Danfoss DGS-SC, DGS-IR Installation And Operation Manual

Danfoss Gas Sensor
Type DGS-SC and DGS-IR with MODBUS
Installation and Operation Guide
ADAP-KOOL® Refrigeration Control System
© Danfoss | ADAP-KOOL® | 2016.12
2 | RS8HJ102 |
Contents
1. Overview ..................................................................................3
1.1 General Information .................................................................. 3
1.2 Technical Specifications ........................................................... 3
2. General Placement Guidelines ...............................................4
2.1 Machinery Rooms ...................................................................... 4
2.2 Refrigerated Spaces................................................................... 4
2.3 Chillers............................................................................................ 4
2.4 Air Conditioning (Direct Systems VRF/VRV) ..................... 5
3. Dimensions and mounting .....................................................6
4. Installation and Wiring ............................................................7
4.1 Electrical connection and diagram ...................................... 7
4.2 Jumper Configurations ..........................................................10
4.3 Adjusting the Alarm Setpoint .............................................. 11
4.4 System integration ..................................................................12
5. Operation and Stabilisation .................................................13
6. Functional Tests and Calibration ..........................................14
6.1 Introduction ............................................................................... 14
6.2 Bump Testing .............................................................................15
6.3 Calibration Overview .............................................................. 16
6.4 Calculating Calibration Voltage ..........................................16
6.5 Calibrating Semiconductor (SC) Sensors ......................... 16
6.6 Calibrating Infrared (IR) Sensors .........................................16
6.7 Calibration of alarm setpoint ...............................................16
6.8 Calibration of 4-20mA output .............................................16
6.9 Issue Test certificate ................................................................16
7. Installation .............................................................................17
8. Accessories .............................................................................21
9. Troubleshooting ....................................................................22
Appendix A.................................................................................23
Appendix B .................................................................................24
Appendix C .................................................................................25
RS8HJ102 | 3
© Danfoss | ADAP-KOOL® | 2016.12
1. Overview
The DGS Modbus is a state-of-the-art fixed gas detector which can detect a wide range of gases. It can also activate external systems such as fans or shut down and activate sirens, warning lights, activate dial out systems, or connect to BMS systems including Danfoss AK-SM 720/ AK-SM 350 and the AK-SM 800 series.
The DGS Modbus can be used:
• in new buildings/areas that require continuous monitoring.
• to add gas detection solutions to an existing system.
1.1 General Information
1.2 Technical Specifications
Power Supply 12/24V AC/DC ±20%, 50/60 Hz, 2 W max.
Power Consump­tion
SC:153mA / IR: 136mA
Power Monitoring Green LED indication Visual Alarm RED LED indication Audible Alarm Buzzer, enabled/disabled Fault Monitoring Red LED ON ~ Green LED OFF Fault State 0 - 0.5V (1-5V), 0 - 1V(2-10V), 0 - 2mA (4-20mA) Analogue Outputs 0-5V, 1-5V, 0-10V, 2-10V, 4-20mA
Digital Outputs 1-Relay, SPDT, Failsafe configured by Modbus or
by product selection 1-Amp / 24V A.C./D.C. / 120V A.C. Configurable delay by Modbus or by jumper configuration: 0, 1min., 5min., 10min.
IP Enclosure rating IP 41 or IP 66
Temperature Rat­ings
IP 41: -20°C to +50°C ( -4°F to 122°F ) IP 66: -40°C to +50°C (-40°F to +122°F )
Dimensions/ Weights per Enclo­sure Type
IP41 86 x 142 x 53 mm
3.35” x 5.59” x 2.09”
180 g
6.3 oz
IP66 175 x 165 x 82 mm
6.89” x 6.5” x 3.29”
629 g 1 lb 6 oz
IP66 w/ Remote Sensor
175 x 155 x 82 mm
6.89” x 6.1” x 3.29”
790 g 1 lb 11 oz
IP66 Airflow/ Duct *
175 x 125 x 82 mm
6.89” x 4.9” x 3.29”
578 g 1 lb 4 oz
RS-485 Communi­cations
Baud rate : 9,600, 19,200 or 38,400 (default) Start bits: 1 Data bits: 8 Parity: even Stop bits: 1 Retry time: 500ms (min time between retries) End of message: silent 3.5 characters
Approvals
IEC61010-1 RoHS WEEE
* See appendix A for supported air flows and duct sizes
© Danfoss | ADAP-KOOL® | 2016.12
4 | RS8HJ102 |
NOTE: The DGS Modbus should be installed plumb and level and securely fastened to a rigid mounting surface.
Sensors must be located within the appropriate wire lengths from the central control unit (if used). In all cases the sensor supplied is designed for maximum sensitiv­ity to a particular gas. However, in certain circumstances false alarms may be caused by the occasional presence of sufficiently high concentrations of other gaseous impurities. Examples of situ­ations where such abnormalities may arise include the following:
• Plant room maintenance activity involving solvent or paint fumes or refrigerant leaks.
• Accidental gas migration in fruit ripening/storage facilities (ba­nanas - ethylene, apples - carbon dioxide).
• Heavy localised exhaust fumes (carbon monoxide, dioxide, propane) from engine-driven forklifts in confined spaces or close to sensors.
It is recommended setting the alarm delay to minimise false alarms.
2.1 Machinery Rooms
There is no absolute rule in determining the number of sensors and their locations. However, a number of simple guidelines will help to make a decision. Sensors monitor a point as opposed to an area. If the gas leak does not reach the sensor then no alarm will be triggered. Therefore, it is extremely important to care­fully select the sensor location. Also consider ease of access for maintenance. The size and nature of the site will help to decide which method is the most appropriate to use. Locations requiring the most protec­tion in a machinery or plant room would be around compressors, pressurised storage vessels, refrigerant cylinders or storage rooms or pipelines. The most common leak sources are valves, gauges, flanges, joints (brazed or mechanical), filling or draining connec­tions, etc.
• When mechanical or natural ventilation is present, mount a sen­sor in the airflow.
• In machinery rooms where there is no discernible or strong airflow then options are:
Point Detection, where sensors are located as near as possible to the most likely sources of leakage, such as the compressor, expan­sion valves, mechanical joints or cable duct trenches. Perimeter Detection, where sensors completely surround the area or equipment.
• For heavier-than-air gases such as halocarbon and hydrocarbon refrigerants such as R404A, propane, and butane sensors should be located near ground level.
• For lighter-than-air gas (e.g., ammonia), the sensor needs to be located above the equipment to be monitored on a bracket or high on a wall within 300 mm (12 in) of (or on) the ceiling – pro­vided there is no possibility of a thermal layer trapped under the ceiling preventing gas from reaching the sensor.
NOTE: At very low temperatures (e.g., refrigerated cold store), am­monia gas becomes heavier than air.
• With similar density or miscible gases (e.g., CO2), sensors should be mounted about head high (about 1.5 m [5 ft]). However, with CO2 in a machinery room it is recommended to mount it 0.3 m (1 ft) above the floor as the air flow is low and CO2 slightly heavier than air.
• Sensors should be positioned just far enough back from any high-pressure parts to allow gas clouds to form and be detected. Otherwise, a gas leak might pass by in a high-speed jet and not be detected by the sensor.
• Make sure that pits, stairwells and trenches are monitored since they may fill with stagnant pockets of gas.
• For racks or chillers pre-fitted with refrigerant sensors, these should be mounted so as to monitor the compressors. If extract ducts are fitted the airflow in the duct may be monitored.
2.2 Refrigerated Spaces
In refrigerated spaces, sensors should be located in the return airflow to the evaporators on a sidewall (below head-high is preferred), or on the ceiling, not directly in front of an evapora­tor. In large rooms with multiple evaporators, sensors should be mounted on the central line between 2 adjacent evaporators, as turbulence will result in airflows mixing.
2.3 Chillers
In the case of small water- or air-cooled enclosed chiller units mount the sensor so as to monitor airflow to the extract fans. With larger models also place a sensor inside the enclosure under or adjacent to the compressors. In the case of outdoor units:
• For enclosed air-cooled chillers or the outdoor unit for vari­able refrigerant volume and variable refrigerant flow (VRV/VRF) systems, mount the sensor so as to monitor airflow to the extract fan. With large units also place a sensor inside the enclosure under or adjacent to the compressors. In the case of non-enclosed outdoor units:
• If there is an enclosed machinery section locate a sensor there.
• In the case of units with enclosed compressors, mount sensors in the enclosures.
• Where you have protective or acoustic panels mount the sensor low down under the compressors where it is protected by the panels.
• With air-cooled chillers or air-cooled condensers with non­enclosed condenser sections it is difficult to effectively monitor leaks in the coil sections. With some designs it will be possible using an airflow sensor to monitor airflow to the start–up fans in the front or rear sections.
• If there is a possibility of refrigerant leaks into a duct or air-han­dling unit install a sensor to monitor the airflow. Weatherproof sensors should be used for unprotected outdoor applications.
2. General Placement Guidelines
RS8HJ102 | 5
© Danfoss | ADAP-KOOL® | 2016.12
2.4 Air Conditioning (Direct Systems VRF/VRV)
For compliance with EN378, at least one detector shall be installed in each occupied space being considered and the location of de­tectors shall be chosen in relation to the refrigerant and they shall be located where the refrigerant from the leak will collect. In this case refrigerants are heavier than air and detectors should have their sensors mounted low, e.g., at less than bed height in the case of an hotel or other similar Category Class A spaces. Ceilings or other voids if not sealed are part of the occupied space.
CAUTION: Monitoring ceiling voids in a hotel room would not strictly comply with EN378.
Best practice installation includes installing the gas detector at a height below the room occupants. E.g. in a hotel room this is less than bed height (between 200 and 500 mm [8 and 20 inches] off the floor).
Ensure the sensor is mounted away from drafts and heat sources like radiators etc. and avoid sources of steam.
Avoid mounting it under mirrors, at vanity units and in or near bed bathrooms.
© Danfoss | ADAP-KOOL® | 2016.12
6 | RS8HJ102 |
3. Dimensions and mounting
DGS Modbus Standard Housing
50 mm
75 mm
IP66 (with Splashguard)
Splashguard
IP66 Airflow Duct Mount Housing
mounting slots = 9mm long x 6mm wide use 5mm ­6mm screws
mounting measurements
2
3
4
IP66 Housing with Remote Sensor Head
M42 thread
5
mounting slots = 9mm long x 6mm wide use 5mm ­6mm screws
RS8HJ102 | 7
© Danfoss | ADAP-KOOL® | 2016.12
4. Installation and Wiring
WARNING
Explosion hazard! Do not mount the DGS Modbus in an area that may contain flammable liquids, vapors, or aerosols. Operation of any electrical equipment in such an environment constitutes a safety hazard.
CAUTION
The DGS contains sensitive electronic components that can be easily damaged. Do not touch nor dis­turb any of these components.
NOTE The mounting location of the monitor should allow
it to be easily accessible for visual monitoring and servicing.
NOTE The monitor must be connected by a marked, suit-
ably located and easily reached switch or circuit­breaker as means of disconnection
NOTE Connect monitor power and signaling terminals us-
ing wiring that complies with local electrical codes or regulations for the intended application.
NOTE This instrument can be equipped with a semicon-
ductor sensor for the detection of refrigerant, com­bustible or VOC gases. Semiconductor sensors are not gas specific and respond to a variety of other gases including propane exhaust, cleaners, and sol­vents. Changes in temperature and humidity may also affect the sensor’s performance.
4.1 Electrical connection and diagram
NOTE: The wiring is the same for the semi-conductor and infrared
models. The controller wiring is the same for all controllers.
There is a 5-minute power-up delay to allow the sensor to stabi­lise. Also see section 5. Refer to Figure 1 for internal components and wiring.
© Danfoss | ADAP-KOOL® | 2016.12
8 | RS8HJ102 |
Figure 1a. Sensor Components (IR sensor)
Figure 1b. Sensor Components (SC Sensor)
Danfoss
80Z731.10
Alarm
P1
J4
Reset
TP1 (Alarm)
Delay
J5 J6
INFRARED (IR) SENSOR PC BOARD
GREEN LED
RED LED
P4
4-20mA
TP2 (Vs)
P3
Span
TP3 0V
J7 J8 J9 J10
CN4
0012
510510
G+
_
MODBUS
VOLTS
Audible Alarm
J3
Addressing
AC Select
J1
CN1
CN2 CN3 DC Select
0V V+
0V V I
Power Supply
Output Signal
Relay Out
N / O
COM
N / C
J2
Zero
P2
TX
+V
-V
RX
SIGNAL
SW1SW2
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Danfoss
80Z730.10
Alarm
P1
J4
Reset
TP1 (Alarm)
Delay
J5 J6
SEMICONDUCTOR (SC) SENSOR PC BOARD
GREEN LED
RED LED
P4
P2
Zero
4-20mATP2
(Vs)
P3
Span
TP3 0V
J7 J8 J9 J10
CN4
0012
510510
G+
_
MODBUS
VOLTS
Audible Alarm
J3
Addressing
AC Select
J1
CN1
CN2 CN3 DC Select
0V V+
0V V I
Power Supply
Output Signal
Relay Out
N / O
COM
N / C
J2
SW1SW2
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Sensor Voltage Test Point
Sensor Voltage Test Point
Board Ground Plane Test Point
Board Ground Plane Test Point
Audible Alarm and Relay Set Point Volage Test Point
Audible Alarm and Relay Set Point Volage Test Point
Loading...
+ 18 hidden pages