Danfoss DHP-AQ Midi, DHP-AQ Maxi Service Instructions Manual

Service instructions
DHP-AQ
VMGFJ102
If these instructions are not followed during installation and service, Danfoss A/Sliability according to the applicable warranty is not binding. Danfoss A/S retains the right to make changes to components and specifications without prior notice.
© 2011 Copyright Danfoss A/S. The Swedish language is used for the original instructions. Other
languages are a translation of original instructions. (Directive 2006/42/EG)
Contents
1 About documents and decals ...................................................... 3
1.1
Introduction .................................................................................... 3
1.2 Symbols in documents ................................................................ 3
1.3 Symbols on decals ........................................................................ 3
1.4 Terminology .................................................................................... 5
2 Important information .................................................................... 6
2.1 General safety precautions ........................................................ 6
2.2 Refrigerant ....................................................................................... 6
2.3 Electrical connection .................................................................... 7
2.4 Important information ................................................................ 7
2.5 Commissioning .............................................................................. 8
3 Troubleshooting ................................................................................ 9
3.1 Alarm ................................................................................................. 9
3.2 Components ................................................................................. 10
3.3 Measurement points ................................................................. 11
3.4 Check points ................................................................................. 14
3.5 Operational problems ............................................................... 14
VMGFJ102 – 1
1 About documents and decals
1.1
Introduction
The following documents are available for this product:
Installation instructions containing information to install and commission a heat pump installation, and infor­mation about the heat pump’s function, accessories and technical data. Supplied with the heat pump on deliv­ery.
Service instructions that contain information about fault tracing. The service instructions are available for download as below.
The electrical instructions that contain the wiring diagram for the heat pump intended for fault tracing and service. The electrical instructions are available for download as below.
The maintenance instructions must handed over and gone through with the end customer. Supplied with the heat pump on delivery.
Country specific instructions and forms are available where relevant. Supplied with the heat pump on delivery.
Sheet with adhesive decals that will be used as translation for the existing English language type plates.
The Service instructions and Electrical instructions are available for download here:
www.documentation.heatpump.danfoss.com
1.2 Symbols in documents
The instructions contain different warning symbols, which, together with text, indicate to the user that there are risks involved with actions to be taken.
The symbols are displayed to the left of the text and three different symbols are used to indicate the degree of danger:
DANGER! Indicates an immediate danger that leads to fatal or serious injury if necessary measures are not taken.
Warning! Risk of personal injury! Indicates a possible danger that can lead to fatal or serious injury if necessary measures are not taken.
Caution! Risk of installation damage. Indicates a possible hazard that can lead to item damage if necessary measures are not taken.
A fourth symbol is used to give practical information or tips on how to perform a procedure.
Note! Information regarding making the handling of the installation easier or a possible operational technical disadvantage.
1.3 Symbols on decals
The following symbols can occur on decals on the different parts of the heat pump. Which symbols are used depends on the heat pump model.
Service instructions VMGFJ102 – 3
Warning symbols
!
Warning, danger!
!
Read the documentation provided.
Read the documentation provided.
Warning, hazardous electrical voltage!
Warning, hot surfaces!
Warning, moving parts!
Warning, risk of crushing injury!
Electrical components
Component, normal Component, accessory
3 Outdoor unit 362 Shunt valve
50 Outdoor sensor 363 Exchange valve hot water
54 Hot water sensor 365 Supply line sensor
55 Sensor hot-water top 366 Return line sensor
71 Flow sensor 406 Room sensor
304 Circulation pump 408 EVU
353 Drip tray 417 Defrost sensor
Example:
406
Room sensor
4 – Service instructions VMGFJ102
Pipe connections
Bleeding
Defrosting tank
Expansion tank with safety valve, brine
Brine
Temperature and pressure relief valve
Tap water
Outdoor unit
Water heater
Heating system
1.4 Terminology
Term Meaning
Heating system/Heat transfer fluid circuit
The circuit that generates heat to the property or to the water heater.
Supply line The heating system’s supply line with flow direction from the heat pump to radiators/
under floor heating or water heater.
Return line The heating system’s return line with flow direction from radiators/under floor heating
or water heater to the heat pump.
Circulation pump Circulation pump for heating system.
Refrigerant circuit The energy carrying circuit between the outdoor air and heating system.
Refrigerant The gas/liquid that circulates in the refrigerant circuit.
Service instructions VMGFJ102 – 5
2 Important information
2.1
General safety precautions
Warning! Risk of personal injury! Children are not permitted to play with the product.
Caution! The heat pump must be installed by authorised installation engineers and the installation must follow the applicable local rules and regulations as well as these installation instructions.
Caution! This product is not intended for persons (including children) with reduced physical, sensory or psychological capacity, or who do not have knowledge or experience, unless supervised or they have received instructions on how the apparatus functions from a safety qualified person.
Caution! When cooling it is important to limit the lowest flow line temperature to prevent condensation.
2.2 Refrigerant
2.2.1
Fire risk
The refrigerant is not combustible or explosive in normal conditions.
2.2.2 Toxicity
In normal use and normal conditions the refrigerant has low toxicity. However, although the toxicity of the refrig­erant is low, it can cause injury (or be highly dangerous) in abnormal circumstances or where deliberately abused.
Warning! Risk of personal injury! Spaces in which heavy vapour can collect below the level of the air must be well ventilated.
Refrigerant vapour is heavier than air and, in enclosed spaces below the level of a door for example, and in the event of leakage, concentrations can arise with a resultant risk of suffocation due to a lack of oxygen.
Warning! Risk of personal injury! Refrigerant exposed to a naked flame creates a poisonous irritating gas. This gas can be detected by its odour even at concentrations below its permitted levels. Evacuate the area until it has been sufficiently ventilated.
2.2.3 Work on the refrigerant circuit
Caution! Work on the refrigerant circuit must only be carried out by a certified engineer!
Caution! When repairing the refrigerant circuit, the refrigerant must not be released from the heat pump ­it must dealt with in the appropriate way.
6 – Service instructions VMGFJ102
Refilling must only be carried out using new refrigerant (for the amount and type of refrigerant see manufacturer’s plate) through the service valves.
Caution! All warranties from Danfoss are void if, when filling with refrigerant other than Danfoss A/S specified refrigerant, if there has not been written notification that the new refrigerant is an approved replacement refrigerant together with other remedies.
2.2.4 Scrapping
Caution! When the heat pump is to be scrapped the refrigerant must be extracted for disposal. Local rules and regulations related to the disposal of refrigerant must be followed.
2.3 Electrical connection
DANGER! Hazardous electrical voltage! The terminal blocks are live and can be highly dangerous due to
the risk of electric shock. All power supplies must be isolated before electrical installation is started. The heat pump is connected internally at the factory, for this reason electrical installation consists mainly of the connection of the power supply.
Warning! Electrical installation may only be carried out by an authorised electrician and must follow applicable local and national regulations.
Warning! The electrical installation must be carried out using permanently routed cables. It must be possible to isolate the power supply using a multi-pole circuit breaker with a minimum contact gap of 3 mm.
2.4 Important information
Caution! A normal heating system always contains a certain amount of corrosion particulates (rust) and sludge products from calcium oxide. This comes from acid that is naturally occurring in the fresh water that the system is filled with. It is not good practice to have to fill the heating system regularly which is why any leakage in the heating system should be repaired immediately. Normal filling should occur only once or twice a year. The water in the heating system should be as clean as possible, always position the dirt filter on the return line from the heating system to the heat pump, as close to the heat pump as possible.
Caution! Hard water; Normally it is not a problem installing a heat pump in areas with hard water because the normal operating temperature for the hot water does not exceed 60°C. In areas where there are exceptional prevailing conditions with the water one can install a softening filter, which softens the water, cleans any impurities and prevents the build up of calcification.
Service instructions VMGFJ102 – 7
2.5 Commissioning
Caution! The installation may only be commissioned if the heating system is filled and bled. Otherwise the circulation pump can be damaged.
Caution! If the installation is only to operate using an auxiliary heater during the installation, ensure that the heating system is filled and bled and that the compressor cannot be started. This is carried out by setting the operating mode to AUX. HEATER.
8 – Service instructions VMGFJ102
3 Troubleshooting
3.1
Alarm
In event of alarm this is indicated in the display with the text ALARM and an alarm message, see following table. For alarms that are not reset automatically acknowledgement is required. Acknowledge the alarm by setting the heat pump to operating mode OFF and then back to the desired operating mode.
Message Meaning
MOTOR P COMP.ERROR The compressor motor protection has deployed.
MOTOR P FAN ERROR The fan motor protection has deployed.
EL. HEATER ERROR The electrical heater overheating protection has deployed.
HEAT / PRESSURE ERROR The expected pressure and temperature change in the refrigerant circuit has
not happened in the correct way at compressor start.
LOW PRESSURE ERROR Evaporation pressure has fallen too low.
LOW PRESSURE TRANSDUCER Fault in low pressure transmitter alternatively cable fault.
HIGH PRESSURE ERROR High pressure switch has deployed.
LOW HEAT CIR. FLOW The flow sensor has registered too low a flow.
MAX TEMP ELEC. HW Too high temperature in heat pump junction box/electrical cabinet.
NO. OF TRIES X/5 (where X=1…5)
Circulation pump is jammed. Start attempt made.
HEATING CIRC. PUMP Circulation pump is jammed.
HEATING SYSTEM PUMP Circulation pump is jammed.
OUTDOOR SENSOR Sensor fault alternatively cable fault.
DEFROST SENSOR Sensor fault alternatively cable fault. Defrost sensor.
SUPPLY LINE SENSOR Sensor fault alternatively cable fault. Supply line sensor.
SYSTEM SUPPLY LINE SENSOR Sensor fault alternatively cable fault. System supply line sensor.
RETURN LINE SENSOR Sensor fault alternatively cable fault. Return line sensor.
HIGH RETURN LINE TEMP Return line temperature too high
BUFFER TANK SENSOR Sensor fault alternatively cable fault.
HGW SENSOR Sensor fault alternatively cable fault.
HOT WATER SENSOR Sensor fault alternatively cable fault (the lower sensor, Start sensor).
HOT WATER TOP Sensor fault alternatively cable fault.
FAILSAFE MODE Sensor fault alternatively cable fault on one of the refrigerant sensors. The heat
pump goes to failsafe mode and defrosts on time.
REFR.1 SENSOR Sensor fault alternatively cable fault. Refrigerant sensor 1
REFR.2 SENSOR Sensor fault alternatively cable fault. Refrigerant sensor 2
LOW RETURN TEMP 1 The return line temperature is too low to start a defrosting.
LOW RETURN TEMP 2 The return line has fallen too low during defrosting.
LOW EVAP. TEMP 1 Evaporation temperature too low.
LOW EVAP. TEMP 2 Too great a deviation in evaporation temperature average value.
SUCTION TEMP SENSOR Sensor fault alternatively cable fault.
ROOM SENSOR Sensor fault alternatively cable fault.
DISCHARGE PIPE SENSOR Sensor fault alternatively cable fault.
DISTR. CIR. 1 SENSOR Sensor fault alternatively cable fault.
DISTR. CIR. 2 SENSOR Sensor fault alternatively cable fault.
POOL SENSOR Sensor fault alternatively cable fault.
COM. ERROR HP-CARD Communication broken between display card and heat pump card (outdoor).
COM. ERROR HUB-CARD Communication broken between display card and hub card (indoor).
Service instructions VMGFJ102 – 9
Message Meaning
COM. ERROR EXV-CARD Communication broken between display card and expansion valve control
card (outdoor).
COM. ERROR EXPANSION CARD Communication broken between display card and expansion card (indoor).
Note! In event of alarm the heat pump will if possible supply heating to the house, primarily with the compressor, secondarily with the auxiliary heater. Hot water will stop to indicate that something noteworthy has occurred.
3.2 Components
3.2.1 Outdoor unit
11
10
12
13
14
16
15
17
1
2
3
4
5
6
7
8
9
19
18
Figure 1. Components
Position Name Position Name
1 Electrical cabinet 11 Electronic expansion valve
2 Fan 12 Receiver
10 – Service instructions VMGFJ102
Position Name Position Name
3 Pressure transmitter 13 Drying filter
4 Suction line 14 Heat exchanger
5 Compressor 15 Flow sensor
6 High pressure switch 16 Heating system supply line
7 Operating pressure switch 17 Return line heating system
8 Four-way valve 18 Solenoid
9 Discharge pipe 19 Non-return valve
10 Air heat exchanger
3.2.2 Indoor unit
1
DHP-AQ Mini
1
2
4
3
5
DHP-AQ Maxi
1
2
3
4
DHP-AQ Midi
Position Description
1 Control module (transparent in image)
2 Immersion heater
3 Reversing valve
4 Circulation pump
5 Water heater
3.3 Measurement points
Caution! When reading the resistance of the sensors, the sensor leads must first be disconnected from the control equipment.
Service instructions VMGFJ102 – 11
Table 1. Outdoor / Defrost sensor
°C 150 ohm, Ω
-30 1884
-25 1443
-20 1115
-15 868
-10 681
-5 538
0 428
5 343
10 276
15 224
20 183
25 150
30 124
35 103
40 86
Table 2. PT1000 sensor
°C 1000 ohm, Ω
0 1000
10 1039
20 1078
30 1117
40 1155
50 1194
60 1232
70 1271
Table 3. Other sensors
°C 22 kilo ohm, kΩ
0 66,3
5 52,4
10 41,8
15 33,5
20 27,1
25 22,0
30 18,0
35 14,8
40 12,2
45 10,1
50 8,5
55 7,1
60 6,0
65 5,0
70 4,2
75 3,7
80 3,1
85 2,7
3.3.1 Measurement checking sensors during fault tracing
1.
Disconnect the relevant sensor from I/O-card/terminal block.
2. Measure the resistance for the sensor and any extension cables.
3. Then measure the sensor only.
Note! To ensure the sensor value the actual temperature must be checked against the measured resistance.
12 – Service instructions VMGFJ102
3.3.2 Positioning sensors
7
7
8
9
Heat pump DHP-AQ Midi DHP-AQ Maxi
Symbol explanation
1 DISCHARGE PIPE SENSOR
2 SUCTION TEMP SENSOR
3 REFR.1 SENSOR
4 REFR.2 SENSOR
5 DEFROST SENSOR (located to rear beside air intake)
6 OUTDOOR SENSOR (positioned on wall to north)
7 SUPPLY LINE SENSOR
8 HOT WATER TOP
9 HOT WATER SENSOR
RETURN LINE SENSOR - Located on return pipe that runs to heat pump. See system solution in the Installa­tion instructions.
Service instructions VMGFJ102 – 13
3.4 Check points
Table 4. Temperatures
Name Values
Condensing temperature 0.5 – 1.5 °C above supply line temperature
Evaporation temperature 7 - 8 °C
Radiator circuit 8°K temperature difference
Overheating R407C 4K ±1 K
Table 5. Break pressure switch/pressure transmitter
Refrigerant Pressure switch/pressure transmitter Break pressure
R407C OP (operating pressure switch) 2.85 MPa
High pressure switch 3,10 MPa
Pressure transmitter low pressure 0.04 MPa
Following parameters can be read off in the display:
Suction gas temperature
Evaporation pressure
Evaporation temperature (calculated from ”Dew point”)
Opening percent EXV
Superheating
This means new opportunities to diagnose the heat pump, without needing to remove the covers and work on the cooling circuit.
In normal operation the heat pump operates with superheating of 5.5°C – 7°C, the expansion valve's degree of opening will vary depending on operating situation.
At outdoor temperatures of -5°C or lower the opening degree is below 20%
At outdoor temperatures of +5C to +13°C the opening degree is around 40-50%
When cooling (A35W18) the degree of opening is 100%
If superheating is >9°C and the degree of opening of the expansion valve lies steady at 100% this can indicate that a significant part of the refrigerant has leaked from the heat pump. If this is the case the heat pump must be checked by service technicians with personal refrigeration certificates!
3.5 Operational problems
The tables list the most probable and common causes of the problem first. When troubleshooting the cause of a problem start with the first cause and go down the list. There may be more than one way of troubleshooting a cause where the most probable is given first.
14 – Service instructions VMGFJ102
3.5.1 Alarm
Table 6. Problem – Alarm LP (lower pressure transmitter)
Cause Troubleshooting Remedy
1. Cable break or loose cable to lower pressure transmitter.
Check that both cables are connected to the lower pressure transmitter.
Using the buzzer, check that there are no cable breaks. In order to do this, disconnect the cables from the lower pressure transmitter and circuit board.
If a cable has come loose, reconnect it. If there is a cable break, replace the
cable.
2. The pressure transmitter opens too soon.
Pressure transmitter fault, opens at a higher pressure than indicated. Check break pressure using the manometer apparatus.
If the pressure transmitter breaks too early, replace it.
3. Lack of refrigerant, not enough refrigerant in the system.
Using manometer apparatus and ther­mometer, check that the unit’s overheat­ing is correct for the specific refrigerant.
Follow the correct procedure (depend­ing on type of refrigerant) to add the cor­rect amount of refrigerant.
If there appears to be a leak in the refrig­erant circuit, carry out leak tracing and any necessary corrective action.
4. Drying filter blockage. Check the temperature difference above the drying filter. A difference of max 1°C is permissible. If the difference is greater, the filter is blocked. Take a reading during operation.
If the drying filter is sealed, replace it.
5. Blocked evaporator on the refriger-
ant side.
Using manometer apparatus and ther­mometer, check that the unit’s overheat­ing is correct for the specific refrigerant.
If the evaporator is thought to be blocked by oil for example, try blowing nitrogen through it to release the oil. If this does not work, it must be replaced
Table 7. Problem – Alarm HP (high pressure switch)
Cause Troubleshooting Remedy
1. Air in the heating system. Listen for air in the heat pump and heat­ing system.
Bleed the heating system according to the installation instructions.
2. Blocked strainer in the heating sys-
tem.
Check that the strainer is not blocked. Clean the strainer if necessary.
3. Closed or partially closed thermo-
stats/valves in the heating system.
Check that the thermostats/valves in the heating system are open.
Open closed thermostats/valves.
4. The circulation pump that is defec-
tive or has jammed.
Is there voltage and 0 – 10V signal (applies to A classed circulation pumps) up to the circulation pump?
Check that the circulation pump is active in the control system’s manual test menu.
Check if there is voltage to the circula­tion pump, if there is, and it does not run, the circulation pump is jammed. If this is the case, open the bleed screw and try to release the paddle wheel using a screw­driver for example (Does not apply to heat pumps in Opti).
If there is no voltage to the circulation pump, check if there is voltage from the I/O card, see wiring diagram. If there is voltage from the I/O card, check the components between the I/O card and the circulation pump.
If a component is defective, replace it.
Service instructions VMGFJ102 – 15
Cause Troubleshooting Remedy
5. Shut-off main tap in heating sys-
tem.
Check that the main tap is open. Open closed main tap.
6. Cable break or loose cable to high
pressure switch.
Check that both cables are connected to the pressure switch.
Using the buzzer, check that there are no cable breaks. In order to do this, disconnect the cables from the pres­sure switch and circuit board.
If a cable has come loose, reconnect it. If there is a cable break, replace the
cable.
7. The high pressure switch does not
open.
Incorrect pressure switch installed. Same or higher break pressure than the high pressure switch. See mark­ing.
Pressure switch fault, opens at a higher pressure than indicated (mark pressure). Check using the manome­ter apparatus.
Defective pressure switch, never opens.
If the high pressure switch does not open, replace it.
8. The high pressure switch opens too
soon.
Incorrect pressure switch installed. As low or lower break pressure than operating pressure switch. See mark­ing.
Pressure switch fault, opens at a lower pressure than indicated (mark pres­sure). Check using the manometer apparatus.
Defective pressure switch, always open.
If the high pressure switch opens too soon or is always open, replace it.
9. External system shunt that closes
on time setting.
Check for shunts or valves in the system, which are timer-controlled, that close down the entire or too large a part of the heating system.
Always ensure that there is a sufficiently large water volume for the heat pump to work against, i.e. for the heat to give off its heat to.
10. Incorrectly facing non-return valve
with too high opening pressure.
Check the system’s direction of flow and that the non-return valve is turned the correct way.
Check that the heat pump’s external available pressure exceeds the non­return valve’s opening pressure.
If the non-return valve is facing the wrong way, turn it.
If the non-return valve has too great an opening pressure, replace it.
11. Large pressure drop in the heating
system.
Dirt in the heating system.
Closed or partially closed thermo­stats/valves in the heating system.
Under dimensioned pipe system. Check that the HP’s external available pressure exceeds the system pressure drop.
If necessary, clean/flush the heating sys­tem.
Open closed thermostats/valves. If there is not sufficient pressure equip-
ment, the heating system can be adjus­ted according to the system solution for large pressure drop.
16 – Service instructions VMGFJ102
Cause Troubleshooting Remedy
12. Blocked condenser on the water
side.
If there is no strainer in the heating sys­tem, there is a risk of dirt sticking in the condenser and blocking it. Unfortunately there is no easy way of checking if the condenser is blocked.
You can carry out a test by allowing the compressor and circulation pumps to remain in operation and after a while, check that the pressure pipe becomes hot and that the circulation pumps work (for circ.pumps with a bleed screw, unscrew it and feel if the pump rotor rotates using a screwdriver).
Then read the temperature on both con­nection pipes to the condenser:
If the temperature difference is <3°C, the condenser is probably blocked.
If the temperature difference is 3-13°C, it is probably not blocked.
If the temperature difference is >13°C, the condenser is probably blocked.
If the condenser is thought to be blocked, try flushing it. If this does not work, it must be replaced
13. Blocked condenser on the refriger-
ant side.
Using manometer apparatus and ther­mometer, check that the unit’s overheat­ing is correct for the specific refrigerant.
If the condenser is thought to be blocked by oil for example, try blowing nitrogen through it to release the oil. If this does not work, it must be replaced
14. Overfilled refrigerant circuit. Using manometer apparatus and ther­mometer, check that the unit’s overheat­ing is correct for the specific refrigerant.
Follow the correct procedure (depend­ing on type of refrigerant) to add the cor­rect amount of refrigerant.
If there appears to be a leak in the refrig­erant circuit, carry out leak tracing and any necessary corrective action.
Table 8. Problem – Alarm MS (motor protection)
Cause Troubleshooting Remedy
1. Phase drop or blown fuse. Check the fuses in the fuse box. Check that all phases are present on the terminal block for incoming supply. Also check that all wiring is secure, if screw terminals are used they must be properly tightened, if phoenix flat spring terminals are used, the cables must be secure in the correct hole with load on the cable.
If any of the phases are missing, check backwards towards the building’s main electrical cabinet. If there are no phases there, contact the network supplier.
2. Cable break. Check the supply to the motor protection, soft-starter or compressor.
If a cable is damaged, replace it.
3. Defective soft-starter (three-phase
heat pump).
Measurement check and establish that when the Heat pump card gives a signal (there must be voltage between A1 & A2 on the soft-starter), the soft-starter relea­ses all three phases down to the compres­sor.
If the soft-starter does not release the phases when it receives signals from the heat pump card, replace it.
4. Defective soft-starter (single phase
heat pump).
Check measure and establish that when the Heat pump card gives a signal (there must be voltage between ON and N on the soft-starter), the soft-starter releases the phases to the compressor.
If the soft-starter does not release the phases when it receives signals from the heat pump card and does not alarm as below, replace it.
Service instructions VMGFJ102 – 17
Cause Troubleshooting Remedy
5. Defective or incorrectly set motor
protection.
Use a hook-on meter to establish when the motor protection deploys, check what the motor protection is set to. Compare with the table. For three phase heat pumps all three phases must be sup­plied.
If the motor protection is defective, replace it.
If incorrectly set, adjust to the correct value.
6. Defective compressor. Measurement check the voltage on the phase(s) (each to zero) at the compressor. There must not be any large deviation between the phases. If measurement checking the winding’s resistance the same value must be on one to three wind­ings.
If the compressor is defective, replace it.
7. Alarm from single phase soft starter. Check the fault cause using the soft start LEDs.
Table 9. Problem – Alarm sensor (all)
Cause Troubleshooting Remedy
Sensor fault alternatively cable fault.
When reading the resistance of the sensors, the sensor leads must first be disconnected from the control equipment or terminal block.
First take a reading from the sensor including cable and check against the ohm table in Symbols on decals.
If the read off value does not corre­spond with the table, only measure the sensor and check the ohm table in Measurement points, Page 11.
If the sensor gives a correct value, the cable is defective.
If the sensor does not give a correct value, the sensor is defective.
Table 10. Problem – Err phase seq.
Cause Troubleshooting Remedy
The incoming phases have the incor­rect sequence (only applies to 3-phase heat pumps), appears after a minute when the compressor is started.
If the text HEAT / PRESSURE ERROR is displayed it can mean that the pha­ses are in the incorrect order.
When the compressor is running, check the pressure pipe temperature by feeling the pressure pipe. If the phases are correctly sequenced it should be hot (not just warm) even a distance from the compressor.
When the compressor runs with the phases incorrectly sequenced a strange noise may be heard (loud, rattling) when the compressor runs backwards.
If the phases are in the incorrect order, switch two incoming phases at the main terminal block and recheck according to the troubleshooting window.
18 – Service instructions VMGFJ102
Table 11. Problem – Alarm electric heater error
Cause Troubleshooting Remedy
1. The overheating protection has trip-
ped.
Check if the overheating protection has tripped.
If the overheating protection has trip­ped, reset it.
2. Phase drop.
The alarm occurs when 230 V is not registered between L2 on the circuit board and N. Does not apply if MAX STEP = P.
Check if the overheating protection has tripped.
Check if any cables at the circuit board or overheating protection are loose or damaged.
If the overheating protection has trip­ped, reset it.
If the cables are loose or damaged, secure or replace them.
3. Overheating protection fault, cannot
be reset.
Press the reset button, measurement check for 230 V on the incoming and out­going connections.
If the overheating protection is defec­tive, replace it.
4. Flow sensor fault. Check what the flow sensor shows. Is it a
plausible/actual value? Measure the resistance of the sensor,
check against the ohm table in Measure­ment points, Page 11.
If the sensor is defective, replace it.
5. No or insufficient circulation in the
heating system.
Check:
That the circulation pump spins
That the shut-off valves are open.
That the strainer is not blocked.
That there is no air in the heating sys­tem.
The circulation pump may have jam­med. If so, open the bleed screw and try to release the paddle wheel using a screwdriver for example.
Open closed valves or taps. Check, and, if necessary, clean the
strainer. If necessary, bleed the heating system
according to the installation instructions
Table 12.
Problem – Alarm circulation pump
Cause Troubleshooting Remedy
The circulation pump’s integrated alarm has deployed. (Only applies to Opti)
Air in the heating system.
Has the circulation pump jammed?
Vent the heating system and TWS coil. If the circulation pump has jammed,
there is an integrated shake function that attempts to shake itself loose up to a maximum of 5 times, if it does not suc­ceed, an alarm will occur.
Try cutting the voltage to the heat pump to stop the alarm and then manually run the circulation pump. If the alarm recurs, repeat the procedure several times. If this does not help, replace the circulation pump.
Service instructions VMGFJ102 – 19
Table 13. Problem – Operating pressure switch open alternatively high hot gas temperature
Cause Troubleshooting Remedy
1. Operating pressure switch, func-
tion.
1. Switch off the main switch for the
heat pump, wait until the com­pressor has been stationary for at least 15 minutes.
2.
Disconnect the two cables on the pressure switch, using a buzzer check if the pressure switch is closed.
If the pressure switch is closed, bridge the pressure switch cables temporarily and switch on the voltage to the heat pump again. If there is an indication 0 (zero) in the display this means that the pressure switch is fault-free and the problem is in the wiring or in the circuit board.
If the pressure switch is open, try care­fully tapping the head of the pressure switch with a screwdriver and use a buz­zer test to see if it has closed again.
Replace the pressure switch if it appears to jam repeatedly.
2. Fault in the discharge pipe sensor. Check what the discharge pipe sensor shows. Is it a plausible/actual value?
Measure the resistance of the discharge pipe sensor, check against the ohm table in Measurement points, Page 11.
If the discharge pipe sensor is defective, replace it.
3. Hot gas temperature too high. The discharge pipe sensor displays more than 140°C. See operating data.
The square symbol appears when the delivery pipe temperature is as high or greater than the maximum temperature of the discharge pipe 140°C.
4. Lack of refrigerant, not enough
refrigerant in the system.
Using manometer apparatus and ther­mometer, check that the unit’s overheat­ing is correct for the specific refrigerant.
Follow the correct procedure (depend­ing on type of refrigerant) to add the cor­rect amount of refrigerant.
If there appears to be a leak in the refrig­erant circuit, carry out leak tracing and any necessary corrective action. If leak tracer is not available, brush soap water on the suspected leak and look for bub­bles. Also check for oil as this can come out from the refrigerant circuit.
3.5.2 Leakage
Table 14. Problem – Leak fluid side
Cause Troubleshooting Remedy
1. Insufficiently tightened connec-
tions.
Locate the leak.
Tighten the connection and check that it is sealed.
If it is still not sealed, replace the entire connection and support sleeve (only at soft pipes).
2. Defective gasket or O-ring. Locate the leak. Replace the gasket or O-ring.
3. Cracked nut or connection. Locate the leak. Replace nut or connection.
4. There is no overflow pipe connec-
ted to the safety valve(s).
Establish which safety valve does not have an overflow pipe.
Install an overflow pipe according to the applicable norms.
5. Filler valve between incoming cold
water and heating system not closed or leaking.
Check whether water continuously leaks from the safety valve on the expansion ves­sel on the hot side.
Try closing the filler valve and see if water stops dripping from the safety valve. If not, replace the filler valve.
20 – Service instructions VMGFJ102
Cause Troubleshooting Remedy
6. Leak at soldered joints. Locate the leak. Drain the system of fluid, repair the leak.
If the leak is on the connection pipe to the heat exchanger, also drain the refrig­erant side.
7. Associated leakage in the con-
denser.
Check for lack of refrigerant in the unit.
Check by smelling at the safety valve on the hot side, open the valve and check.
If the condenser has a leak, replace it.
8. Leak at soldered joint on water
heater (only applies to DHP-AQ Maxi)
Locate the leak. If there is a leak at the soldered joint,
replace the water heater.
9. Associated leakage on plate heat
exchanger (only applies to DHP-AQ Maxi)
Check for lack of refrigerant in the unit
Check by smelling at the safety valve on the hot side, open the valve and check.
If there is leakage, replace plate heat exchanger.
3.5.3 Noise
Table 15. Problem – Noise problem in the radiator system
Cause Troubleshooting Remedy
1. Flexible hoses missing. Flexible hoses must be installed according
to the instructions.
Install flexible hoses according to the instructions.
2. Incorrectly installed flexible hoses. Flexible hoses must be installed according
to the instructions.
Install flexible hoses according to the instructions.
3. Installing/suspending pipes. Check if vibrations are transmitted via one
of the pipe mountings in the installation.
Remove or move the mounting point or install vibration isolating mounting parts.
4. Circulation noise (whistling noise in
the heating system).
Check the heating system.
Closed valves, choke valves, adjuster valves or other restrictions in the radia­tor system can cause circulation noise.
Is the heating system correctly adjus­ted for flow?
Too great a flow in the heating system can cause circulation noise.
If the incorrect type of valve is used to choke the flow, replace with the correct type.
If the heating system is not correctly adjusted, make adjustments.
Can the heating system be run at a lower flow?
5. Clicking.
Check that the volume tank is installed and has the correct dimensions for the relevant system. See the installation instructions.
Establish when clicking occurs, during heating and/or in connection with completed hot water production?
Locate the clicking noises.
A surge tank can be installed on the sup­ply line to mix the hot water with the existing, slightly cooler, water, before it goes out to the radiators.
Try lubricating lead-ins in walls, ceilings and floors with silicone spray.
Service instructions VMGFJ102 – 21
Table 16. Problem – Loud compressor noise
Cause Troubleshooting Remedy
1. Phase drop.
The compressor attempts to start or operates on two phases (only applies to 3 phase heat pumps) .
1. Check that there is 400 V between incoming phases on the heat pump.
2.
If there is supply to the heat pump, measure the voltage for all electrical components all the way to the compressor, see wiring dia­gram.
Check where the phase drop is and rec­tify.
2. Touching pipes – vibrations. Establish which pipe(s) is/are causing the problem.
Try to remove the contact:
3. Compressor fault Determine whether the compressor is unusually loud.
Check with a voltmeter at a point before and after the soft starter. The measurement values should not dif­fer.
If the compressor is defective, replace it.
Table 17. Problem – Shrieking, whistling noise
Cause Troubleshooting Remedy
1. Noise from the soft-starter. Measurement check the input and output
phases for the soft-starter as well as the control signals from the heat pump card, see wiring diagram.
If the soft-starter is defective, replace it.
2. The compressor’s safety valve
opens.
The compressor has an integrated safety valve that opens when the pressure differ­ence between high and low pressure sides is too large. A whistling sound can be heard during pressure equalisation. Use a manometer to check at which pressure differential pressure equalisation occurs.
Replace the compressor if the valve opens at too low pressure or when the compressor is stationary.
Table 18. Problem – Noise – miscellaneous
Cause Troubleshooting Remedy
1. Vibrating protective sleeves on the
pressure switches.
Establish where the vibration noise is com­ing from.
Prevent the protection sleeve vibrating by using insulation tape for example.
2. Vibration noise from the electrical
installation.
Check for electrical steps or similar devices screwed to the heat pump and wall. These can cause vibrations and noise.
Carry out according to the installation instructions.
22 – Service instructions VMGFJ102
3.5.4 Hot-water
Table 19. Problem – Temperature and/or quantity
Cause Troubleshooting Remedy
1. Defective 3-way valve motor. Check the function of the reversing valve by test running it manually.
If the motor is defective, replace it.
2. Jammed reversing valve.
The valve is not secure and releases hot water to the radiators during hot water production.
Detach the motor and test closing and opening the valve by turning the shaft by hand.
If it jams, replace with a new one.
3. Air in TWS coil or water outer jacket. During hot water production:
Listen for air.
Check the temperature difference between supply and return line.
Bleed the system. A Large temperature difference can indi-
cate air in the system.
4. Start temperature set too high for
hot water production.
Check that the start temperature is cor­rectly set. Should not be set above the factory set value.
If the start value is set too high, reduce it to the factory set value.
5. Sensor fault, hot water sensor.
Hot water production is started by the hot water sensor.
Check what the hot water sensor (the start sensor) shows. Is it a plausible/actual value?
Measure the resistance of the sensor, check against the ohm table in Measure­ment points, Page 11.
If the sensor is defective, replace it.
6. Large drain flow (>12 l/min). Check how many litres of hot water (approx. 40°C) per minute drains from the tap. Use a clock and bucket to measure the drain flow.
If the drain water flow is greater than 12 l/min, stratification in the water heater is affected, which reduces the hot water capacity.
Suggested corrective actions:
Install a pressure reduction valve on the incoming cold water pipe.
Change to a mixer with lower flow.
Adjust the drain flow on the exist­ing mixer, do not open the tap fully.
7. Water heater too small in relation to
requirement.
How large is the requirement and what is the capacity of the heater?
Replace with a larger heater or supple­ment with an extra heater.
E.g. supplement with an DWH or an electric heater.
8. The operating pressure switch opens
too soon (at too low a pressure). Hot water production ends when the
operating pressure switch opens.
Check the break pressure using manome­ter apparatus.
If the pressure switch opens at the incor­rect pressure, replace it.
The replacement pressure switch can be installed on the service output (Schrader valve).
Service instructions VMGFJ102 – 23
Cause Troubleshooting Remedy
9. Insufficient exchange surface to
transfer the heat pump’s output to the heater. (Only applies to heat pumps with a separate heater.)
Is the exchange surface too small? Can the heater cope with the heat pump’s
output?
Replace with a heater with a larger exchange surface.
10. Heat loss in the hot water pipe. Open the hot water tap, read off the tem­perature on the outgoing hot water pipe from the heat pump and the temperature of the hot water. The temperature differ­ence measured between the heat pump and hot water indicates the temperature loss.
Examples of temperature loss causes:
Long water pipes.
Uninsulated hot water pipes.
Hot water pipes routed through cold areas.
Other causes that can affect the hot water temperature:
Is a mixer valve installed in the sys­tem? Temperature set too low on the mixer valve? Leaking mixer valve?
Water tap fault? Leaking thermostat mixer?
VVC loss.
If any problems occur during trouble­shooting as per the points, carry out cor­rective actions.
To quickly check that the heat pump’s hot water production works as it should, drain the hot water so that the heat pump starts to produce the hot water. When done, read off the temperature on the top sensor and on the start sensor. The top sensor should show a tempera­ture of around 50 - 55°C and the start sensor around 45 - 48°C. If, after comple­ted hot water production, these temper­atures are obtained, this means that you have the correct temperature and vol­ume of hot water in the water heater.
3.5.5 Heating comfort
Table 20. Problem – Too cold
Cause Troubleshooting Remedy
1. The heat pump’s control computer is
not set/adjusted to the customer’s requirements/wishes.
Check the ROOM and CURVE and MAX settings.
Adjust incorrect values in the heat pump’s control computer.
ROOM = Desired indoor temperature CURVE = Should be set so that the
desired indoor temperature (ROOM) is maintained regardless of the outdoor temperature.
MAX = Highest set-point value on the supply line regardless of the outdoor temperature.
2. Incorrect operating mode set in the
heat pump’s control computer.
Check which operating mode is set. If the incorrect operating mode is set,
change to the desired operating mode.
3. Sensor fault, OUTDOOR/ROOM/SUP-
PLY LINE/RETURN LINE.
Check what the relevant sensor shows. Is it a plausible/actual value?
Measure the resistance of the sensor, check against the ohm table in Measure­ment points, Page 11.
If the sensor is defective, replace it.
24 – Service instructions VMGFJ102
Cause Troubleshooting Remedy
4. The 3-way valve has jammed in hot
water mode.
1. Check the function of the 3-way valve motor by test running it manually. If the motor does not shift mode during manual test operation, check that there is voltage to the motor, see wiring diagram.
2.
Detach the motor and test clos­ing and opening the valve by turning the shaft by hand.
Is the motor being supplied with voltage according to the wiring diagram in both operating instances? MANUAL TEST – REV.V. HOT WATER 0=Radiator mode
1=Hot water mode
If there is voltage to the motor but it does not shift mode, replace it.
5. Defective electric heating element. Use a buzzer and check if all coils in the electric heating element are intact.
If the electric heating element is defec­tive, replace it.
6. The heat pump has stopped on HIGH
RETURN.
Check what the MAX RETURN value is set at in the heat pump’s control computer. It must be adjusted to the unit’s maximum supply temper­ature and the system’s delta tem­perature so that it does not cut at too high a return temperature when the highest supply tempera­ture is transmitted.
Check what the return line sensor shows. Is it a plausible/actual value? If not, take a resistance reading from the sensors and check against the ohm table in Measurement points, Page 11.
If the MAX RETURN value is not adjusted for the system according to the trouble­shooting window, adjust it.
If the sensor is defective, replace it.
7. Heat production is stopped by the
HYSTERESIS function.
If the flow temperature rises as soon as heat production is stopped by HYSTERE­SIS before INTEGRAL reaches 0, there may be heating deficit in the house.
Check if heat production stops because the hysteresis value is set too low? (See the installation instructions for factory setting.)
Check if heat production stops because thermostats/valves in the heating system are closed or parti­ally closed?
Check if heat production stops because the heating system is under dimensioned?
Try increasing the hysteresis value until the heat pump stops on INTE­GRAL instead.
Open thermostats/valves in the heating system and check that the heat pump stops on INTEGRAL.
If the heating system is deemed to be under dimensioned, the system must be extended (the heat emit­ting surface increased).
8. The auxiliary heater is not permitted
to cut in with sufficient output. Value set too low on MAXSTEP. MAXSTEP 1 = 3 kW MAXSTEP 2 = 6 kW MAXSTEP 3 = 9 kW MAXSTEP 4 = 12 kW MAXSTEP 5 = 15 kW
Check the set value on MAXSTEP in the heat pump’s control computer.
If necessary, adjust the MAXSTEP value in the heat pump’s control computer. 230V 1-N MAXSTEP 1 – 3
400 V 3-N: MAXSTEP 1 – 5
MAXSTEP 1 = 3 kW MAXSTEP 2 = 6 kW MAXSTEP 3 = 9 kW MAX STEP 4 = 12 kW (cannot cut in
when the compressor is running.) MAX STEP 5 = 15 kW (cannot cut in
when the compressor is running.)
9. The external auxiliary heater does not
start when the heat pump’s control computer requests it.
If an external auxiliary heater is used, check that it is correctly installed by test running it in MANUAL TEST – EXT.AUX.HEATER - 1.
If it does not start at manual test opera­tion, check that the start signal/voltage comes from the heat pump. See wiring diagram.
Connect the external auxiliary heater according to the instructions.
Measure the voltage on the I/O card’s probe L2 Oil/Electricity.
Service instructions VMGFJ102 – 25
Cause Troubleshooting Remedy
10. Closed or partially closed thermo-
stats/valves in the heating system.
Check that the thermostats/valves in the heating system are open.
Open closed thermostats/valves.
11. The total output of the heat pump
and auxiliary heater is too low in relation to the building’s power demand.
What is the building’s power demand? What is the output of the heat pump? What is the output of the auxiliary
heater, what is it set to?
Ensure that available power is at least as great as the building’s power demand.
12. Under dimensioned heating system. Check existing heating system. What output is it dimensioned for to
produce at what supply temperature? What output is required to keep the
room warm?
If the heating system is dimensioned for greater supply temperatures than the heat pump can provide, it must be adjusted by increasing the heat emitting surface for example.
If the room requires a higher output than the heating system can provide, extend the heating system.
13. Changed conditions
Have you increased your heating and/or hot water demand?
If the heat pump has been dimen­sioned for a certain demand and this demand is increased, the heat pump might not be able to main­tain the desired room temperature.
If hot water consumption increases, a larger proportion of time is used to produce hot water, which means less time for heat production (only applies to system solution 1).
If the heat pump cannot cope with the demand, replace it with one with a higher output or supplement it with a higher output auxiliary heater.
Table 21. Problem – Too hot
Cause Troubleshooting Remedy
1. The heat pump’s control computer is
not set/adjusted to the customer’s requirements/wishes.
Check the ROOM and CURVE and MIN set­tings.
Adjust incorrect values in the heat pump’s control computer.
ROOM = Desired indoor temperature. CURVE = Should be set so that the
desired indoor temperature (ROOM) is maintained regardless of the outdoor temperature.
MIN = Lowest set-point value on the supply line regardless of the outdoor temperature.
2. Sensor fault, OUTDOOR/ROOM/SUP-
PLY LINE.
Check what the relevant sensor shows. Is it a plausible/actual value?
Measure the resistance of the sensor, check against the ohm table in Measure­ment points, Page 11.
If the sensor is defective, replace it.
26 – Service instructions VMGFJ102
Cause Troubleshooting Remedy
3. Defective 3-way valve motor.
The motor should set the valve to the relevant position depending on oper­ating conditions. If it does not, hot water from the water heater will mix with the radiator water.
Check the function of the 3-way valve motor by test running it manually. If the motor does not shift mode during manual test operation, check that there is voltage to the motor, see wiring diagram.
Is the motor being supplied with voltage according to the wiring diagram in both operating instances?
MANUAL TEST – REV.V. HOT WATER 0=Radiator mode 1=Hot water mode If there is voltage to the motor but it
does not shift mode, replace it.
4. Jammed reversing valve.
If the valve is not sealed, hot water from the water heater will mix with the radiator water.
Detach the motor and test closing and opening the valve by turning the shaft by hand.
If it is sluggish or jams, replace with a new one.
Table 22. Problem – Irregular indoor temperature
Cause Troubleshooting Remedy
1. The heat pump’s control computer
is not set/adjusted to the customer’s requirements/wishes.
Check the ROOM and CURVE, MIN, MAX CURVE5, CURVE0, CURVE-5 and HEAT STOP settings.
Adjust incorrect values in the heat pump’s control computer.
ROOM = Desired indoor temperature CURVE = Should be set so that the
desired indoor temperature (ROOM) is maintained regardless of the outdoor temperature.
MIN = Lowest set-point value on the sup­ply line regardless of the outdoor tem­perature (on the condition that heat stop does not apply).
MAX = Highest set-point value on the supply line regardless of the outdoor temperature.
CURVE5,0,-5 = The supply temperature can be adjusted up or down 5°C at these outdoor tem­peratures.
HEAT STOP = Stops all production of heat when the outdoor temperature is the same as or greater than the set value. To exit heat stop the outdoor tempera­ture must drop to 3°C below the set value.
2. Incorrectly positioned/installed sen-
sors.
Check that outdoor sensors and any room sensors are installed according to the instructions and that they are calibrated.
Check that the room sensor is posi­tioned in a suitable place that is rep­resentative of the building and cali­brate it if necessary. Avoid placing near external doors, windows and heat sources.
Install the outdoor sensor according to the instructions and calibrate it, if necessary.
Service instructions VMGFJ102 – 27
3.5.6 Other
Table 23. Problem – The heat pump runs and runs but never stops
Cause Troubleshooting Remedy
1. Air in the heating system. Listen for air in the heat pump and heat-
ing system.
Bleed the heating system according to the installation instructions.
2. Changed conditions Have you
increased your heating and/or hot water demand?
If the heat pump has been dimen­sioned for a certain demand and this demand is increased, the heat pump might not be able to maintain the desired room temperature.
If hot water consumption increases, a larger proportion of time is used to produce hot water, which means less time for heat production.
If the heat pump cannot cope with the demand, replace it with one with a higher output or supplement it with a higher output auxiliary heater.
3. Lack of refrigerant, not enough
refrigerant in the system.
Using manometer apparatus and ther­mometer, check that the unit’s overheat­ing is correct for the specific refrigerant.
Follow the correct procedure (depend­ing on type of refrigerant) to add the cor­rect amount of refrigerant.
If there appears to be a leak in the refrig­erant circuit, carry out leak tracing and any necessary corrective action. If leak tracer is not available, brush soap water on the suspected leak and look for bub­bles. Also check for oil as this can come out from the refrigerant circuit.
Table 24. Problem – Runs on electric heating element
Cause Troubleshooting Remedy
1. Operating mode AUX. HEATER is
selected.
If this operating mode is selected, the auxil­iary heater is used for heating and hot water production, not the compressor.
If AUX. HEATER mode is selected and you no longer want it, change to AUTO, the heat pump then controls both the compressor and auxiliary heater.
2. The compressor cannot run due to
an alarm.
Check the alarm that is indicated in the dis­play.
Rectify the problem and rest the alarm. See Operational problems, Page 14.
3. The integral value has reached the
start level for the auxiliary heater.
Check what the integral value is in the con­trol system.
If the auxiliary heater is in operation because the integral value has counted down to the start value, the computer reacts as it should, see the Installation instructions for further information.
4. Peak heat operation (anti-legion-
ella function) is running.
Check if the heat pump runs peak heat. Peak heat operation occurs in connec-
tion with hot water production with the set interval. The compressor should then start to produce hot water and 2 minutes later the auxiliary heater starts. The compressor must then stop and the stop temperature be reached with only the auxiliary heater connected. Take no corrective action.
28 – Service instructions VMGFJ102
Cause Troubleshooting Remedy
5. The heat pump has stopped on
HIGH RETURN.
Check what the MAX RETURN value is set at in the heat pump’s control com­puter. It must be adjusted to the unit’s maximum supply temperature and the system’s delta temperature so that it does not cut at too high a return tem­perature when the highest supply temperature is transmitted.
Check what the return line sensor shows. Is it a plausible/actual value? If not, take a resistance reading from the sensors and check against the ohm table in Measurement points, Page 11.
If the MAX RETURN value is not adjusted for the system according to the trouble­shooting window, adjust it.
If the sensor is defective, replace it.
6. The compressor runs backwards.
The incoming phases have the incor­rect sequence (only applies to 3­phase heat pumps).
If the compressor runs backwards, it will not cope with compressing the refrigerant and therefore does not produce the correct power, which leads to the control system request­ing auxiliary heating.
If the text ERR PHASE SEQ. appears in the display when the heat pump is powered, (only appears in the first 10 minutes) this means that the phases have the incorrect sequence.
When the compressor is running, check the pressure pipe temperature by feeling the pressure pipe. If the phases are correctly sequenced it should be hot (not just warm) even a distance from the compressor.
When the compressor runs with the phases incorrectly sequenced a strange noise may be heard (loud, rat­tling) when the compressor runs back­wards.
If the phases are in the incorrect order, switch two incoming phases at the main terminal block and recheck according to the troubleshooting window.
7. Changed conditions Have you
increased your heating and/or hot water demand?
If the heat pump has been dimen­sioned for a certain demand and this demand is increased, the heat pump might not be able to maintain the desired room temperature.
If hot water consumption increases, a larger proportion of time is used to produce hot water, which means less time for heat production.
If the heat pump cannot cope with the demand, replace it with one with a higher output or supplement it with a higher output auxiliary heater.
Table 25. Problem – The auxiliary heater is in operation but not the compressor
Cause Troubleshooting Remedy
1. Operating mode AUX. HEATER is
selected.
If this operating mode is selected, the auxiliary heater is used for heating and hot water production, not the compres­sor.
If AUX. HEATER mode is selected and you no longer want it, change to AUTO, the heat pump then controls both the compressor and auxiliary heater.
2. Peak heat operation (anti-legionella
function) is running.
Check if the heat pump runs peak heat. Peak heat operation occurs in connec-
tion with hot water production with the set interval. The compressor should then start to produce hot water and 2 minutes later the auxiliary heater starts. The compressor must then stop and the stop temperature be reached with only the auxiliary heater connected. Take no corrective action, this is normal.
3. The compressor cannot run due to
an alarm.
Check the alarm that is indicated in the display.
Rectify the problem and rest the alarm.
Service instructions VMGFJ102 – 29
Cause Troubleshooting Remedy
4. The heat pump has stopped on high
return.
Check what the MAX value is set at in the heat pump’s control computer. It must be adjusted to the unit’s maxi­mum supply temperature and the system’s delta temperature so that it does not cut at too high a return temperature when the highest sup­ply temperature is transmitted.
Check what the return line sensor shows. Is it a plausible/actual value? If not, take a resistance reading from the sensors and check against the ohm table in Measurement points, Page 11.
If the MAX RETURN value is not adjusted for the system according to the troubleshooting window, adjust it.
If the sensor is defective, replace it.
5. The compressor has been stopped
by the operating pressure switch or delivery line sensor.
Check if a square appears in the display’s lower left corner. If so, the operating pres­sure switch is open or the delivery pipe sensor triggers an alarm for too high tem­perature.
The operating pressure switch is most easily checked by using a buz­zer to see if it is connected.
The pressure pipe sensor value is read off from the control system in the HEAT PUMP menu. Is it a plausi­ble/actual value? If not, take a resist­ance reading from the sensor and check against the ohm table in Meas­urement points, Page 11.
The compressor has been stopped by the delivery line sensor and you have established that it shows the correct temperature. This may have been caused by a leak in the refrigerant cir­cuit.
If the operating pressure switch has stuck in the open position, try gently tapping on the pressure switch head. If this does not help, or it sticks in the open position repeatedly, replace the pressure switch. If the delivery line sen­sor is defective, replace it. If the delivery line temperature gets so hot that the compressor stops, start by leak-tracing the unit. Rectify the leak, if a leak is found. If no leak is found, try draining and refilling the unit and then restarting the heat pump and seeing what the delivery line temperature is. If the prob­lem persists, replace the compressor.
6. The compressor runs backwards. The
incoming phases have the incorrect sequence (only applies to 3-phase heat pumps). If the compressor runs back­wards, it will not cope with compress­ing the refrigerant and therefore does not produce the correct power, which leads to the control system requesting auxiliary heating.
If the text ERR PHASE SEQ. appears in the display when the heat pump is powered, (only appears in the first 10 minutes) this means that the phases have the incorrect sequence.
When the compressor is running, check the pressure pipe temperature by feeling the pressure pipe. If the phases are correctly sequenced it should be hot (not just warm) even a distance from the compressor.
When the compressor runs with the phases incorrectly sequenced a strange noise may be heard (loud, rattling) when the compressor runs backwards.
If the phases are in the incorrect order, switch two incoming phases at the main terminal block and recheck according to the troubleshooting window.
7. The built-in overheating protection
(bi-metal protection) in the compres­sor has tripped.
Check if the heat pump’s control com­puter indicates that the compressor is in operation, and if there is voltage in the soft-starter control inputs. Then read off and check that there is voltage on the compressor’s electrical connection(s).
If there is voltage on the compressor’s electrical connection(s) and the over­heating protection does not close when the compressor has not run and has cooled down for at least 1 hour, replace the compressor.
30 – Service instructions VMGFJ102
Table 26. Problem – The heat pump consumes too much energy
Cause Troubleshooting Remedy
1. Blocked strainer in the heating sys-
tem.
Check that the strainer is not blocked. Clean the strainer if necessary.
2. The compressor cannot run due to
an alarm.
Check the alarm that is indicated in the dis­play.
Rectify the problem and rest the alarm. See section Alarm, Page 15.
3. Incorrect flow over hot side of the
heat pump.
Measurement check what the difference between the supply and return line is using a thermometer (∆t). The difference should be about 8°C (can vary depending on refrigerant). A lower ∆t results in reduced efficiency in the heat pump.
Adjust the system to obtain the correct ∆t.
4. The heat pump’s control computer
is not set/adjusted to the customer’s requirements/wishes.
Check the ROOM and CURVE and MIN set­tings.
Adjust incorrect values in the heat pump’s control computer. ROOM = Desired indoor temperature CURVE = Should be set so that the desired indoor temperature (ROOM) is maintained regardless of the outdoor temperature. MIN = Lowest set-point value on the supply line regardless of the outdoor temperature.
5. The interval for peak heat opera-
tion has changed to a lower value than the factory set value. This results in the heat pump going into peak heat operation more often than cal­culated.
Check the specified interval for peak heat operation in the control computer.
If there is a shorter interval between the peak heat productions, this explains why the unit consumes more current than calculated, but this does not mean for sure that it should be increased, there might be a reason why the interval has been changed.
6. The heat pump has stopped on
HIGH RETURN.
Check what the MAX RETURN value is set at in the heat pump’s control com­puter. It must be adjusted to the unit’s maximum supply temperature and the system’s delta temperature so that it does not cut at too high a return tem­perature when the highest supply temperature is transmitted.
Check what the return line sensor shows. Is it a plausible/actual value? If not, take a resistance reading from the sensors and check against the ohm table in Measurement points, Page 11.
If the MAX RETURN value is not adjusted for the system according to the trouble­shooting window, adjust it. If the sensor is defective, replace it.
7. The compressor runs backwards.
The incoming phases have the incor­rect sequence (only applies to 3­phase heat pumps). If the compressor runs backwards, it will not cope with compressing the refrigerant and therefore does not produce the cor­rect power, which leads to the control computer requesting auxiliary heat­ing.
If the text ERR PHASE SEQ. appears in the display when the heat pump is powered, (only appears in the first 10 minutes) this means that the phases have the incorrect sequence.
When the compressor is running, check the pressure pipe temperature by feeling the pressure pipe. If the phases are correctly sequenced it should be hot (not just warm) even a distance from the compressor.
When the compressor runs with the phases incorrectly sequenced a strange noise may be heard (loud, rat­tling) when the compressor runs back­wards.
If the phases are in the incorrect order, switch two incoming phases at the main terminal block and recheck according to the troubleshooting window.
Service instructions VMGFJ102 – 31
Cause Troubleshooting Remedy
8. The compressor has been stopped
by the operating pressure switch or delivery line sensor.
Check if a square appears in the display’s lower left corner. If so, the operating pres­sure switch is open or the delivery pipe sensor triggers an alarm for too high tem­perature.
The operating pressure switch is most easily checked by using a buzzer to see if it is connected.
The delivery line sensor value is read off from the control computer in the HEAT PUMP menu. Is it a plausible/ actual value? If not, take a resistance reading from the sensor and check against the ohm table in the installa­tion instructions.
The compressor has been stopped by the delivery line sensor and you have established that it shows the correct temperature. This may have been caused by a leak in the refrigerant cir­cuit.
If the operating pressure switch has stuck in the open position, try gently tapping on the pressure switch head. If this does not help, or it sticks in the open position repeatedly, replace the pressure switch. If the delivery line sen­sor is defective, replace it. If the delivery line temperature gets so hot that the compressor stops, start by leak-tracing the unit. Rectify the leak, if a leak is found. If no leak is found, try draining and refilling the unit and then restarting the heat pump and seeing what the delivery line temperature is. If the prob­lem persists, replace the compressor.
9. Expansion valve defective or incor-
rectly set.
Using manometer apparatus and ther­mometer check what the overheating read­ing of the unit is.
If the expansion valve is defective, replace it.
10. Lack of refrigerant, not enough
refrigerant in the system.
Using manometer apparatus and ther­mometer, check that the unit’s overheating is correct for the specific refrigerant.
If there appears to be a leak in the refrig­erant circuit, carry out leak tracing and any necessary corrective action. If leak tracer is not available, brush soap water on the suspected leak and look for bub­bles. Also check for oil as this can come out from the refrigerant circuit.
11. Overfilled refrigerant circuit. Using manometer apparatus and ther-
mometer, check that the unit’s overheating is correct for the specific refrigerant.
Follow the correct procedure (depend­ing on type of refrigerant) to add the correct amount of refrigerant.
12. Changed conditions Have you
increased your heating and/or hot water demand?
If the heat pump has been dimen­sioned for a certain demand and this demand is increased, the heat pump might not be able to maintain the desired room temperature.
If hot water consumption increases, a larger proportion of time is used to produce hot water, which means less time for heat production.
If the heat pump cannot cope with the demand, replace it with one with a higher output or supplement it with a higher output auxiliary heater.
32 – Service instructions VMGFJ102
Table 27. Problem – Auxiliary heater cuts in too soon
Cause Troubleshooting Remedy
1. The heat pump’s control computer
is not set/adjusted to the customer’s requirements/wishes.
Check the ROOM, CURVE, INTEGRAL A1 and INTEGRAL A2 settings
Adjust incorrect values in the heat pump’s control computer. ROOM = Desired indoor temperature CURVE = Should be set so that the desired indoor temperature (ROOM) is maintained regardless of the outdoor temperature. INTEGRAL A1 = Start value for the com­pressor. INTEGRAL A2 = Start value (cal­culated from A1) for the auxiliary heater.
2. Changed conditions Have you
increased your heating and/or hot water demand?
If the heat pump has been dimen­sioned for a certain demand and this demand is increased, the heat pump might not be able to maintain the desired room temperature.
If hot water consumption increases, a larger proportion of time is used to produce hot water, which means less time for heat production.
If the heat pump cannot cope with the demand, replace it with one with a higher output or supplement it with a higher output auxiliary heater.
3. Lack of refrigerant, not enough
refrigerant in the system.
Using manometer apparatus and ther­mometer, check that the unit’s overheating is correct for the specific refrigerant.
If there appears to be a leak in the refrig­erant circuit, carry out leak tracing and any necessary corrective action. If leak tracer is not available, brush soap water on the suspected leak and look for bub­bles. Also check for oil as this can come out from the refrigerant circuit.
Table 28. Problem – Short operating times despite heating demand
Cause Troubleshooting Remedy
ROOM and/or CURVE set too high in combination with a heating system with poor circulation due to closed radiator valves, too small elements or insufficient water volume. A tight fit­ting system with poor pipe dimen­sions may produce the same phe­nomena.
Check if the heat pumps starts, if the sup­ply temperature rises quickly whilst noth­ing happens to the return temperature. If this happens and the heat pump is stopped by the hysteresis function to later quickly drop in temperature (supply) in order to start again, but cannot due to time condi­tions in regulation, this means that the heat pump cannot transport the heat away from the condenser as it should. In such a case, hysteresis starts and stops the heat pump often.
Adjust ROOM and CURVE if necessary. Ensure that there is sufficient flow over the condenser and the heating circuit.
Table 29. Problem – Connection of external AH
Cause Troubleshooting Remedy
Incorrectly connected auxiliary heater. Does not start when the control com­puter gives the signal.
Check the connection against the instruc­tions/wiring diagram. Test the function in manual mode.
If the auxiliary heater is incorrectly con­nected, reconnect according to the instructions.
Service instructions VMGFJ102 – 33
3.5.7 Heat pump
Table 30.
Problem – Noise/loud noise
Cause Troubleshooting Remedy
1. Positioning the heat pump. Determine whether the heat pump can
be moved to a more suitable location.
Move the heat pump if possible.
2. Connection/wall lead-ins. Check that the unit is installed according
to the instructions.
Rigid mountings can generate noise from the heat pump via walls in the house.
Table 31. Problem – Defrosting problems
Cause Troubleshooting Remedy
Location/calibration of the outdoor sensor.
Check that the outdoor sensor is installed according to the installation instructions and that it is correctly calibrated.
Install according to the instructions and calibrate, if necessary.
Defrost sensor calibration Check that the defrost sensor is installed
according to the installation instructions and that it is correctly calibrated.
Calibrate if necessary.
Table 32. Problem – Build-up of ice under and around the outdoor unit
Cause Troubleshooting Remedy
Insufficient drainage. Does a lot of ice accumulate under and
around the outdoor unit because the mel­ted water has nowhere to run?
Drain the ground under and around the outdoor section or install a drainpipe routed to an indoor drain or gully. NOTE! Install a heating cable in the drainpipe.
Table 33. Problem – Water run-off by the outdoor unit, risk of moisture problems in house foundations
Cause Troubleshooting Remedy
Insufficient drainage. During some periods when the outdoor
unit is being defrosted, large amounts of water can run off.
Drain the ground under and around the outdoor unit so that it can cope with the extra amount of water produced because of defrosting or install a drain­pipe routed to an indoor drain or gully. NOTE! Install a heating cable in the drainpipe.
34 – Service instructions VMGFJ102
VMGFJ102
Loading...