3. Installation and maintenance .......................................................................................................3
3.1 Technician use only! ............................................................................................................................................ 3
3.2 Regular Test .......................................................................................................................................................... 3
3.8 Installation Test .................................................................................................................................................... 6
5.2 Alarm Status ........................................................................................................................................................ 13
5.3 Relay Status ......................................................................................................................................................... 13
5.4 Menu Measuring Values ...................................................................................................................................13
5.5.1 Software Version ................................................................................................................................... 14
5.5.2 Language ................................................................................................................................................ 14
5.5.3 LCD Function Check .............................................................................................................................14
5.8 AO Settings ..........................................................................................................................................................16
5.9 Operating Data ..................................................................................................................................................17
5.10.1 Zero calibration ..................................................................................................................................... 19
5.10.2 Gain calibration ....................................................................................................................................20
5.10.3 Zero point calibration of analogue output .....................................................................................21
1. Intended useThis document has the intent to provide the guidelines to avoid possible damages deriving from
overvoltage and other possible issues resulting from the connection to the DGS power supply and
the serial communication network. Moreover it provides the operations executed via handheld
Service Tool. The display of the hand-held Service Tool and the MODBUS interface for integration with
Building Management Systems is used as interface for operation, commissioning and calibration of
the DGS gas detection unit.
2. Introduction
3. Installation and
maintenance
3.1 Technician use only!
For what concerns display devices, this user guide contains the maximum possible functionality.
Depending on the DGS type some features described here are not applicable and therefore the menu
items may be hidden.
Some special features are available via the hand-held Service Tool interface only (not via MODBUS).
This includes the calibration routine and certain properties of the sensor head.
This unit must be installed by a suitably qualified
technician who will install this unit in accordance
with these instructions and the standards set
down in their particular industry/country.
Suitably qualified operators of the unit should be
aware of the regulations and standards set down
by their industry/country for the operation of this
unit.
These notes are only intended as a guide, and
the manufacturer bears no responsibility for the
installation or operation of this unit.
Please observe that DGS works as a safety
device securing a reaction to a detected high
gas concentration. If a leakage occurs, the
DGS will provide alarm functions, but it will
not solve or take care of the leakage root
cause itself.
Failure to install and operate the unit in
accordance with these instructions and with
industry guidelines may cause serious injury
including death, and the manufacturer will not
be held responsible in this regard.
It is the installer’s responsibility to adequately
ensure that the equipment is installed correctly
and set up according to the environment and the
application in which the products are being used.
3.2 Regular Test
3.3 Location
To maintain product performance and comply
with the local requirements, the DGS must be
tested regularly.
DGSs are provided with a test button that may be
activated to validate the alarm reactions.
Additionally, the sensors must be tested by either
bump test or calibration.
Danfoss recommends the following minimum
calibration intervals:
DGS-IR: 60 months
DGS-SC: 12 months
DGS-PE: 6 months
For all gases heavier than air, Danfoss
recommends placing the sensor head app. 30 cm
(12”) above the floor and, if possible, in the air
flow. All gases measured with these DGS sensors
are heavier than air: HFC grp 1, HFC grp 2, HFC
grp 3, CO and propane.
For further details on Test and Location please see
the Danfoss Application Guide: “Gas detection in
refrigeration systems”.
With DGS-IR it is recommended to do an annual
bump test in years without calibration.
Check local regulations on calibration or testing
requirements.
For propane: after exposure to a substantial gas
leak, the sensor should be checked by bump test
or calibration and replaced if necessary.
RED flashing: is an indication of alarm due to gas
concentration level. The Buzzer & Light behaves
identical to the status LED.
Ackn. / Test button / DI_01:
TEST: The button must be pressed for 8 sec.
– Critical and warning alarm is simulated and
AO goes to max. (10 V/20 mA), stops on
release.
ACKN: If pressed during critical alarm, as default*
the relays and Buzzer go out of alarm condition
and back on after 5 minutes if the alarm situation
is still active.
* the duration and whether to include the relay
status with this function or not is user defined.
DI_01 (terminals 1 and 2) is a dry-contact
(potential-free) behaving identically to the
Ackn./Test button.
DC supply for external Strobe & Horn
Whether the DGS is powered by 24 V DC or 24
V AC, a 24 V DC power supply (max. 50 mA)
is available between terminals 1 and 5 on
connector x1.
* JP5 open → AO 0 – 20 mA
JP5 closed → AO 0 – 10 V (default)
Note: the DGS must be power cycled before any
change to JP4 takes effect.
Analog Output:
If the analog output AO_01 is used (terminals 4
and 5) then you need the same ground potential
for the AO and the connected device.
Note: JP1, JP2 and JP3 are not used.
3.7 Installation instructions
The DGS is available with one or two sensors and
B&L (Buzzer and Light) as option (see fig. 1).
For sensors that can be poisoned by e.g. silicones
like all semiconductor and catalytic bead sensors,
it is imperative to only remove the protective cap
after all silicones are dry, and then energize the
device.
The sensor protection cap must be removed
before taking the DGS into operation
Mounting and wiring
To wall mount the DGS, unscrew the lid by
releasing the four plastic screws in each corner
and remove the lid. Mount the DGS base to the
wall by fitting screws through the holes which
the lid screws were fastened by. Complete the
mounting by re-applying the lid and fastening
the screws.
The sensor head must always be mounted so that
it points downwards. The DGS-IR sensor head is
sensitive to shock – special attention should be
paid to protect the sensor head from shocks
during installation and operation.
Observe the recommended placing of the sensor
head as stated on page 1.
Extra cable glands are added by following the
instruction in fig. 2.
The exact position of the terminals for the
sensors, alarm relays, digital input and analogue
output is shown in the connection diagrams (see
fig. 3).
The technical requirements and regulations
for wiring, electrical security, as well as project
specific and environmental requirements and
regulations must be met.
Configuration
For convenient commissioning, the DGS is preconfigured and parameterized with factory-set
defaults. See Menu Survey on page 5.
Jumpers are used to change the analogue output
type and the MODBUS baud rate. See fig. 3.
For DGS with Buzzer & Light, alarm actions are
given according to following table below.
System integration
To integrate the DGS with a Danfoss system
manager or general BMS system, set the
MODBUS address using the DGS Service Tool,
using password "1234" when prompted. See the
DGS User Guide for details on operating the DGS
Service Tool.
The Baud Rate is adjusted by jumper JP4. As
default, the setting is 38.4k Baud. For integration
with AK-SM 720/350 change the setting to 19.2k
Baud.
For more information about data communication
see Danfoss document RC8AC--
Sensor replacement
The sensor is connected to the DGS via a plug
connection enabling simple sensor exchange
instead of an on-site calibration.
The internal replacement routine recognizes
the exchanging process and the exchanged
sensor and re-starts the measurement mode
automatically.
The internal replacement routine also examines
the sensor for actual type of gas and actual
measuring range. If the data does not match the
existing configuration, the built-in status LED
indicates an error. If everything is OK the LED will
light up green.
As an alternative, the on-site calibration via the
DGS Service Tool can be performed with the
integrated, user friendly calibration routine.
See the DGS User Guide for details on operating
the DGS Service Tool.
Loss of power to DGSOFFOFFX (closed)
Gas signal < warning alarm
threshold
Gas signal > warning alarm
threshold
Gas signal > critical alarm
threshold
Gas signal ≥ critical alarm
threshold, but ackn. button
pressed
No alarm, no faultOFFGREEN
No fault, but maintenance dueOFFGREEN Slow
Sensor communication errorOFFYELLOW
DGS in special modeOFFYELLOW flashing
Alarm thresholds can have the same value, therefore both the relays and the Buzzer and Light can be triggered
simultaneously.
The alarm thresholds have a hysteresis of app. 5%
* whether to include the relay status with the acknowledge function or not is user defined.
** If the DGS has two sensors and the "Room Mode" is configured to "2 rooms", then relay 1 acts as a critical
relay for sensor 1 and relay 3 acts as a critical relay for sensor 2. Both relays are SPDT NC. The Buzzer and Light
operation is independent of the "Room Mode" setting.
Buzzer
OFFGREEN
OFFRED Slow flashing X (closed)
ONRED Fast flashing X (closed)X (closed)
OFF
(ON after
delay)
3.8 Installation TestAs DGS is a digital device with self-monitoring,
all internal errors are visible via the LED and
MODBUS alarm messages.
All other error sources often have their origins in
other parts of the installation.
For fast and comfortable installation test we
recommend proceeding as follows.
Optical Check
Right cable type used.
Correct mounting height according to definition
in the section about mounting.
LED status – see DGS trouble shooting.
Reaction
Light
RED Fast flashing X (closed)*(open)*
flashing
Warning relay 1**
SPDT NO
(Normally Open)
Critical relay 3**
SPDT NC
(Normally closed)
In doing so, the set alarm thresholds are
exceeded, and all output functions are activated.
It is necessary to check if the connected output
functions are working correctly (e.g. the horn
sounds, the fan switches on, devices shut down).
By pressing the push-button on the horn, the
horn acknowledgement must be checked. After
removal of the reference gas, all outputs must
automatically return to their initial position.
Other than the trip testing, it is also possible to
perform a functional test by means of calibration.
For further information, please refer to the User
Guide.
Functional test (for initial operation and
maintenance)
Functional test is done by pressing the test
button for more than 8 seconds and observing
that all connected outputs (Buzzer, LED, Relay
connected devices) are working properly. After
deactivation all outputs must automatically
return to their initial position.
Zero-point test (if prescribed by local
regulations)
Zero-point test with fresh outdoor air.
A potential zero offset can be read out by use of
the Service Tool.
Trip test with reference gas (if prescribed by
local regulations)
The sensor is gassed with reference gas (for this
you need a gas bottle with pressure regulator
and a calibration adapter).
Comparing sensor gas type with DGS
specification
The replacement sensor specification must match
the DGS specification.
The DGS software automatically reads the
specification of the connected sensor and
compares with the DGS specification.
This feature increases the user and operating
security.
New sensors are always delivered factorycalibrated by Danfoss. This is documented by the
calibration label indicating date and calibration
gas. A re-calibration is not necessary during
commissioning if the device is still in its original
packaging (including air-tight protection by
the red protective cap) and if the calibration
certificate has not expired
• DGS MODBUS was possibly damaged in transit. Check by installing another DGS
to confirm the fault.
Green flashing• The sensor calibration interval has been exceeded or the sensor has reached the
end of life. Carry out calibration routine or replace with a new factory calibrated
sensor.
Yellow• AO configured but not connected (only 0 – 20 mA output). Check wiring.
• Sensor type does not match DGS specification. Check gas type and measuring
range.
• Sensor may be disconnected from printed circuit board. Check to see if the sensor
is properly connected.
• The sensor has been damaged and needs to be exchanged. Order replacement
sensor from Danfoss.
• Supply voltage out of range. Check power supply.
Yellow flashing • The DGS is set to service mode from the hand-held Service Tool. Change setting
or await time-out within 15 minutes.
Alarms in the absence
of a leak
The zero-measurement
drifts
• If you experience alarms in the absence of a leak, try setting an alarm delay.
• Perform a bump test to ensure proper operation.
The DGS-SC sensor technology is sensitive to the environment (temperature, moist,
cleaning agents, gases from trucks, etc). All ppm measurements below 75 ppm
should be disregarded, i.e. no zero-adjustment made.
Standalone DGS without Modbus network communication
Shield/screen is not required for standalone DGS with no connection to a RS-485 communication line.
However, it can be done as described in the next paragraph (Fig. 4).
DGS with Modbus network communication in combination with other devices powered by the
same power supply
It is strongly recommended to use direct current power supply when:
• more than 5 DGS units are powered by the same power supply
• the bus cable length is longer than 50 m for those powered units
It is moreover recommended to use class 2 power supply (see AK-PS 075)
Make sure to not interrupt the shield when connecting A and B to the DGS (see Fig. 4).
–
A+B
Fig. 4: Loop trough
Shield
A
Shld
B
DGS 1
#adr 10
A
B Gnd
Danfoss
Modbus
device
Fig. 5: Wiring diagram for system with one power supply
Danf
AK-PS 075 power supply
+
+
DGS 2
#adr 11
A
B Gnd
+
1 KΩ
DGS n
#adr xx
A
B Gnd
+
–
Input 230 V
L
230 V
N
Danfoss
80Z876
Ground potential difference between nodes of the RS485 network might affect the communication.
It is advised to connect a 1 KΩ 5% ¼ W resistor between the shield and the ground (X4.2) of any unit
or group of units connected to the same power supply (Fig. 5).
Please refer to Literature No. AP363940176099.
DGS with Modbus network communication in combination with other devices powered by more
than one power supply
It is strongly recommended to use direct current power supply when:
• more than 5 DGS units are powered by the same power supply
• the bus cable length is longer than 50 m for those powered units
It is moreover recommended to use class 2 power supply (see AK-PS 075)
Make sure to not interrupt the shield when connecting A and B to the DGS (see Fig. 4).
1 KΩ
1 KΩ
Shield
DGS 1
#adr n1
A
B Gnd
Shield
DGS 1
#adr n11
A
B Gnd
AK-PS 075 power supply
+
+
+
DGS 2
#adr n2
A
B Gnd
DGS 2
#adr n12
A
B Gnd
+
+
DGS n
#adr nx
A
B Gnd
DGS n
#adr ny
A
B Gnd
+
–
AK-PS 075 power supply
+
+
–
L
230 V
N
L
230 V
N
L
230 V
N
Danfoss
Modbus
device
AK-SM
A
B
Shld
Busslave
L
230 V
N
Danfoss
Modbus
device
AK-CC
A
B
Shld
Fig. 6: Wiring diagram for system with multiple power supplies
Ground potential difference between nodes of the RS485 network might affect the communication.
It is advised to connect a 1 KΩ 5% ¼ W resistor between the shield and the ground (X4.2) of any unit
or group of units connected to the same power supply (Fig. 6).
Please refer to Literature No. AP363940176099.
Power supply and voltage alarm
The DGS device goes into voltage alarm when voltage exceeds certain limits.
The lower limit is 16 V.
The upper limit is 28 V, if DGS software version is lower than 1.2 or 33.3 V in all other cases.
When in the DGS the voltage alarm is active, in the System Manager the “Alarm inhibited” is raised.