Danfoss DHP-AQ Series, DHP-AQ Maxi, DHP-AQ Mini, DHP-AQ Midi Service Instructions Manual

MAKING MODERN LIVING POSSIBLE
Service Instructions
DHP-AQ
www.heating.danfoss.com
Danfoss A/S is not liable or bound by warranty if these instructions are not adhered to during installation or service.
The English language is used for the original instructions. Other languages are a translation of the original instructions. (Directive 2006/42/EC)
© Copyright Danfoss A/S
Service Instructions DHP-AQ

Table of Contents

1 About documents and decals ........................................................ 4
1.1 Introduction ................................................................ 4
1.2 Symbols in documents .......................................................... 4
1.3 Symbols on decals ............................................................ 4
2 Important information/Safety regulation ................................................ 6
2.1 General safety precautions ....................................................... 6
2.2 Refrigerant ................................................................. 7
2.3 Electrical connection ........................................................... 8
2.4 Water quality ................................................................ 8
2.5 Commissioning .............................................................. 9
3 Troubleshooting ................................................................. 10
3.1 Alarm ..................................................................... 10
3.2 Components ................................................................ 11
3.3 Measurement points ........................................................... 12
3.4 Check points ................................................................ 14
3.5 Operational problems .......................................................... 15
Danfoss Heating Solutions VMGFJ202
3
N
Service Instructions
DHP-AQ

1 About documents and decals

1.1 Introduction

The following documents are available for this product:
Installation quick guide containing information to install a heat pump. Supplied with the heat pump on delivery.
The Service instructions contain information about the heat pump’s function, accessories, fault tracing and technical data. The in-
structions also contain tips and advice that should be followed before a heat pump installation. It is therefore recommended that the instructions are read before installation. The Service instructions are available for download as below.
The Wiring diagrams that contain the wiring diagram for the heat pump intended for fault tracing and service. The Wiring diagrams
are available for download as below. The User manual must handed over and gone through with the end customer. Supplied with the heat pump on delivery.
Country specific instructions and forms are available where relevant. Supplied with the heat pump on delivery.
Self-adhesive decals with translation text. Must be placed on the manufacturing plate in conjunction with installation. Supplied
with the heat pump on delivery.
The Service instructions and Wiring diagrams are available for download here:
www.documentation.heatpump.danfoss.com
1.2
The instructions contain different warning symbols, which, together with text, indicate to the user that there are risks involved with ac­tions to be taken.
The symbols are displayed to the left of the text and three different symbols are used to indicate the degree of danger:
A fourth symbol is used to give practical information or tips on how to perform a procedure.

Symbols in documents

Danger Indicates an immediate danger that leads to fatal or serious injury if necessary measures are not taken.
Warning Risk of personal injury!
Indicates a possible danger that can lead to fatal or serious injury if necessary measures are not taken.
Caution Risk of installation damage.
Indicates a possible hazard that can lead to item damage if necessary measures are not taken.
Information regarding making the handling of the installation easier or a possible operational technical disad­vantage.

1.3 Symbols on decals

The following symbols can occur on decals on the different parts of the heat pump. Which symbols are used depends on the heat pump model.
4
VMGFJ202 Danfoss Heating Solutions
!
!
3
50
54
55
71
353
362
304
363
365
366
406
62
408
417
Service Instructions

1.3.1 General

DHP-AQ
Warning, danger!
Read the documentation provided.
Read the documentation provided.
Warning, hazardous electrical voltage!

1.3.2 Electrical components

Outdoor unit Outdoor sensor Hot water sensor Hot water top sensor Flow guard Drip tray Shunt valve Circulation pump Exchange valve hot water Supply line sensor Return line sensor
Warning, hot surfaces!
Warning, moving parts!
Warning, risk of crushing injury!
Room sensor
or
EVU Defrost sensor
Explanation
Component, ordinary delivery according to proposed sys­tem solutions
Component, accessorie according to proposed system sol­utions

1.3.3 Pipe connections

Tap water
Heating system
Brine system
Defrosting tank
Expansion tank with safety valve, brine
Air bleeding
Temperature and pressure relief valve
Outdoor unit
Water heater
Danfoss Heating Solutions VMGFJ202
5
Service Instructions DHP-AQ

2 Important information/Safety regulation

2.1 General safety precautions

Warning Risk of personal injury! Children are not permitted to play with the product.
Caution The heat pump must be installed by authorised installation engineers and the installation must follow the
applicable local rules and regulations as well as these installation instructions.
Caution This product is not intended for persons (including children) with reduced physical, sensory or psychological
capacity, or who do not have knowledge or experience, unless supervised or they have received instructions on how the apparatus functions from a safety qualified person.
Caution The heat pump must be located in a frost-free environment!
Caution The heat pump must be placed in an area with a floor drain.
Caution The heat pump must be located on a stable base. The floor must be able to support the gross weight of the
heat pump with filled hot water tank (see Technical data).
Caution To prevent leaks, ensure that there are no stresses in the connecting pipes!
Caution It is important that the heating system is bled after installation.
Caution Bleed valves must be installed where necessary.
Caution The hot water tank must be equipped with an approved safety valve.
Caution Heating systems with closed expansion tanks must also be supplied with approved pressure gauges and safe-
ty valves.
6
VMGFJ202 Danfoss Heating Solutions
N
N
Service Instructions DHP-AQ
Caution Cold and hot water pipes and overflow pipes from safety valves must be made of heat resistant and corro-
sion-resistant material, for example copper. The safety valve overflow pipes must have an open connection to the drain and visibly flow into this in a frost-free environment.
Caution The connecting pipe between the expansion tank and the safety valve must slope continuously upwards. A
continuous upwards slope means that the pipe must not slope downwards from the horizontal at any point.
Caution When cooling it is important to limit the lowest flow line temperature to prevent condensation.
If there is any risk of groundwater infiltration at wall lead-ins for brine pipes, watertight grommets must be used.
In addition to applicable local rules and regulations the installation should be carried out in a manner that prevents vibrations from the heat pump being transmitted into the house causing noise.

2.2 Refrigerant

2.2.1 Refrigerant

Caution Work on the refrigerant circuit must only be carried out by a certified engineer!
Although the heat pump cooling system (refrigerant circuit) is filled with a chlorine-free and environmentally-approved refrigerant that will not affect the ozone layer, work on this system may only be carried out by authorized persons.
2.2.2

Fire risk

The refrigerant is not combustible or explosive in normal conditions.
2.2.3

Toxicity

In normal use and normal conditions the refrigerant has low toxicity. However, although the toxicity of the refrigerant is low, it can cause injury (or be highly dangerous) in abnormal circumstances or where deliberately abused.
Warning Risk of personal injury! Spaces in which heavy vapour can collect below the level of the air must be well venti-
lated.
Refrigerant vapour is heavier than air and, in enclosed spaces below the level of a door for example, and in the event of leakage, concen­trations can arise with a resultant risk of suffocation due to a lack of oxygen.
Warning Risk of personal injury! Refrigerant exposed to a naked flame creates a poisonous irritating gas. This gas can
be detected by its odour even at concentrations below its permitted levels. Evacuate the area until it has been sufficiently ventilated.
Danfoss Heating Solutions VMGFJ202
7
Service Instructions DHP-AQ

2.2.4 Work on the refrigerant circuit

Caution When repairing the refrigerant circuit, the refrigerant must not be released from the heat pump, it must trea-
ted in the appropriate way.
Draining and refilling must only be carried out using new refrigerant (for the amount and type of refrigerant see manufacturer’s plate) through the service valves.
Caution All warranties from Danfoss are void if, when filling with refrigerant other than Danfoss A/S specified refriger-
ant, if there has not been written notification that the new refrigerant is an approved replacement refrigerant together with other remedies.

2.2.5 Scrapping

Caution When the heat pump is to be scrapped the refrigerant must be extracted for disposal. Local rules and regula-
tions related to the disposal of refrigerant must be followed.

2.3 Electrical connection

Warning Hazardous electrical voltage! The terminal blocks are live and can be highly dangerous due to the risk of elec-
tric shock. All power supplies must be isolated before electrical installation is started. The heat pump is con­nected internally at the factory, for this reason electrical installation consists mainly of the connection of the power supply.
Caution Electrical installation may only be carried out by an authorized electrician and must follow applicable local
and national regulations.
Caution The electrical installation must be carried out using permanently routed cables. It must be possible to isolate
the power supply using an all-pole circuit breaker with a minimum contact gap of 3 mm. (The maximum load for externally connected units is 2A).

2.4 Water quality

Caution A normal heating system always contains a certain amount of corrosion particulates (rust) and sludge prod-
ucts from calcium oxide. This comes from acid that is naturally occurring in the fresh water that the system is filled with. It is not good practice to have to fill the heating system regularly which is why any leakage in the heating system should be repaired immediately. Normal filling should occur only once or twice a year. The water in the heating system should be as clean as possible, always position the dirt filter on the return line from the heating system to the heat pump, as close to the heat pump as possible.
Caution Hard water; Normally it is not a problem installing a heat pump in areas with hard water because the normal
operating temperature for the hot water does not exceed 60°C. In areas where there are exceptional prevail­ing conditions with the water one can install a softening filter, which softens the water, cleans any impurities and prevents the build up of calcification.
8
VMGFJ202 Danfoss Heating Solutions
Service Instructions DHP-AQ

2.5 Commissioning

Caution The installation may only be commissioned if the heating system and brine system have been filled and bled.
Otherwise the circulation pumps can be damaged.
Caution If the installation is only to be driven by the immersion heater during the installation, ensure that the heating
system is filled and the brine pump and compressor cannot be started. This is carried out by setting the oper­ating mode to AUX. HEATER.
Danfoss Heating Solutions VMGFJ202
9
Service Instructions DHP-AQ

3 Troubleshooting

3.1 Alarm

In event of alarm this is indicated in the display with the text ALARM and an alarm message, see following table. For alarms that are not reset automatically acknowledgement is required. Acknowledge the alarm by setting the heat pump to operating mode OFF and then back to the desired operating mode.
Message Meaning MOTOR P COMP.ERROR The compressor motor protection has deployed. MOTOR P FAN ERROR The fan motor protection has deployed. EL. HEATER ERROR The electrical heater overheating protection has deployed. HEAT / PRESSURE ERROR The expected pressure and temperature change in the refrigerant circuit has not happened in the
correct way at compressor start. LOW PRESSURE ERROR Evaporation pressure has fallen too low. LOW PRESSURE TRANSDUCER Fault in low pressure transmitter alternatively cable fault. HIGH PRESSURE ERROR High pressure switch has deployed. LOW HEAT CIR. FLOW The flow sensor has registered too low a flow. MAX TEMP ELEC. HW Too high temperature in heat pump junction box/electrical cabinet. NO. OF TRIES X/5(where X=1…5) Circulation pump is jammed. Start attempt made. HEATING CIRC. PUMP Circulation pump is jammed. HEATING SYSTEM PUMP Circulation pump is jammed. OUTDOOR SENSOR Sensor fault alternatively cable fault. DEFROST SENSOR Sensor fault alternatively cable fault. Defrost sensor. SUPPLY LINE SENSOR Sensor fault alternatively cable fault. Supply line sensor. SYSTEM SUPPLY LINE SENSOR Sensor fault alternatively cable fault. System supply line sensor. RETURN LINE SENSOR Sensor fault alternatively cable fault. Return line sensor. HIGH RETURN LINE TEMP Return line temperature too high BUFFER TANK SENSOR Sensor fault alternatively cable fault. HGW SENSOR Sensor fault alternatively cable fault. HOT WATER SENSOR Sensor fault alternatively cable fault (the lower sensor, Start sensor). HOT WATER TOP Sensor fault alternatively cable fault. FAILSAFE MODE Sensor fault alternatively cable fault on one of the refrigerant sensors. The heat pump goes to fail-
safe mode and defrosts on time. REFR.1 SENSOR Sensor fault alternatively cable fault. Refrigerant sensor 1 REFR.2 SENSOR Sensor fault alternatively cable fault. Refrigerant sensor 2 LOW RETURN TEMP 1 The return line temperature is too low to start a defrosting. LOW RETURN TEMP 2 The return line has fallen too low during defrosting. LOW EVAP. TEMP 1 Evaporation temperature too low. LOW EVAP. TEMP 2 Too great a deviation in evaporation temperature average value. SUCTION TEMP SENSOR Sensor fault alternatively cable fault. ROOM SENSOR Sensor fault alternatively cable fault. DISCHARGE PIPE SENSOR Sensor fault alternatively cable fault. DISTR. CIR. 1 SENSOR Sensor fault alternatively cable fault. DISTR. CIR. 2 SENSOR Sensor fault alternatively cable fault. POOL SENSOR Sensor fault alternatively cable fault. COM. ERROR HP-CARD Communication broken between display card and heat pump card (outdoor). COM. ERROR HUB-CARD Communication broken between display card and hub card (indoor).
10
VMGFJ202 Danfoss Heating Solutions
N
11
10
12
13
14
16
15
17
1
2
3
4
5
6
7
8
9
19
18
Service Instructions DHP-AQ
Message Meaning COM. ERROR EXV-CARD Communication broken between display card and expansion valve control card (outdoor). COM. ERROR EXPANSION CARD Communication broken between display card and expansion card (indoor).
In event of alarm the heat pump will if possible supply heating to the house, primarily with the compressor, secondarily with the auxiliary heater. Hot water will stop to indicate that something noteworthy has occurred.

3.2 Components

3.2.1 Outdoor unit

Fig. 1: Components
Position
Name Position Name 1 Electrical cabinet 11 Electronic expansion valve 2 Fan 12 Receiver 3 Pressure transmitter 13 Drying filter 4 Suction line 14 Heat exchanger 5 Compressor 15 Flow sensor 6 High pressure switch 16 Heating system supply line
Danfoss Heating Solutions VMGFJ202
11
1
1
2
3
4
1
2
4
3
5
Service Instructions DHP-AQ
Position Name Position Name 7 Operating pressure switch 17 Return line heating system 8 Four-way valve 18 Solenoid 9 Discharge pipe 19 Non-return valve 10 Air heat exchanger

3.2.2 Indoor unit

DHP-AQ Mini
DHP-AQ Maxi
1. Control module (transparent in image)
2. Immersion heater
DHP-AQ Midi
3.3

Measurement points

Caution When reading the resistance of the sensors, the sensor leads must first be disconnected from the control
equipment.
3. Reversing valve
4. Circulation pump
5. Water heater
°C Outdoor / Defrost sensor
-30 1884
-25 1443
12
150 ohm, Ω
VMGFJ202 Danfoss Heating Solutions
PT1000 sensor 1000 ohm, Ω
Other sensors 22 kilo ohm, kΩ
N
Service Instructions DHP-AQ
°C Outdoor / Defrost sensor
150 ohm, Ω
PT1000 sensor 1000 ohm, Ω
Other sensors 22 kilo ohm, kΩ
-20 1115
-15 868
-10 681
-5 538 – 0 428 1000 66,3 5 343 52,4 10 276 1039 41,8 15 224 33,5 20 183 1078 27,1 25 150 22,0 30 124 1117 18,0 35 103 14,8 40 86 1155 12,2 45 10,1 50 1194 8,5 55 7,1 60 1232 6,0 65 5,0 70 1271 4,2 75 3,7 80 3,1 85 2,7

3.3.1 Measurement checking sensors during fault tracing

1. Disconnect the relevant sensor from I/O-card/terminal block.
2. Measure the resistance for the sensor and any extension cables.
3. Then measure the sensor only.
To ensure the sensor value the actual temperature must be checked against the measured resistance.
Danfoss Heating Solutions VMGFJ202
13
7
8
9
7
Service Instructions DHP-AQ

3.3.2 Positioning sensors

DHP-AQ Maxi
Heat pump
1. DISCHARGE PIPE SENSOR
2. SUCTION TEMP SENSOR
3. REFR.1 SENSOR
4. REFR.2 SENSOR
5. DEFROST SENSOR (located to rear beside air intake)
6. OUTDOOR SENSOR (positioned on wall to north)
7. SUPPLY LINE SENSOR
8. HOT WATER TOP
9. HOT WATER SENSOR
RETURN LINE SENSOR - Located on return pipe that runs to heat pump. See sys­tem solution in the Installation instructions.
DHP-AQ Midi

3.4 Check points

Temperatures
Condensing temperature: 0.5 – 1.5 °C above supply line temperature Evaporation temperature: 7 - 8 °C Radiator circuit: 8°K temperature difference Overheating R407C: 4K ±1 K
14
VMGFJ202 Danfoss Heating Solutions
Service Instructions DHP-AQ
Pressure switch/pressure transmitter Refrigerant R407C
OP (operating pressure switch) 2.85 MPa High pressure switch 3,10 MPa Pressure transmitter low pressure 0.04 MPa
Following parameters can be read off in the display:
Suction gas temperature
Evaporation pressure
Evaporation temperature (calculated from ”Dew point”)
Opening percent EXV
Superheating
This means new opportunities to diagnose the heat pump, without having to remove the covers when working on the cooling circuit.
In normal operation the heat pump operates with superheating of 5.5°C – 7°C, the expansion valve's degree of opening will vary
depending on operating situation. At outdoor temperatures of -5°C or lower the opening degree is below 20%
At outdoor temperatures of +5C to +13°C the opening degree is around 40-50%
When cooling (A35W18) the degree of opening is 100%
Caution If superheating is >9°C and the degree of opening of the expansion valve lies steady at 100% this can indicate
that a significant part of the refrigerant has leaked from the heat pump.
If this is the case, the heat pump must be checked by service technicians with personal refrigeration certificates!
Break pressure

3.5 Operational problems

The tables list the most probable and common causes of the problem first. When troubleshooting the cause of a problem start with the first cause and go down the list. There may be more than one way of troubleshooting a cause where the most probable is given first.
3.5.1
Problem – Alarm LP (lower pressure transmitter)
Cause
1. Cable break or loose cable to lower pressure transmit­ter.
2. The pressure transmitter opens too soon.
3. Lack of refrigerant, not enough refrigerant in the system.

Alarm

Troubleshooting Remedy
Check that both cables are connected to the lower
pressure transmitter. Using the buzzer, check that there are no cable
breaks. In order to do this, disconnect the cables from the lower pressure transmitter and circuit board.
Pressure transmitter fault, opens at a higher pressure than indicated. Check break pressure using the manometer ap­paratus.
Using manometer apparatus and thermometer, check that the unit’s overheating is correct for the specific refrigerant.
If a cable has come loose, reconnect it. If there is a cable break, replace the cable.
If the pressure transmitter breaks too early, replace it.
Follow the correct procedure (depending on type of refrigerant) to add the correct amount of refrigerant. If there appears to be a leak in the refriger­ant circuit, carry out leak tracing and any necessary corrective action.
Danfoss Heating Solutions VMGFJ202
15
Service Instructions DHP-AQ
Cause Troubleshooting Remedy
4. Drying filter blockage. Check the temperature difference above the drying filter. A difference of max 1°C is permissible. If the difference is greater, the filter is blocked. Take a reading during opera­tion.
5. Blocked evaporator on
the refrigerant side.
Problem – Alarm HP (high pressure switch)
Cause Troubleshooting Remedy
1. Air in the heating system. Listen for air in the heat pump and heating system. Bleed the heating system according to the
2. Blocked strainer in the
heating system.
3. Closed or partially closed
thermostats/valves in the heating system.
4. The circulation pump that
is defective or has jammed.
Using manometer apparatus and thermometer, check that the unit’s overheating is correct for the specific refrigerant.
Check that the strainer is not blocked. Clean the strainer if necessary.
Check that the thermostats/valves in the heating system are open.
Is there voltage and 0 – 10V signal (applies to A classed cir­culation pumps) up to the circulation pump?
If the drying filter is sealed, replace it.
If the evaporator is thought to be blocked by oil for example, try blowing nitrogen through it to release the oil. If this does not work, it must be replaced
installation instructions.
Open closed thermostats/valves.
Check that the circulation pump is active in the control system’s manual test menu. Check if there is voltage to the circulation pump, if there is, and it does not run, the circulation pump is jammed. If this is the case, open the bleed screw and try to re­lease the paddle wheel using a screwdriver for example (Does not apply to heat pumps in not valid ).
5. Shut-off main tap in heat-
ing system.
6. Cable break or loose cable
to high pressure switch.
7. The high pressure switch
does not open.
If there is no voltage to the circulation pump, check if there is voltage from the I/O card, see wiring diagram. If there is voltage from the I/O card, check the components between the I/O card and the circulation pump.
If a component is defective, replace it.
Check that the main tap is open. Open closed main tap.
Check that both cables are connected to the pressure
switch. Using the buzzer, check that there are no cable
breaks. In order to do this, disconnect the cables from the pressure switch and circuit board.
Incorrect pressure switch installed. Same or higher
break pressure than the high pressure switch. See marking.
Pressure switch fault, opens at a higher pressure than
indicated (mark pressure). Check using the manome­ter apparatus.
Defective pressure switch, never opens.
If a cable has come loose, reconnect it. If there is a cable break, replace the cable.
If the high pressure switch does not open, replace it.
16
VMGFJ202 Danfoss Heating Solutions
Service Instructions DHP-AQ
Cause Troubleshooting Remedy
8. The high pressure switch opens too soon.
Incorrect pressure switch installed. As low or lower
break pressure than operating pressure switch. See marking.
Pressure switch fault, opens at a lower pressure than
indicated (mark pressure). Check using the manome­ter apparatus.
Defective pressure switch, always open.
If the high pressure switch opens too soon or is always open, replace it.
9. External system shunt that closes on time setting.
10. Incorrectly facing non­return valve with too high opening pressure.
11. Large pressure drop in the heating system.
12. Blocked condenser on the water side.
Check for shunts or valves in the system, which are timer­controlled, that close down the entire or too large a part of the heating system.
Check the system’s direction of flow and that the non-
return valve is turned the correct way. Check that the heat pump’s external available pres-
sure exceeds the non-return valve’s opening pressure.
Dirt in the heating system.
Closed or partially closed thermostats/valves in the
heating system. Under dimensioned pipe system. Check that the HP’s
external available pressure exceeds the system pres­sure drop.
If there is no strainer in the heating system, there is a risk of dirt sticking in the condenser and blocking it. Unfortu­nately there is no easy way of checking if the condenser is blocked. You can carry out a test by allowing the compressor and circulation pumps to remain in operation and after a while, check that the pressure pipe becomes hot and that the cir­culation pumps work (for circ.pumps with a bleed screw, unscrew it and feel if the pump rotor rotates using a screw­driver).
Always ensure that there is a sufficiently large water volume for the heat pump to work against, i.e. for the heat to give off its heat to.
If the non-return valve is facing the wrong way, turn it. If the non-return valve has too great an opening pressure, replace it.
If necessary, clean/flush the heating system. Open closed thermostats/valves.
If there is not sufficient pressure equip­ment, the heating system can be adjusted according to the system solution for large pressure drop.
If the condenser is thought to be blocked, try flushing it. If this does not work, it must be replaced
Then read the temperature on both connection pipes to the condenser:
If the temperature difference is <3°C, the condenser is probably blocked.
If the temperature difference is 3-13°C, it is probably not blocked.
If the temperature difference is >13°C, the condenser is probably blocked.
13. Blocked condenser on the refrigerant side.
14. Overfilled refrigerant cir­cuit.
Danfoss Heating Solutions VMGFJ202
Using manometer apparatus and thermometer, check that the unit’s overheating is correct for the specific refrigerant.
Using manometer apparatus and thermometer, check that the unit’s overheating is correct for the specific refrigerant.
If the condenser is thought to be blocked by oil for example, try blowing nitrogen through it to release the oil. If this does not work, it must be replaced
Follow the correct procedure (depending on type of refrigerant) to add the correct amount of refrigerant. If there appears to be a leak in the refriger­ant circuit, carry out leak tracing and any necessary corrective action.
17
Service Instructions DHP-AQ
Problem – Alarm (motor protection)
Cause Troubleshooting Remedy
1. Phase drop or blown fuse. Check the fuses in the fuse box. Check that all phases are present on the terminal block for incoming supply. Also check that all wiring is secure, if screw terminals are used they must be properly tightened, if phoenix flat spring ter­minals are used, the cables must be secure in the correct hole with load on the cable.
2. Cable break. Check the supply to the motor protection, soft-starter or compressor.
3. Defective soft-starter
(three-phase heat pump).
4. Defective soft-starter (sin-
gle phase heat pump).
5. Defective or incorrectly
set motor protection.
6. Defective compressor. Measurement check the voltage on the phase(s) (each to
7. Alarm from single phase
soft starter.
Measurement check and establish that when the Heat pump card gives a signal (there must be voltage between A1 & A2 on the soft-starter), the soft-starter releases all three phases down to the compressor.
Check measure and establish that when the Heat pump card gives a signal (there must be voltage between ON and N on the soft-starter), the soft-starter releases the pha­ses to the compressor.
Use a hook-on meter to establish when the motor protec­tion deploys, check what the motor protection is set to.Compare with the table. For three phase heat pumps all three phases must be supplied.
zero) at the compressor. There must not be any large devi­ation between the phases. If measurement checking the winding’s resistance the same value must be on one to three windings.
Check the fault cause using the soft start LEDs.
If any of the phases are missing, check backwards towards the building’s main electrical cabinet. If there are no phases there, contact the network supplier.
If a cable is damaged, replace it.
If the soft-starter does not release the pha­ses when it receives signals from the heat pump card, replace it.
If the soft-starter does not release the pha­ses when it receives signals from the heat pump card and does not alarm as below, replace it.
If the motor protection is defective, replace it. If incorrectly set, adjust to the correct value.
If the compressor is defective, replace it.
Problem – Alarm sensor (all)
Cause Sensor fault alternatively ca-
ble fault.
Problem – Error phase sequence
Cause The incoming phases have
the incorrect sequence (only applies to 3-phase heat pumps), appears after a mi­nute when the compressor is started.
Troubleshooting Remedy
Troubleshooting Remedy
When reading the resistance of the sensors, the sen-
sor leads must first be disconnected from the control equipment or terminal block.
First take a reading from the sensor including cable
and check against the ohm table in Measurement points .
If the read off value does not correspond with the ta-
ble, only measure the sensor and check the ohm table in Measurement points .
If the text HEAT / PRESSURE ERROR is displayed it can
mean that the phases are in the incorrect order. When the compressor is running, check the pressure
pipe temperature by feeling the pressure pipe. If the phases are correctly sequenced it should be hot (not just warm) even a distance from the compressor.
When the compressor runs with the phases incorrect-
ly sequenced a strange noise may be heard (loud, rat­tling) when the compressor runs backwards.
If the sensor gives a correct value, the cable is defective. If the sensor does not give a correct value, the sensor is defective.
If the phases are in the incorrect order, switch two incoming phases at the main terminal block and recheck according to the troubleshooting window.
18
VMGFJ202 Danfoss Heating Solutions
Service Instructions
Problem – Alarm electric heater error
Cause Troubleshooting Remedy
1. The overheating protec­tion has tripped.
2. Phase drop. The alarm occurs when 230 V is not registered between L2 on the circuit board and N. Does not apply if MAX STEP = P.
3. Overheating protection fault, cannot be reset.
4. Flow sensor fault. Check what the flow sensor shows. Is it a plausible/actual
5. No or insufficient circula­tion in the heating system.
Check if the overheating protection has tripped. If the overheating protection has tripped,
Check if the overheating protection has tripped.
Check if any cables at the circuit board or overheating
protection are loose or damaged.
Press the reset button, measurement check for 230 V on the incoming and outgoing connections.
value? Measure the resistance of the sensor, check against the ohm table in Measurement points .
Check:
That the circulation pump spins
That the shut-off valves are open.
That the strainer is not blocked.
That there is no air in the heating system.
DHP-AQ
reset it. If the overheating protection has tripped,
reset it. If the cables are loose or damaged, secure or replace them.
If the overheating protection is defective, replace it.
If the sensor is defective, replace it.
The circulation pump may have jammed. If so, open the bleed screw and try to release the paddle wheel using a screwdriver for example. Open closed valves or taps.
Check, and, if necessary, clean the strainer.
Problem – Alarm circulation pump
Cause The circulation pump’s inte-
grated alarm has deployed. (Only applies to not valid )
Troubleshooting Remedy
Air in the heating system. Has the circulation pump jammed?
If necessary, bleed the heating system ac­cording to the installation instructions
Vent the heating system and TWS coil.
If the circulation pump has jammed, there is an integrated shake function that at­tempts to shake itself loose up to a maxi­mum of 5 times, if it does not succeed, an alarm will occur.
Try cutting the voltage to the heat pump to stop the alarm and then manually run the circulation pump.If the alarm recurs, repeat the procedure several times. If this does not help, replace the circulation pump.
Danfoss Heating Solutions VMGFJ202
19
Service Instructions DHP-AQ
Problem – Operating pressure switch open alternatively high hot gas temperature
Cause Troubleshooting Remedy
1. Operating pressure
switch, function.
2. Fault in the discharge
pipe sensor.
3. Hot gas temperature too
high.
4. Lack of refrigerant, not
enough refrigerant in the system.
1. Switch off the main switch for the heat pump, wait until the compressor has been stationary for at least 15 minutes.
2. Disconnect the two cables on the pressure switch, us­ing a buzzer check if the pressure switch is closed.
Check what the discharge pipe sensor shows. Is it a plausi­ble/actual value? Measure the resistance of the discharge pipe sensor, check against the ohm table in Measurement points .
The discharge pipe sensor displays more than 140°C. See operating data.
Using manometer apparatus and thermometer, check that the unit’s overheating is correct for the specific refrigerant.
If the pressure switch is closed, bridge the pressure switch cables temporarily and switch on the voltage to the heat pump again. If there is an indication 0 (zero) in the display this means that the pressure switch is fault-free and the problem is in the wiring or in the circuit board. If the pressure switch is open, try carefully tapping the head of the pressure switch with a screwdriver and use a buzzer test to see if it has closed again.
Replace the pressure switch if it appears to jam repeatedly.
If the discharge pipe sensor is defective, re­place it.
The square symbol appears when the deliv­ery pipe temperature is as high or greater than the maximum temperature of the dis­charge pipe 140°C.
Follow the correct procedure (depending on type of refrigerant) to add the correct amount of refrigerant. If there appears to be a leak in the refriger­ant circuit, carry out leak tracing and any necessary corrective action. If leak tracer is not available, brush soap water on the sus­pected leak and look for bubbles. Also check for oil as this can come out from the refrigerant circuit.

3.5.2 Leakage

Problem – Leak fluid side
Cause
1. Insufficiently tightened connections.
2. Defective gasket or O­ring.
3. Cracked nut or connec­tion.
4. There is no overflow pipe connected to the safety valve(s).
5. Filler valve between in­coming cold water and heating system not closed or leaking.
20
Troubleshooting Remedy Locate the leak.
Locate the leak. Replace the gasket or O-ring.
Locate the leak. Replace nut or connection.
Establish which safety valve does not have an overflow pipe.
Check whether water continuously leaks from the safety valve on the expansion vessel on the hot side.
VMGFJ202 Danfoss Heating Solutions
Tighten the connection and check that
it is sealed. If it is still not sealed, replace the entire
connection and support sleeve (only at soft pipes).
Install an overflow pipe according to the applicable norms.
Try closing the filler valve and see if water stops dripping from the safety valve. If not, replace the filler valve.
Service Instructions DHP-AQ
Cause Troubleshooting Remedy
6. Leak at soldered joints. Locate the leak. Drain the system of fluid, repair the leak.If the leak is on the connection pipe to the heat exchanger, also drain the refrigerant side.
7. Associated leakage in the
condenser.
Check for lack of refrigerant in the unit.
Check by smelling at the safety valve on the hot side,
open the valve and check.
If the condenser has a leak, replace it.
8. Leak at soldered joint on
water heater (only applies to DHP-AQ Maxi DHP-AQ Maxi)
9. Associated leakage on
plate heat exchanger (only applies to DHP-AQ Maxi DHP-AQ Maxi)

3.5.3 Noise

Problem – Noise problem in the radiator system
Cause
1. Flexible hoses missing. Flexible hoses must be installed according to the instruc-
2. Incorrectly installed flexi-
ble hoses.
3. Installing/suspending
pipes.
4. Circulation noise (whis-
tling noise in the heating system).
5. Clicking.
Locate the leak. If there is a leak at the soldered joint, re-
Check for lack of refrigerant in the unit
Check by smelling at the safety valve on the hot side,
open the valve and check.
Troubleshooting Remedy
tions. Flexible hoses must be installed according to the instruc-
tions. Check if vibrations are transmitted via one of the pipe
mountings in the installation. Check the heating system.
Closed valves, choke valves, adjuster valves or other
restrictions in the radiator system can cause circula­tion noise.
Is the heating system correctly adjusted for flow?
Too great a flow in the heating system can cause cir-
culation noise.
Check that the volume tank is installed and has the
correct dimensions for the relevant system. See the installation instructions.
Establish when clicking occurs, during heating and/or
in connection with completed hot water production? Locate the clicking noises.
place the water heater.
If there is leakage, replace plate heat ex­changer.
Install flexible hoses according to the in­structions.
Install flexible hoses according to the in­structions.
Remove or move the mounting point or in­stall vibration isolating mounting parts.
If the incorrect type of valve is used to choke the flow, replace with the correct type. If the heating system is not correctly adjus­ted, make adjustments.
Can the heating system be run at a lower flow?
A surge tank can be installed on the supply line to mix the hot water with the existing, slightly cooler, water, before it goes out to the radiators. Try lubricating lead-ins in walls, ceilings and floors with silicone spray.
Danfoss Heating Solutions VMGFJ202
21
Service Instructions DHP-AQ
Problem – Loud compressor noise
Cause Troubleshooting Remedy
1. Phase drop. The compressor attempts to start or operates on two phases (only applies to 3 phase heat pumps) .
1. Check that there is 400 V between incoming phases on the heat pump.
2. If there is supply to the heat pump, measure the volt­age for all electrical components all the way to the compressor, see wiring diagram.
Check where the phase drop is and rectify.
2. Touching pipes – vibra­tions.
3. Compressor fault Determine whether the compressor is unusually loud.
Problem – Shrieking, whistling noise
Cause
1. Noise from the soft-start­er.
2. The compressor’s safety valve opens.
Problem – Noise – miscellaneous
Cause
1. Vibrating protective sleeves on the pressure switches.
2. Vibration noise from the electrical installation.
Establish which pipe(s) is/are causing the problem. Try to remove the contact:
Check with a voltmeter at a point before and after the
soft starter. The measurement values should not dif­fer.
Troubleshooting Remedy Measurement check the input and output phases for the
soft-starter as well as the control signals from the heat pump card, see wiring diagram.
The compressor has an integrated safety valve that opens when the pressure difference between high and low pres­sure sides is too large. A whistling sound can be heard dur­ing pressure equalisation. Use a manometer to check at which pressure differential pressure equalisation occurs.
Troubleshooting Remedy Establish where the vibration noise is coming from. Prevent the protection sleeve vibrating by
Check for electrical steps or similar devices screwed to the heat pump and wall. These can cause vibrations and noise.
If the compressor is defective, replace it.
If the soft-starter is defective, replace it.
Replace the compressor if the valve opens at too low pressure or when the compres­sor is stationary.
using insulation tape for example.
Carry out according to the installation in­structions.

3.5.4 Hot-water

Problem – Temperature and/or quantity
Cause
1. Defective 3-way valve mo­tor.
2. Jammed reversing valve. The valve is not secure and releases hot water to the ra­diators during hot water production.
3. Air in TWS coil or water outer jacket.
4. Start temperature set too high for hot water produc­tion.
22
Troubleshooting Remedy Check the function of the reversing valve by test running it
manually. Detach the motor and test closing and opening the valve
by turning the shaft by hand.
During hot water production:
Check that the start temperature is correctly set. Should not be set above the factory set value.
Listen for air. Check the temperature difference between supply
and return line.
VMGFJ202 Danfoss Heating Solutions
If the motor is defective, replace it.
If it jams, replace with a new one.
Bleed the system. A Large temperature difference can indi­cate air in the system.
If the start value is set too high, reduce
it to the factory set value.
Service Instructions
Cause Troubleshooting Remedy
5. Sensor fault, hot water sensor. Hot water production is star­ted by the hot water sensor.
6. Large drain flow (>12 l/ min).
Check what the hot water sensor (the start sensor) shows. Is it a plausible/actual value? Measure the resistance of the sensor, check against the ohm table in Measurement points .
Check how many litres of hot water (approx. 40°C) per mi­nute drains from the tap.Use a clock and bucket to meas­ure the drain flow.
DHP-AQ
If the sensor is defective, replace it.
If the drain water flow is greater than 12 l/ min, stratification in the water heater is af­fected, which reduces the hot water capaci­ty. Suggested corrective actions:
Install a pressure reduction valve on the incoming cold water pipe.
Change to a mixer with lower flow. Adjust the drain flow on the existing
mixer, do not open the tap fully.
7. Water heater too small in relation to requirement.
8. The operating pressure switch opens too soon (at too low a pressure). Hot water production ends when the operating pres­sure switch opens.
9. Insufficient exchange sur­face to transfer the heat pump’s output to the heat­er.(Only applies to heat pumps with a separate heat­er.)
10. Heat loss in the hot wa­ter pipe.
How large is the requirement and what is the capacity of the heater?
Check the break pressure using manometer apparatus. If the pressure switch opens at the incorrect
Is the exchange surface too small? Can the heater cope with the heat pump’s output?
Open the hot water tap, read off the temperature on the outgoing hot water pipe from the heat pump and the tem­perature of the hot water. The temperature difference measured between the heat pump and hot water indicates the temperature loss. Examples of temperature loss causes:
Long water pipes.
Uninsulated hot water pipes.
Hot water pipes routed through cold areas.
Other causes that can affect the hot water temperature:
Is a mixer valve installed in the system? Temperature
set too low on the mixer valve? Leaking mixer valve? Water tap fault? Leaking thermostat mixer?
VVC loss.
Replace with a larger heater or supplement with an extra heater. E.g. supplement with an DWH DWH or an electric heater.
pressure, replace it. The replacement pressure switch can be in­stalled on the service output (Schrader valve).
Replace with a heater with a larger ex­change surface.
If any problems occur during troubleshoot­ing as per the points, carry out corrective actions. To quickly check that the heat pump’s hot water production works as it should, drain the hot water so that the heat pump starts to produce the hot water. When done, read off the temperature on the top sensor and on the start sensor. The top sensor should show a temperature of around 50 - 55°C and the start sensor around 45 - 48°C. If, af­ter completed hot water production, these temperatures are obtained, this means that you have the correct temperature and vol­ume of hot water in the water heater.
Danfoss Heating Solutions VMGFJ202
23
Service Instructions DHP-AQ

3.5.5 Heating comfort

Problem – Too cold
Cause Troubleshooting Remedy
1. The heat pump’s control computer is not set/adjus­ted to the customer’s re­quirements/wishes.
2. Incorrect operating mode set in the heat pump’s con­trol computer.
3. Sensor fault, OUTDOOR/ ROOM/SUPPLY LINE/ RETURN LINE.
4. The 3-way valve has jam­med in hot water mode.
Check the ROOM and CURVE and MAX settings. Adjust incorrect values in the heat pump’s
control computer. ROOM = Desired indoor temperature
CURVE = Should be set so that the desired indoor temperature (ROOM) is maintained regardless of the outdoor temperature.
MAX = Highest set-point value on the sup­ply line regardless of the outdoor tempera­ture.
Check which operating mode is set. If the incorrect operating mode is set,
change to the desired operating mode.
Check what the relevant sensor shows. Is it a plausible/ actual value? Measure the resistance of the sensor, check against the ohm table in Measurement points .
1. Check the function of the 3-way valve motor by test running it manually. If the motor does not shift mode during manual test operation, check that there is volt­age to the motor, see wiring diagram.
2. Detach the motor and test closing and opening the valve by turning the shaft by hand.
If the sensor is defective, replace it.
Is the motor being supplied with voltage according to the wiring diagram in both operating instances?MANUAL TEST – REV.V. HOT WATER 0=Radiator mode1=Hot water modeIf there is voltage to the motor but it does not shift mode, replace it.
5. Defective electric heating element.
6. The heat pump has stop­ped on HIGH RETURN.
7. Heat production is stop­ped by the HYSTERESIS function.
Use a buzzer and check if all coils in the electric heating el­ement are intact.
Check what the MAX RETURN value is set at in the
heat pump’s control computer. It must be adjusted to the unit’s maximum supply temperature and the sys­tem’s delta temperature so that it does not cut at too high a return temperature when the highest supply temperature is transmitted.
Check what the return line sensor shows. Is it a plausi-
ble/actual value? If not, take a resistance reading from the sensors and check against the ohm table in Meas­urement points .
If the flow temperature rises as soon as heat production is stopped by HYSTERESIS before INTEGRAL reaches 0, there may be heating deficit in the house.
Check if heat production stops because the hysteresis
value is set too low? (See the installation instructions for factory setting.)
Check if heat production stops because thermostats/
valves in the heating system are closed or partially closed?
Check if heat production stops because the heating
system is under dimensioned?
If the electric heating element is defective, replace it.
If the MAX RETURN value is not adjusted for the system according to the troubleshoot­ing window, adjust it. If the sensor is defective, replace it.
Try increasing the hysteresis value un-
til the heat pump stops on INTEGRAL instead.
Open thermostats/valves in the heat-
ing system and check that the heat pump stops on INTEGRAL.
If the heating system is deemed to be
under dimensioned, the system must be extended (the heat emitting sur­face increased).
24
VMGFJ202 Danfoss Heating Solutions
Service Instructions DHP-AQ
Cause Troubleshooting Remedy
8. The auxiliary heater is not permitted to cut in with suf­ficient output. Value set too low on MAX­STEP.
MAXSTEP 1 = 3 kW
MAXSTEP 2 = 6 kW
MAXSTEP 3 = 9 kW
Check the set value on MAXSTEP in the heat pump’s con­trol computer.
If necessary, adjust the MAXSTEP value in the heat pump’s control computer.230V 1­N MAXSTEP 1 – 3400 V 3-N: MAXSTEP 1 – 5 MAXSTEP 1 = 3 kW
MAXSTEP 2 = 6 kW
MAXSTEP 3 = 9 kW
MAX STEP 4 = 12 kW (cannot cut in when the compressor is running.)
MAXSTEP 4 = 12 kW
MAXSTEP 5 = 15 kW
9. The external auxiliary heater does not start when the heat pump’s control computer requests it.
10. Closed or partially closed thermostats/valves in the heating system.
11. The total output of the heat pump and auxiliary heater is too low in relation to the building’s power de­mand.
12. Under dimensioned heating system.
13. Changed conditions Have you increased your heating and/or hot water demand?
If an external auxiliary heater is used, check that it is cor­rectly installed by test running it in MANUAL TEST – EXT.AUX.HEATER - 1. If it does not start at manual test operation, check that the start signal/voltage comes from the heat pump. See wiring diagram.
Check that the thermostats/valves in the heating system are open.
What is the building’s power demand? What is the output of the heat pump?
What is the output of the auxiliary heater, what is it set to? Check existing heating system.
What output is it dimensioned for to produce at what sup­ply temperature?
What output is required to keep the room warm?
If the heat pump has been dimensioned for a certain
demand and this demand is increased, the heat pump might not be able to maintain the desired room tem­perature.
If hot water consumption increases, a larger propor-
tion of time is used to produce hot water, which means less time for heat production (only applies to system solution 1).
MAX STEP 5 = 15 kW (cannot cut in when the compressor is running.)
Connect the external auxiliary heater ac­cording to the instructions. Measure the voltage on the I/O card’s probe L2 Oil/Electricity.
Open closed thermostats/valves.
Ensure that available power is at least as great as the building’s power demand.
If the heating system is dimensioned for greater supply temperatures than the heat pump can provide, it must be adjusted by increasing the heat emitting surface for ex­ample. If the room requires a higher output than the heating system can provide, extend the heating system.
If the heat pump cannot cope with the de­mand, replace it with one with a higher output or supplement it with a higher out­put auxiliary heater.
Danfoss Heating Solutions VMGFJ202
25
Service Instructions DHP-AQ
Problem – Too hot
Cause Troubleshooting Remedy
1. The heat pump’s control computer is not set/adjus­ted to the customer’s re­quirements/wishes.
2. Sensor fault, OUTDOOR/ ROOM/SUPPLY LINE.
3. Defective 3-way valve mo­tor. The motor should set the valve to the relevant posi­tion depending on operat­ing conditions. If it does not, hot water from the water heater will mix with the radi­ator water.
Check the ROOM and CURVE and MIN settings. Adjust incorrect values in the heat pump’s
control computer. ROOM = Desired indoor temperature.
CURVE = Should be set so that the desired indoor temperature (ROOM) is maintained regardless of the outdoor temperature.
MIN = Lowest set-point value on the supply line regardless of the outdoor temperature.
Check what the relevant sensor shows. Is it a plausible/ actual value? Measure the resistance of the sensor, check against the ohm table in Measurement points .
Check the function of the 3-way valve motor by test run­ning it manually. If the motor does not shift mode during manual test operation, check that there is voltage to the motor, see wiring diagram.
If the sensor is defective, replace it.
Is the motor being supplied with voltage according to the wiring diagram in both operating instances? MANUAL TEST – REV.V. HOT WATER
0=Radiator mode
1=Hot water mode
4. Jammed reversing valve. If the valve is not sealed, hot water from the water heater will mix with the radiator water.
Detach the motor and test closing and opening the valve by turning the shaft by hand.
If there is voltage to the motor but it does not shift mode, replace it.
If it is sluggish or jams, replace with a new one.
26
VMGFJ202 Danfoss Heating Solutions
Service Instructions DHP-AQ
Problem – Irregular indoor temperature
Cause Troubleshooting Remedy
1. The heat pump’s control computer is not set/adjus­ted to the customer’s re­quirements/wishes.
Check the ROOM and CURVE, MIN, MAX CURVE5, CURVE0, CURVE-5 and HEAT STOP settings.
Adjust incorrect values in the heat pump’s control computer. ROOM = Desired indoor temperature
CURVE = Should be set so that the desired indoor temperature (ROOM) is maintained regardless of the outdoor temperature.
MIN = Lowest set-point value on the supply line regardless of the outdoor temperature (on the condition that heat stop does not apply).
MAX = Highest set-point value on the sup­ply line regardless of the outdoor tempera­ture.
CURVE5,0,-5 =The supply temperature can be adjusted up or down 5°C at these out­door temperatures.
2. Incorrectly positioned/ installed sensors.
Check that outdoor sensors and any room sensors are in­stalled according to the instructions and that they are cali­brated.
HEAT STOP = Stops all production of heat when the outdoor temperature is the same as or greater than the set value. To exit heat stop the outdoor temperature must drop to 3°C below the set value.
Check that the room sensor is posi-
tioned in a suitable place that is repre­sentative of the building and calibrate it if necessary. Avoid placing near ex­ternal doors, windows and heat sour­ces.
Install the outdoor sensor according to
the instructions and calibrate it, if nec­essary.
Danfoss Heating Solutions VMGFJ202
27
Service Instructions DHP-AQ

3.5.6 Other

Problem – The heat pump runs and runs but never stops
Cause Troubleshooting Remedy
1. Air in the heating system. Listen for air in the heat pump and heating system. Bleed the heating system according to the installation instructions.
2. Changed conditions Have
you increased your heating and/or hot water demand?
If the heat pump has been dimensioned for a certain
demand and this demand is increased, the heat pump might not be able to maintain the desired room tem­perature.
If hot water consumption increases, a larger propor-
tion of time is used to produce hot water, which means less time for heat production.
If the heat pump cannot cope with the de­mand, replace it with one with a higher output or supplement it with a higher out­put auxiliary heater.
3. Lack of refrigerant, not
enough refrigerant in the system.
Problem – Runs on electric heating element
Cause
1. Operating mode AUX.
HEATER is selected.
2. The compressor cannot
run due to an alarm.
3. The integral value has
reached the start level for the auxiliary heater.
4. Peak heat operation (anti-
legionella function) is run­ning.
5. The heat pump has stop-
ped on HIGH RETURN.
Using manometer apparatus and thermometer, check that the unit’s overheating is correct for the specific refrigerant.
Troubleshooting Remedy If this operating mode is selected, the auxiliary heater is
used for heating and hot water production, not the com­pressor.
Check the alarm that is indicated in the display. Rectify the problem and rest the alarm. See
Check what the integral value is in the control system. If the auxiliary heater is in operation be-
Check if the heat pump runs peak heat. Peak heat operation occurs in connection
Check what the MAX RETURN value is set at in the
heat pump’s control computer. It must be adjusted to the unit’s maximum supply temperature and the sys­tem’s delta temperature so that it does not cut at too high a return temperature when the highest supply temperature is transmitted.
Check what the return line sensor shows. Is it a plausi-
ble/actual value? If not, take a resistance reading from the sensors and check against the ohm table in Meas­urement points .
Follow the correct procedure (depending on type of refrigerant) to add the correct amount of refrigerant. If there appears to be a leak in the refriger­ant circuit, carry out leak tracing and any necessary corrective action. If leak tracer is not available, brush soap water on the sus­pected leak and look for bubbles. Also check for oil as this can come out from the refrigerant circuit.
If AUX. HEATER mode is selected and you no longer want it, change to AUTO, the heat pump then controls both the com­pressor and auxiliary heater.
Alarm .
cause the integral value has counted down to the start value, the computer reacts as it should, see the Installation instructions for further information.
with hot water production with the set in­terval. The compressor should then start to produce hot water and 2 minutes later the auxiliary heater starts. The compressor must then stop and the stop temperature be reached with only the auxiliary heater connected. Take no corrective action.
If the MAX RETURN value is not adjusted for the system according to the troubleshoot­ing window, adjust it. If the sensor is defective, replace it.
28
VMGFJ202 Danfoss Heating Solutions
Service Instructions DHP-AQ
Cause Troubleshooting Remedy
6. The compressor runs backwards.The incoming phases have the incorrect sequence (only applies to 3­phase heat pumps). If the compressor runs back­wards, it will not cope with compressing the refrigerant and therefore does not pro­duce the correct power, which leads to the control system requesting auxiliary heating.
7. Changed conditions Have you increased your heating and/or hot water demand?
If the text ERR PHASE SEQ. appears in the display
when the heat pump is powered, (only appears in the first 10 minutes) this means that the phases have the incorrect sequence.
When the compressor is running, check the pressure
pipe temperature by feeling the pressure pipe. If the phases are correctly sequenced it should be hot (not just warm) even a distance from the compressor.
When the compressor runs with the phases incorrect-
ly sequenced a strange noise may be heard (loud, rat­tling) when the compressor runs backwards.
If the heat pump has been dimensioned for a certain
demand and this demand is increased, the heat pump might not be able to maintain the desired room tem­perature.
If hot water consumption increases, a larger propor-
tion of time is used to produce hot water, which means less time for heat production.
If the phases are in the incorrect order, switch two incoming phases at the main terminal block and recheck according to the troubleshooting window.
If the heat pump cannot cope with the de­mand, replace it with one with a higher output or supplement it with a higher out­put auxiliary heater.
Problem – The auxiliary heater is in operation but not the compressor
Cause
1. Operating mode AUX. HEATER is selected.
2. Peak heat operation (anti­legionella function) is run­ning.
3. The compressor cannot run due to an alarm.
4. The heat pump has stop­ped on high return.
Troubleshooting Remedy If this operating mode is selected, the auxiliary heater is
used for heating and hot water production, not the com­pressor.
Check if the heat pump runs peak heat. Peak heat operation occurs in connection
Check the alarm that is indicated in the display. Rectify the problem and rest the alarm.
Check what the MAX value is set at in the heat pump’s
control computer. It must be adjusted to the unit’s maximum supply temperature and the system’s delta temperature so that it does not cut at too high a re­turn temperature when the highest supply tempera­ture is transmitted.
Check what the return line sensor shows. Is it a plausi-
ble/actual value? If not, take a resistance reading from the sensors and check against the ohm table in Meas­urement points .
If AUX. HEATER mode is selected and you no longer want it, change to AUTO, the heat pump then controls both the com­pressor and auxiliary heater.
with hot water production with the set in­terval. The compressor should then start to produce hot water and 2 minutes later the auxiliary heater starts. The compressor must then stop and the stop temperature be reached with only the auxiliary heater connected. Take no corrective action, this is normal.
If the MAX RETURN value is not adjus-
ted for the system according to the troubleshooting window, adjust it.
If the sensor is defective, replace it.
Danfoss Heating Solutions VMGFJ202
29
Service Instructions DHP-AQ
Cause Troubleshooting Remedy
5. The compressor has been
stopped by the operating pressure switch or delivery line sensor.
Check if a square appears in the display’s lower left corner. If so, the operating pressure switch is open or the delivery pipe sensor triggers an alarm for too high temperature.
The operating pressure switch is most easily checked
by using a buzzer to see if it is connected. The pressure pipe sensor value is read off from the
control system in the HEAT PUMP menu. Is it a plausi­ble/actual value? If not, take a resistance reading from the sensor and check against the ohm table in Meas­urement points .
The compressor has been stopped by the delivery line
sensor and you have established that it shows the correct temperature. This may have been caused by a leak in the refrigerant circuit.
If the operating pressure switch has stuck in the open position, try gently tapping on the pressure switch head. If this does not help, or it sticks in the open position re­peatedly, replace the pressure switch. If the delivery line sensor is defective, replace it. If the delivery line temperature gets so hot that the compressor stops, start by leak­tracing the unit. Rectify the leak, if a leak is found. If no leak is found, try draining and refilling the unit and then restarting the heat pump and seeing what the delivery line temperature is. If the problem persists, replace the compressor.
6. The compressor runs
backwards. The incoming phases have the incorrect sequence (only applies to 3­phase heat pumps). If the compressor runs backwards, it will not cope with com­pressing the refrigerant and therefore does not produce the correct power, which leads to the control system requesting auxiliary heating.
7. The built-in overheating
protection (bi-metal protec­tion) in the compressor has tripped.
Problem – The heat pump consumes too much energy
Cause
1. Blocked strainer in the
heating system.
2. The compressor cannot
run due to an alarm.
3. Incorrect flow over hot
side of the heat pump.
4. The heat pump’s control
computer is not set/adjus­ted to the customer’s re­quirements/wishes.
If the text ERR PHASE SEQ. appears in the display
when the heat pump is powered, (only appears in the first 10 minutes) this means that the phases have the incorrect sequence.
When the compressor is running, check the pressure
pipe temperature by feeling the pressure pipe. If the phases are correctly sequenced it should be hot (not just warm) even a distance from the compressor.
When the compressor runs with the phases incorrect-
ly sequenced a strange noise may be heard (loud, rat­tling) when the compressor runs backwards.
Check if the heat pump’s control computer indicates that the compressor is in operation, and if there is voltage in the soft-starter control inputs. Then read off and check that there is voltage on the compressor’s electrical connec­tion(s).
Troubleshooting Remedy Check that the strainer is not blocked. Clean the strainer if necessary.
Check the alarm that is indicated in the display. Rectify the problem and rest the alarm. See
Measurement check what the difference between the sup­ply and return line is using a thermometer (∆t). The differ­ence should be about 8°C (can vary depending on refriger­ant). A lower ∆t results in reduced efficiency in the heat pump.
Check the ROOM and CURVE and MIN settings. Adjust incorrect values in the heat pump’s
If the phases are in the incorrect order, switch two incoming phases at the main terminal block and recheck according to the troubleshooting window.
If there is voltage on the compressor’s elec­trical connection(s) and the overheating protection does not close when the com­pressor has not run and has cooled down for at least 1 hour, replace the compressor.
section Alarm . Adjust the system to obtain the correct ∆t.
control computer. ROOM = Desired indoor temperature CURVE = Should be set so that the desired indoor temperature (ROOM) is maintained regardless of the outdoor tem­perature. MIN = Lowest set-point value on the supply line regardless of the outdoor temperature.
30
VMGFJ202 Danfoss Heating Solutions
Service Instructions DHP-AQ
Cause Troubleshooting Remedy
5. The interval for peak heat operation has changed to a lower value than the factory set value. This results in the heat pump going into peak heat operation more often than calculated.
6. The heat pump has stop­ped on HIGH RETURN.
Check the specified interval for peak heat operation in the control computer.
Check what the MAX RETURN value is set at in the
heat pump’s control computer. It must be adjusted to the unit’s maximum supply temperature and the sys­tem’s delta temperature so that it does not cut at too high a return temperature when the highest supply temperature is transmitted.
Check what the return line sensor shows. Is it a plausi-
ble/actual value? If not, take a resistance reading from the sensors and check against the ohm table in Meas­urement points .
If there is a shorter interval between the peak heat productions, this explains why the unit consumes more current than calcu­lated, but this does not mean for sure that it should be increased, there might be a reason why the interval has been changed.
If the MAX RETURN value is not adjusted for the system according to the troubleshoot­ing window, adjust it. If the sensor is defec­tive, replace it.
7. The compressor runs backwards. The incoming phases have the incorrect sequence (only applies to 3­phase heat pumps). If the compressor runs backwards, it will not cope with com­pressing the refrigerant and therefore does not produce the correct power, which leads to the control comput­er requesting auxiliary heat­ing.
8. The compressor has been stopped by the operating pressure switch or delivery line sensor.
If the text ERR PHASE SEQ. appears in the display
when the heat pump is powered, (only appears in the first 10 minutes) this means that the phases have the incorrect sequence.
When the compressor is running, check the pressure
pipe temperature by feeling the pressure pipe. If the phases are correctly sequenced it should be hot (not just warm) even a distance from the compressor.
When the compressor runs with the phases incorrect-
ly sequenced a strange noise may be heard (loud, rat­tling) when the compressor runs backwards.
Check if a square appears in the display’s lower left corner. If so, the operating pressure switch is open or the delivery pipe sensor triggers an alarm for too high temperature.
The operating pressure switch is most easily checked
by using a buzzer to see if it is connected. The delivery line sensor value is read off from the con-
trol computer in the HEAT PUMP menu. Is it a plausi­ble/actual value? If not, take a resistance reading from the sensor and check against the ohm table in the in­stallation instructions.
The compressor has been stopped by the delivery line
sensor and you have established that it shows the correct temperature. This may have been caused by a leak in the refrigerant circuit.
If the phases are in the incorrect order, switch two incoming phases at the main terminal block and recheck according to the troubleshooting window.
If the operating pressure switch has stuck in the open position, try gently tapping on the pressure switch head. If this does not help, or it sticks in the open position re­peatedly, replace the pressure switch. If the delivery line sensor is defective, replace it. If the delivery line temperature gets so hot that the compressor stops, start by leak­tracing the unit. Rectify the leak, if a leak is found. If no leak is found, try draining and refilling the unit and then restarting the heat pump and seeing what the delivery line temperature is. If the problem persists, replace the compressor.
9. Expansion valve defective or incorrectly set.
10. Lack of refrigerant, not enough refrigerant in the system.
Danfoss Heating Solutions VMGFJ202
Using manometer apparatus and thermometer check what the overheating reading of the unit is.
Using manometer apparatus and thermometer, check that the unit’s overheating is correct for the specific refrigerant.
If the expansion valve is defective, replace it.
If there appears to be a leak in the refriger­ant circuit, carry out leak tracing and any necessary corrective action. If leak tracer is not available, brush soap water on the sus­pected leak and look for bubbles. Also check for oil as this can come out from the refrigerant circuit.
31
Service Instructions DHP-AQ
Cause Troubleshooting Remedy
11. Overfilled refrigerant cir-
cuit.
12. Changed conditions
Have you increased your heating and/or hot water demand?
Problem – Auxiliary heater cuts in too soon
Cause
1. The heat pump’s control
computer is not set/adjus­ted to the customer’s re­quirements/wishes.
2. Changed conditions Have
you increased your heating and/or hot water demand?
Using manometer apparatus and thermometer, check that the unit’s overheating is correct for the specific refrigerant.
If the heat pump has been dimensioned for a certain
demand and this demand is increased, the heat pump might not be able to maintain the desired room tem­perature.
If hot water consumption increases, a larger propor-
tion of time is used to produce hot water, which means less time for heat production.
Troubleshooting Remedy Check the ROOM, CURVE, INTEGRAL A1 and INTEGRAL A2
settings
If the heat pump has been dimensioned for a certain
demand and this demand is increased, the heat pump might not be able to maintain the desired room tem­perature.
If hot water consumption increases, a larger propor-
tion of time is used to produce hot water, which means less time for heat production.
Follow the correct procedure (depending on type of refrigerant) to add the correct amount of refrigerant.
If the heat pump cannot cope with the de­mand, replace it with one with a higher output or supplement it with a higher out­put auxiliary heater.
Adjust incorrect values in the heat pump’s control computer. ROOM = Desired indoor temperature CURVE = Should be set so that the desired indoor temperature (ROOM) is maintained regardless of the outdoor tem­perature. INTEGRAL A1 = Start value for the compressor. INTEGRAL A2 = Start value (calculated from A1) for the auxiliary heater.
If the heat pump cannot cope with the de­mand, replace it with one with a higher output or supplement it with a higher out­put auxiliary heater.
3. Lack of refrigerant, not
enough refrigerant in the system.
Problem – Short operating times despite heating demand
Cause ROOM and/or CURVE set too
high in combination with a heating system with poor circulation due to closed ra­diator valves, too small ele­ments or insufficient water volume. A tight fitting sys­tem with poor pipe dimen­sions may produce the same phenomena.
Problem – Connection of external AH
Cause Incorrectly connected auxili-
ary heater. Does not start when the control computer gives the signal.
Using manometer apparatus and thermometer, check that the unit’s overheating is correct for the specific refrigerant.
Troubleshooting Remedy Check if the heat pumps starts, if the supply temperature
rises quickly whilst nothing happens to the return temper­ature. If this happens and the heat pump is stopped by the hysteresis function to later quickly drop in temperature (supply) in order to start again, but cannot due to time conditions in regulation, this means that the heat pump cannot transport the heat away from the condenser as it should. In such a case, hysteresis starts and stops the heat pump often.
Troubleshooting Remedy Check the connection against the instructions/wiring dia-
gram. Test the function in manual mode.
If there appears to be a leak in the refriger­ant circuit, carry out leak tracing and any necessary corrective action. If leak tracer is not available, brush soap water on the sus­pected leak and look for bubbles. Also check for oil as this can come out from the refrigerant circuit.
Adjust ROOM and CURVE if necessary. En­sure that there is sufficient flow over the condenser and the heating circuit.
If the auxiliary heater is incorrectly connec­ted, reconnect according to the instruc­tions.
32
VMGFJ202 Danfoss Heating Solutions
Service Instructions DHP-AQ

3.5.7 Heat pump

Problem – Noise/loud noise
Cause Troubleshooting Remedy
1. Positioning the heat pump.
2. Connection/wall lead-ins. Check that the unit is installed according to the instruc-
Problem – Defrosting problems
Cause Troubleshooting Remedy Location/calibration of the
outdoor sensor. Defrost sensor calibration Check that the defrost sensor is installed according to the
Problem – Build-up of ice under and around the outdoor unit
Cause Insufficient drainage. Does a lot of ice accumulate under and around the out-
Determine whether the heat pump can be moved to a more suitable location.
tions.
Check that the outdoor sensor is installed according to the installation instructions and that it is correctly calibrated.
installation instructions and that it is correctly calibrated.
Troubleshooting Remedy
door unit because the melted water has nowhere to run?
Move the heat pump if possible.
Rigid mountings can generate noise from the heat pump via walls in the house.
Install according to the instructions and cal­ibrate, if necessary.
Calibrate if necessary.
Drain the ground under and around the outdoor section or install a drainpipe rout­ed to an indoor drain or gully. NOTE! Install a heating cable in the drainpipe.
Problem – Water run-off by the outdoor unit, risk of moisture problems in house foundations
Cause Insufficient drainage. During some periods when the outdoor unit is being de-
Troubleshooting Remedy
Drain the ground under and around the
frosted, large amounts of water can run off.
outdoor unit so that it can cope with the extra amount of water produced because of defrosting or install a drainpipe routed to an indoor drain or gully. NOTE! Install a heating cable in the drainpipe.
Danfoss Heating Solutions VMGFJ202
33
Service Instructions DHP-AQ
34
VMGFJ202 Danfoss Heating Solutions
Service Instructions DHP-AQ
Danfoss Heating Solutions VMGFJ202
35
Service Instructions DHP-AQ
Danfoss Heat Pumps Box 950 671 29 ARVIKA Phone +46 570 81300 E-mail: dhpinfo@danfoss.com Internet: www.heating.danfoss.com
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss Heating Solutions and the Danfoss Heating Solutions logotype are trademarks of Danfoss A/S. All rights reserved.
VMGFJ202 Produced by Danfoss Heating Solutions © Aug 2013
Loading...