Danfoss DGS Series User Manual

Danfoss Gas Sensor
Type DGS Modbus or Service Tool display operation
User Guide
danfoss.com
1. Intended use .....................................................................................4
2. Content ..........................................................................................4
3. Operation ........................................................................................4
3.1 Function of the keys and LEDs on the keypad ................................................6
3.2 Setting / changing of parameters and set points .............................................6
3.3 Code Levels.................................................................................7
4. Menu Overview ..................................................................................7
4.1 Error status ............................................................................... 10
4.2 Alarm Status .............................................................................. 10
4.3 Relay Status............................................................................... 10
4.4 Menu Measuring Values ................................................................... 11
4.5 Display Parameters........................................................................ 11
4.5.1 Software Version ........................................................................ 11
4.5.2 Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.5.3 LCD Function Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.6. Measuring Point Parameters ..............................................................12
4.6.1 Alarm limits ............................................................................. 12
4.6.2 Alarm delay ............................................................................. 12
4.7 Menu System Parameters..................................................................13
4.7.1 AO function .............................................................................13
4.8 Operating data............................................................................ 14
4.9 Calibration................................................................................ 15
4.9.1 Zero Calibration .........................................................................16
4.9.2 Gain Calibration .........................................................................17
4.9.3 Zero-point calibration of Analog output.................................................. 18
4.10 Addressing .............................................................................. 18
5. Modbus menu survey .......................................................................... 19
6. Technician use only! ............................................................................ 22
6.1 Regular test............................................................................... 22
6.2 Locaton................................................................................... 22
7. Ordering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
User Guide | Danfoss Gas sensor. Type DGS. Modbus or Service Tool display operation
2 | RS8KD102
© Danfoss | DCS (ADAP-KOOL®) | 2018.12
User Guide | Danfoss Gas sensor. Type DGS. Modbus or Service Tool display operation
© Danfoss | DCS (ADAP-KOOL®) | 2018.12
RS8KD102 | 3
User Guide | Danfoss Gas sensor. Type DGS. Modbus or Service Tool display operation
4 | RS8KD102
© Danfoss | DCS (ADAP-KOOL®) | 2018.12
1 Intended use
The display of the handheld Service Tool and the Modbus interface for integration with Building Management Systems is used as interface for operation, commissioning and calibration of the DGS gas detection unit
2 Content
This user guide contains the maximum possible functionality of concerned display devices.
Depending on the DGS type some features described here are not possible and therefore the menu items may be hidden.
Some features are available from Modbus or handheld Service Tool interface only. Differences is highlighted in this document.
3 Operation
The configuration and service is made via the handheld Service Tool or in combination with the Modbus interface. Security is provided via password protection against unauthorized intervention.
Handheld Service Tool:
Operation is done via 6 buttons.
AK-SM 800 Front End:
The configuration is done via the graphical display and buttons or via the PC tools StoreView Desktop or AK-ST 500.
Gas D etection Service Tool
Esc
←─
D1 CO2 ppm Warm-up Time
DGS Service Tool
User Guide | Danfoss Gas sensor. Type DGS. Modbus or Service Tool display operation
© Danfoss | DCS (ADAP-KOOL®) | 2018.12
RS8KD102 | 5
Operation with the handheld Service Tool is described in sections 3.1 and 3.2 and chapter 4.
Operation with the Danfoss Front End is described in chapter 5.
2 functions are configured via jumpers on the DGS.
Jumper 4, JP 4, located on the bottom left is used to configure the Modbus baud rate. As default the baud rate is 38.400 Baud. By removing the jumper the baud rate is changed to
19.200 Baud. Removing the jumper is required for integrating with Danfoss System Managers AK­SM 720 and AK-SM 350.
Jumper 5, JP5, located on the top left is used to configure the analogue output type. As default this is Voltage output. By removing the jumper this is change to Current output.
Note: the DGS must be power cycled before any change to JP4 take effect.
JP5
5
4
2
1
not used
GND
AO_01
DI_01
S&H supply
x1
open: 0-20mA closed: 0-10V
LED Yellow/Green/Red
1
2
3
1
2
3
x6
x5
Rel. 3
Rel. 1
x4
4
3
2
1
not used
JP3 JP2 JP1
x3
Ackn.-/Test button
Sensor 1
Sensor 2
Tool
x9
x2
x8
B&L
JP4
Danfoss
80Z790.1
1
open: 19200 Baud closed: 38400 Baud
B­Modbus A+
-
24V ac/dc
+
(critical)
(warning)
User Guide | Danfoss Gas sensor. Type DGS. Modbus or Service Tool display operation
6 | RS8KD102
© Danfoss | DCS (ADAP-KOOL®) | 2018.12
3.1 Function of the keys and LEDs on the keypad
Exits programming, returns to the previous menu level.
Enters sub menus, and saves parameter settings.
Scrolls up & down within a menu, changes a value.
Change of cursor position.
The status LEDs indicate the operating state.
Green Continuous = Operating voltage Flashing = Maintenance message
Yellow Continuous = Failure Slowly flashing = Warming-up Fast flashing = Special mode
Red = Alarm
The backlight of the display changes from green to red when an alarm is active.
3.2 Setting / changing of parameters and set points
Open desired menu window. Code input field opens automatically, if no code is approved.
Set the desired parameter / set point with the keys.
After input of valid code the cursor jumps onto the first position segment to be changed.
Push the cursor onto the position segment, which has to be changed.
Save the changed value, confirm storage (ENTER).
Cancel the save / close editing / return to a higher menu level (ESCAPE function).
User Guide | Danfoss Gas sensor. Type DGS. Modbus or Service Tool display operation
© Danfoss | DCS (ADAP-KOOL®) | 2018.12
RS8KD102 | 7
3.3 Code Levels
All inputs and changes are protected by a four-digit numeric code (= password) against unauthorised intervention according to the regulations of all national and international standards for gas warning systems. The menu windows of status messages and measuring values are visible without entering a code.
The access to the protected features is cancelled automatically if no button is pushed within 15 minutes.
The service technician access code to the protected features is ‘1234’
4 Menu Overview
Menu operation is done via a clear, intuitive and logical menu structure. The operating menu contains the following levels:
• Starting menu with indication of the device type if no Measuring Point is registered, otherwise scrolling display of the gas concentrations of all registered sensors in 5-second intervals. If alarms are active, only the values of the sensors currently in alarm status are displayed.
• Main menu
• 5 sub menus under “Installation and Calibration”
Power On Time of the basic device Second counter counts down, when communication display <> basic device is OK. In case of communication error the count-down will stop.
“Warm-up Time” is displayed. As soon as the sensor warm-up time has expired, the measured value is displayed = measuring mode.
Seconds indicator = 0
After about 2 seconds
Power On Time 19s
Danfoss
DGS
D1 CO2 ppm Warm-up Time
User Guide | Danfoss Gas sensor. Type DGS. Modbus or Service Tool display operation
8 | RS8KD102
© Danfoss | DCS (ADAP-KOOL®) | 2018.12
4 Menu Overview
(Continued)
Starting menu
Main menu
Error Status
Alarm Status
Relay Status
Measuring Values
Display Parameters
Installation & Calibration
Reading and acknowledgement of errors See chapter 4.1
Display of the status of active alarms See chapter 4.2
Display of the relay status. Protected by password. See chapter 4.3
Display of measuring values See chapter 4.4
Read-out of handheld tool version, language and set-up of language. Partly protected by password See chapter 4.5
Reading and change of the relay, measuring point and system parameters as well as test and calibration functions
Chapter #
Loading...
+ 16 hidden pages