the designated terminal
block.
See separate manual for the control system.
Note that the power supply cable must only be con-
nected to the intended terminal block. No other ter­minal blocks may be used!
Incoming cable control circuit
Incoming cable
Electrical cabinet layout
NOTE! The bridge is
removed in the event
of separate control
Bridged at delivery
circuit.
K1 Contactor compressor
K2 Contactor brine pump
F10 Over current relay compressor.
F11 Over current relay brine pump
F1 Fuse brine pump
F2 Control fuse regulation. overheating protection
compressor
F3 Control fuse condensation pump
F100 Fuse 24 VAC 1
F101 Fuse 24 VDC
F102 Fuse 24 VAC 2
X1 Terminal blocks for incoming supply and tempera-
ture sensor as well as terminal blocks for external components
T1 Transformer 24 VAC 2x50 VA
E1 WM HPC
E2 HPC RM
6.2 Connecting pump hot gas
Pump hot gas
Connect the hot gas pump to the designated terminal block. The voltage is 230 VAC. The pump is designed to be placed outside the heat pump casing and must be con­nected with flexible hoses. This pump runs in parallel with the compressor.
6.3 Connecting sensor for outside temper­ature
Sensor outdoor
PT1000
Position the outdoor sensor on the north or north west facing side of the house. away from direct sunlight. The outdoor sensor should not be placed on reflective panel walls. The sensor must be positioned at least 1 m from openings in the walls that emit hot air. If the sensor cable is connected through a pipe. the pipe must be sealed so that the sensor is not affected by out­going indoor air.
• Remove the rear piece from the heat pump.
• Route the outdoor sensor’s connecting cable through
the opening in the rear of the heat pump up to the con­necting block.
• Connect the sensor to the designated terminal block.
See separate manual for the control system.
Note that the outdoor sensor is connected with
extra low protection voltage.
Also follow the applicable installation instructions for out-
door sensors!
12
6.4 Connecting hot water sensor
Hot water sensor
PT1000
Connect the hot water sensor to the designated terminal block. The sensor should be positioned a third way up from the bottom in the water heater which is supplied with incoming cold water. See separate manual for the control system.
6.5 Connecting sensor for system supply temperature
Sensor system sup-
ply temperature
PT1000
The system supply sensor must always be installed on the system’s supply pipe after the auxiliary heater. The sensor must be positioned so that the heated water has been able to mix properly. See separate manual for the control system.
6.6 Connecting external start brine pump (passive cooling option)
Any passive cooling
brine pump
Potential free connection between terminal blocks 127­128 that start the brine pump. This function can be used for passive cooling from the brine circuit. Connect to the incoming brine pipe. See separate manual for the control system.
• Auxiliary modules
The two separate 24 VAC circuits must never be con-
nected to each other or to protective ground.
The total power load on 24 VAC 1 respectively 24
VAC 2 must not exceed 50VA.
6.9 Connecting pressure and/or flow switch (option)
NOTE! Bridge
Any Pressure switch brine
Flow switch
(option)
removed at pres­sure switch brine Flow switch
Bridged at delivery
Connect the pressure and/or flow switch for the brine side to the intended terminal block 123-124 at the same time as removing the bridge. When using both the pressure and flow switch. these must be connected in series. See separate manual for the control system.
6.10 Connecting start/stop auxiliary heater
Any Start/
stop auxiliary
heater
Start/stop auxiliary heating connected to terminal block 133-134 (24 VAC) See separate manual for the control system.
6.11 Connecting external buzzer
Any external
buzzer 24 VAC
6.7 Connecting exchange valve for hot water
Exchange valve
See separate manual for the control system.
6.8 Connecting room sensor (option)
Sensor room 0-10 V
(option)
• Remove the front cover from the heat pump.
• Route the room sensor’s connecting cable through the
opening in the rear piece up to the connecting block.
• Connect the sensor to the designated terminal block.
See separate manual for the control system.
Note that the room sensor’s connecting voltage is
extra low protection voltage. Also note that this is an active sensor supplied with 24 VAC.
24 VAC 1 must not be connected together with:
• 24 VAC 2
• 24 VDC
• Other equipment that uses 0-10V control signal
• Signal ground GND
24 VAC 2 must only be used as power supply to:
• External equipment that requires 0-10V control
signal
Active alarm produces 24 VAC out on terminal block 135-
136. See separate manual for the control system.
6.12 Connecting system pump
System pump
Start/stop of the house system pump 24 VAC. See separate manual for the control system.
6.13 Connecting control signal for auxiliary heater
Analogue control
signal for auxiliary
heater
See separate manual for the control system.
24 VAC 1 must not be connected together with:
• 24 VAC 2
• 24 VDC
• Other equipment that uses 0-10V control signal
• Signal ground GND
24 VAC 2 must only be used as power supply to:
• External equipment that requires 0-10V control
signal
• Auxiliary modules
The two separate 24 VAC circuits must never be con-
nected to each other or to protective ground.
The total power load on 24 VAC 1 respectively 24
VAC 2 must not exceed 50VA.
VVMIFI102
13
VMIFI102
6.14 Locations of the switches
7 Brine installation
7.1 Brine pipes and expansion tank
• Install a filter (max mesh size 0.7 mm) in the input cool­ant pipe to protect the unit against foreign particles.
• Install the input coolant pipe with all the accompanying
components.
• Install the output coolant pipe with all the accompany­ing components.
• Supply both the pipes with diffusion sealed condensa­tion insulation.
• The expansion vessel for the coolant is sized according
to the manufacturer’s instructions.
• Max operating pressure heat source (see manufacturer’s
plate). Max 6 bar.
Auto
S1
Off
S2
Auto
Manual
Auto
Off
S3
Off
Manual
S1 Switch compressor. (Auto/Off ) S2 Switch coolant pump. (Auto/Off/Manual)
NOTE! Must only be used in manual position when fill­ing the system or other maintenance/service work.
S3 Switch circulation pump. (Auto/Off/Manual)
6.15 Conversion table for sensors
°C ohm
-30 882
-20 921
-10 960 0 1000
10 1039 20 1078 30 1117 40 1155 50 1194 60 1232 70 1270 80 1309
90 1347 100 1385 110 1422 120 1460
130 1497
When reading the resistance of the sensors, the sensor leads must first be disconnected from the control equip­ment. First measure the sensor including the cable. Then measure the sensor only.
7.2 Filling the coolant system
WARNING! Ethylene glycol and ethanol must be han-
dled according to the instructions on the packaging!
1
3
6
4
5
1 Connect the hose from the filler pump to valve 1.
2 Connect the return hose to valve 2.
3 Close valve 3.
4 Open valves 1 and 2.
5 Mix coolant in container 4.
6 Ensure that the heat pump is not powered.
7 Start filling pump 5.
8 When the coolant flows out of the return hose the
internal coolant pump is bled inside the heat pump.
9 Set switch marked S1 in position Off. (Compressor
Auto/Off)
10 Switch on the heat pump’s safety switch.
11 Set switch marked S2 in position Manual. (Brine pump
Auto/Off/Manual)
12 Then let both the pumps operate until there is no air
mixture left in the circuit.
2
13 Stop both the pumps and immediately close valve 1
and 2.
14 Open valve 3 and disconnect the filling hoses.
15 Open valve 6 and pressurise the system, and vent via
valve 1. Pressurise to max 1.5 bar.
16 Close valve 6.
17 Set switch S1 and S2 to Auto
(compressor and brine pump).
18 Clean the strainers after filling.
8 Start up
The installation may only start operation if the heat-
ing system, any hot water tanks and the coolant circuit are filled. Otherwise the pumps can be dam­aged.
In addition, the following points must be checked before starting operations:
• Check the rotation direction of the coolant pump. This is
most easily done by setting switch S2 to manual. There is an indicator lamp, under the cover of the coolant pump connection terminal box, which lights when the rotation direction is correct.
• Check that all connections are sealed.
• Check the compressor’s direction of rotation by start-
ing the compressor and feel by hand if the pressure line (upper pipe) is warm and the suction line (lower pipe) is cold.
• If this is not the case, two of the phases in the power
supply must be switched (for example L1 and L3).
• Adapt the factory settings to the customer require­ments.
8.1 Installing the front cover
Take care not to damage the front cover!
2
1
Install the front cover as follows:
• Align the upper section of the front cover (2) in both the
side channels on the unit and slide it carefully down­wards until it covers the entire front side.
• Tighten the screws (1).
14
VMIFI102
9 Handover
9.1 Installation and commissioning carried out by:
As user please ensure that the installer fills in the following information to facilitate servicing.
PIPE INSTALLATION
Date ............................ Company ........................................................................
Name ........................... Tel. No............................................................................
ELECTRICAL INSTALLATION
Date ............................ Company ........................................................................
Name ........................... Tel. No............................................................................
SYSTEM ADJUSTMENT
Date ............................ Company ........................................................................
Name ........................... Tel. No............................................................................
VMIFI102
15
10 Troubleshooting
Alarm
In the event of an error message try restarting the installation using the reset button on the control panel. If restarting the heat pump does not help try rectifying the problem using the table below.
Message Meaning Cause Remedy
LOW PRESS ERROR
HIGH PRESS ERROR
MOTOR P ERROR
Low pressure error - The com­pressor stops and there is no hot water pro­duction.
High pressure error - The com­pressor stops and there is no hot water pro­duction.
Motor protec­tion error - (Over current relay compressor or brine pump). The compressor stops and there is no hot water production.
Not enough anti-freeze in the coolant system. Air in the brine system. Blocked filter in the brine system.
Coolant pump has stopped or is running at slow speed.
Ice build up in the coolant system.
Underfilled cooling system or
any leaks.
Blocked or filled drying filter in the cooling circuit.
Insufficiently opened radiator/ floor loop thermostats. Air in the heating system. Blocked strainer in the heating system, located in the heat pump return.
Overfilled refrigerant circuit. Draining the refrigerant circuit and
Heat transfer fluid pump has stopped or is running at slow speed.
Phase drop or blown fuse. Check the fuses and cable terminals
Poorly tightened electrical connections.
Too low network voltage. Measure the voltage to the heat
Fill the refrigerant with the correct percentage of anti-freeze and bleed using the safety valve on the volume container. Check if the strainer needs cleaning.
Take temperature difference readings between incoming and outgoing coolant. The difference should be between approximately 3-5°C.
Measure the amount of anti-freeze in %, wait until the ice melts, which affects the low pressure switch not contacting the wiring.
Drain and leak trace as well as filling new refrigerant. No refilling of drai­ned medium.
Measure the temperature difference of the filter – max 2°C.
Open radiator / floor loop thermo­stats. Fill and bleed the heating system. Measure delta over the heat pump supply and return lines. Temperature difference.
refilling with new refrigerant, accor­ding to the instructions.
Check the heart transfer fluid pump.
(power supply to the compressor or brine pump).
Check the electrical connections.
pump’s electrical connection.
Other alarms;
See separate manual for the control system.
16
VMIFI102
11 Technical data
DHP-R Eco 22 26 33 42
Refrigerant Type R410A R410A R410A R410A
Compressor Type Scroll Scroll Scroll Scroll
Electrical data 3-N
Performance COP
Nominal flow
External available pressure drop
Internal pressure drop Condenser
Maximum system pressure Brine
Min/max temperature
Pressure switches Low pressure
Sound power level
Anti freeze media Ethanol+water solution -17°C ± 2
Weight kg 244 260 281 290
The meas urements are pe rformed on a li mited number o f heat pumps whi ch can caus e variations i n the results. Tole rances in the me asuring metho ds can also cause variations.
2
4
5
7
Amount kg 3.8 3.9 4.5 4.6 Test pressure MPa 4.5 4.5 4.5 4.5 Design pressure MPa 4.3 4.3 4.3 4.3
Oil POE POE POE POE
Main supply Volt 400 400 400 400 Rated power, compressor Rated power, circulationpumps Start current A 21.7 23.8 32.2 37.1 Fuse A 20 25 32 32
1
Heating capacity Electrical power
Cooling circuit Heating circuit l/s 0.5 0.6 0.8 0.9
Cooling circuit kPa 81 75 73 63 Heating circuit kPa 75 70 66 50
Evaporator
Heat transfer fluid
Cooling circuit °C 20/-10 20/-10 20/-10 20/-10 Heating circuit
Operating High pressure MPa 4.3 4.3 4.3 4.3
1
1
3
6
1) B0/W35, Accor ding to EN14511 incl. c irc.pump.
2) Nominal flow h eating circui t Δ10K , coo ling circuit Δ3 K.
3) Anti-fr eeze in cooling ci rcuit: Ethano l-water.
4) At nominal flo w.
kW kW
kW kW
l/s 1.4 1.5 2.1 2.4
kPa kPa
bar bar
°C 65/20 65/20 65/20 65/20
MPa MPa
dB (A) 55 55,2 56,4 56
9,91
0.5
4.40
21.9
5.0
2.3
23.8
0.35
4.0
12,40
0.5
4.40
25.4
5.8
6.6
27.0
6 6
6 6
0.35
4.0
8
5) Please note t hat not all cooli ng circuit temp eratures and h eating temperatures can be combined.
6) Min. incomi ng cooling circu it temperatu re 0°C.
Sound power level measured according to EN 12102 and EN ISO 3741 at B0W
7)
8) Always chec k local rules an d regulations b efore using ant ifreeze.
14,83
0.6
4.37
33.5
7.7
5.0
33.0
6 6
0.35
4.0
19,12
0.6
4.31
41.4
9.6
16.0
37.0
6 6
0.35
4.0
Danfoss Heat Pumps reserves the right to make changes without further notice. 130923_R_ENG
35
Min/Max Operation Temperature R410A
70
60
50
40
30
Twater °C
20
10
0
-15 -10 -5 0 5 10 15 20 25
Tbrine °C
R410A T brine °C T water °C
20 65
0 65
-5 60
-10 54
-10 20 5 20
20 30
VMIFI102
17
If these instructions are not followed during installation,
operation and maintenance Danfoss Heat Pumps’ liability
according to the applicable warranty is not binding.
DanfossHeatPumpsAB•Box950•SE-67129Arvika
www.danfoss.com
Loading...