Installation Guide
Danfoss Gas Sensor
080R9333
Type DGS
ENGLISH
Technician use only!
This unit must be installed by a suitably qualified technician who
will install this unit in accordance with these instructions and the
standards set down in their particular industry/country.
Suitably qualified operators of the unit should be aware of the
regulations and standards set down by their industry/country for
the operation of this unit.
These notes are only intended as a guide, and the manufacturer
bears no responsibility for the installation or operation of this unit.
Failure to install and operate the unit in accordance with these
instructions and with industry guidelines may cause serious
injury including death, and the manufacturer will not be held
responsible in this regard.
It is the installer’s responsibility to adequately ensure that the
equipment is installed correctly and set up according to the
environment and the application in which the products are being
used.
Please observe that DGS works as a safety device securing a
reaction to a detected high gas concentration. If a leakage
occurs, the DGS will provide alarm functions, but it will not
solve or take care of the leakage root cause itself.
AN284527372096en-000301
Regular Test:
To maintain product performance and comply with the local
requirements, the DGS must be tested regularly.
DGSs are provided with a test button that may be activated to
validate the alarm reactions.
Additionally, the sensors must be tested by either bump test or
calibration.
Danfoss recommends the following minimum calibration intervals:
DGS-IR: 60 months
DGS-SC: 12 months
DGS-PE: 6 months
With DGS-IR it is recommended to do an annual bump test in years
without calibration.
Check local regulations on calibration or testing requirements.
Do not spray or pour pure refrigerant or other liquids onto the
sensor head to perform a bump test. This may significantly reduce
the lifetime of the sensor head or even destroy it.
For propane: after exposure to a substantial gas leak, the sensor
should be checked by bump test or calibration and replaced if
necessary.
Location:
For all gases heavier than air, Danfoss recommends placing the
sensor head app. 30cm (12") above the floor and, if possible, in the
air flow. All gases measured with these DGS sensors are heavier
than air: HFC grp 1, HFC grp 2, HFC grp 3, CO and Propane.
Dimensions and appearance
For further details on Test and Location please see the Danfoss
Application Guide: "Gas detection in refrigeration systems".
Fig. 1
© Danfoss | Climate Solutions | 2022.01
AN284527372096en-000301 | 1
Cable gland opening
148H126_01-2018
Hole punching for cable gland:
1. Select the location for the safest cable entry
2. Use a sharp screwdriver and a small hammer
3. Place the screwdriver and hammer with precision
while moving the screwdriver within a small area
until the plastic is penetrated.
Fig. 2
Danfoss Gas Sensor DGS
5
GND
4
AO_01
not used
2
DI_01
1
S&H supply
x1
LED
Yellow/Green/Red
Sensor 2
x9
open: 0-20mA
closed: 0-10V
B&L
open: 19200 Baud
closed: 38400 Baud
JP5
x8
x2
JP4
Continue precision punching with small movements
until the round piece can be pulled out with your
fingers.
WARNING: be very careful not to damage
the internal board components with the
screwdriver.
Status LED / B&L:
GREEN is power on.
- flashing if maintenance needed
YELLOW is an indicator of Error.
- the sensor head is disconnected or not the expected type
- AO configured as 0 – 20 mA, but no current is
80Z790.1
running
- flashing when sensor is in special mode (e.g. when
- Supply voltage out of range
RED flashing: is an indication of alarm due to gas
concentration level. The Buzzer & Light behaves identical
to the status LED.
x6
x5
Ackn.-/Test
button
1
2
3
1
2
3
Rel. 3
(critical)
Rel. 1
(warning)
4
3
x4
2
1
Danfoss
BMODBUS
A+
24 V AC/D
+
Ackn. / Test button / DI_01:
TEST: The button must be pressed for 8 sec.
Tool
JP3
x3
JP2
JP1
not used
- Critical and warning alarm is simulated and AO goes to
ACKN: If pressed during critical alarm, as default* the relays
and Buzzer go out of alarm condition and back on after 5
minutes if the alarm situation is still active.
* the duration and whether to include the relay status with this
function or not is user defined.
Sensor 1
DI_01 (terminals 1 and 2) is a dry-contact (potential-free)
behaving identically to the Ackn./Test button.
Remove potential burrs and secure flat surfaces.
Install the cable gland according to the enclosed guide.
changing parameters with the Service Tool)
max. (10 V/20 mA), stops on release.
Note: For what concern the power supply, please refer to chapter 3.10 Power Con-
ditions and Shielding Conceptions in the User Guide (BC291049702513en-000201).
A Class II power supply is recommended
Fig. 3
2 | AN284527372096en-000301
DC supply for external Strobe&Horn
Whether the DGS is powered by 24 V DC or 24 V AC, a 24
V DC power supply (max. 50 mA) is available between
terminals 1 and 5 on connector x1.
Jumpers
* JP4 open → 19200 Baud
JP4 closed → 38400 Baud (default)
* JP5 open → AO 0 – 20 mA
JP5 closed → AO 0 – 10 V (default)
Note: the DGS must be power cycled before any change to
JP4 takes effect.
Analog Output:
If the analog output AO_01 is used (terminals 4 and 5) then
you need the same ground potential for the AO and the
connected device.
Note: JP1, JP2 and JP3 are not used.
© Danfoss | Climate Solutions | 2022.01
DGS installation instructions
The DGS is available with one or two sensors and B&L (Buzzer and
Light) as option (see fig. 1).
For sensors that can be poisoned by e.g. silicones like all
semiconductor and catalytic bead sensors, it is imperative to only
remove the protective cap after all silicones are dry, and then
energize the device.
The sensor protection cap must be removed before taking the
DGS into operation
Mounting and wiring
To wall mount the DGS, unscrew the lid by releasing the four
plastic screws in each corner and remove the lid. Mount the DGS
base to the wall by fitting screws through the holes which the lid
screws were fastened by. Complete the mounting by re-applying
the lid and fastening the screws.
The sensor head must always be mounted so that it points
downwards. The DGS-IR sensor head is sensitive to shock – special
attention should be paid to protect the sensor head from shocks
during installation and operation.
Observe the recommended placing of the sensor head as stated
on page 1.
Extra cable glands are added by following the instruction in fig. 2.
The exact position of the terminals for the sensors, alarm relays,
digital input and analogue output is shown in the connection
diagrams (see fig. 3).
The technical requirements and regulations for wiring,
electrical security, as well as project specific and environmental
requirements and regulations must be met.
Configuration
For convenient commissioning, the DGS is pre-configured and
parameterized with factory-set defaults. See Menu Survey on
page 5.
Jumpers are used to change the analogue output type and the
MODBUS baud rate. See fig. 3.
For DGS with Buzzer & Light, alarm actions are given according to
following table below.
System integration
To integrate the DGS with a Danfoss system manager or general
BMS system, set the MODBUS address using the DGS Service Tool,
using password "1234" when prompted. See the DGS User Guide
for details on operating the DGS Service Tool.
The Baud Rate is adjusted by jumper JP4. As default, the setting
is 38.4k Baud. For integration with AK-SM 720/350 change the
setting to 19.2k Baud.
For more information about data communication see Danfoss
document RC8AC--
Sensor replacement
The sensor is connected to the DGS via a plug connection
enabling simple sensor exchange instead of an on-site calibration.
The internal replacement routine recognizes the exchanging
process and the exchanged sensor and re-starts the measurement
mode automatically.
The internal replacement routine also examines the sensor for
actual type of gas and actual measuring range. If the data does not
match the existing configuration, the built-in status LED indicates
an error. If everything is OK the LED will light up green.
As an alternative, the on-site calibration via the DGS Service Tool
can be performed with the integrated, user friendly calibration
routine.
See the DGS User Guide for details on operating the DGS Service
Tool.
Action Reaction
Loss of power to DGS OFF OFF X (closed)
Gas signal < warning alarm threshold OFF GREEN
Gas signal > warning alarm threshold OFF RED Slow flashing X (closed)
Gas signal > critical alarm threshold ON RED Fast flashing X (closed) X (closed)
Gas signal ≥ critical alarm threshold,
but ackn. button pressed
No alarm, no fault OFF GREEN
No fault, but maintenance due OFF GREEN Slow flashing
Sensor communication error OFF YELLOW
DGS in special mode OFF YELLOW flashing
Alarm thresholds can have the same value, therefore both the relays and the Buzzer
and Light can be triggered simultaneously.
The alarm thresholds have a hysteresis of app. 5%
* whether to include the relay status with the acknowledge function or not is user
defined.
** If the DGS has two sensors and the "Room Mode" is configured to "2 rooms",
then relay 1 ac ts as a critical relay for sensor 1 and relay 3 acts as a critical
relay for sensor 2. Both relays are SPDT NC. The Buzzer and Light operation is
independent of the "Room Mode" setting.
Buzzer
OFF
(ON after delay)
Reaction
Light
RED Fast flashing X (closed)* (open)*
Warning relay 1**
SPDT NO (Normally Open)
Critical relay 3**
SPDT NC (Normally closed)
© Danfoss | Climate Solutions | 2022.01
AN284527372096en-000301 | 3