Danfoss DGS Installation guide

Installation Guide
Danfoss Gas Sensor
080R9333
Type DGS
ENGLISH
Technician use only!
Suitably qualified operators of the unit should be aware of the regulations and standards set down by their industry/country for the operation of this unit.
These notes are only intended as a guide, and the manufacturer bears no responsibility for the installation or operation of this unit.
Failure to install and operate the unit in accordance with these instructions and with industry guidelines may cause serious injury including death, and the manufacturer will not be held responsible in this regard.
It is the installer’s responsibility to adequately ensure that the equipment is installed correctly and set up according to the environment and the application in which the products are being used.
Please observe that DGS works as a safety device securing a reaction to a detected high gas concentration. If a leakage occurs, the DGS will provide alarm functions, but it will not solve or take care of the leakage root cause itself.
AN284527372096en-000301
Regular Test:
To maintain product performance and comply with the local requirements, the DGS must be tested regularly. DGSs are provided with a test button that may be activated to validate the alarm reactions. Additionally, the sensors must be tested by either bump test or calibration. Danfoss recommends the following minimum calibration intervals: DGS-IR: 60 months DGS-SC: 12 months DGS-PE: 6 months With DGS-IR it is recommended to do an annual bump test in years without calibration. Check local regulations on calibration or testing requirements. Do not spray or pour pure refrigerant or other liquids onto the sensor head to perform a bump test. This may significantly reduce the lifetime of the sensor head or even destroy it. For propane: after exposure to a substantial gas leak, the sensor should be checked by bump test or calibration and replaced if necessary.
Location:
For all gases heavier than air, Danfoss recommends placing the sensor head app. 30cm (12") above the floor and, if possible, in the air flow. All gases measured with these DGS sensors are heavier than air: HFC grp 1, HFC grp 2, HFC grp 3, CO and Propane.
Dimensions and appearance
For further details on Test and Location please see the Danfoss Application Guide: "Gas detection in refrigeration systems".
Fig. 1
© Danfoss | Climate Solutions | 2022.01
AN284527372096en-000301 | 1
Cable gland opening
Danfoss
1
C
148H126_01-2018
Hole punching for cable gland:
1. Select the location for the safest cable entry
2. Use a sharp screwdriver and a small hammer
3. Place the screwdriver and hammer with precision while moving the screwdriver within a small area until the plastic is penetrated.
Fig. 2
Danfoss Gas Sensor DGS
5
GND
4
AO_01
not used
2
DI_01
1
S&H supply
x1
LED Yellow/Green/Red
Sensor 2
x9
open: 0-20mA closed: 0-10V
B&L
open: 19200 Baud closed: 38400 Baud
JP5
x8
x2
JP4
Continue precision punching with small movements until the round piece can be pulled out with your fingers.
WARNING: be very careful not to damage
the internal board components with the screwdriver.
Status LED / B&L:
GREEN is power on.
- flashing if maintenance needed
YELLOW is an indicator of Error.
- the sensor head is disconnected or not the expected type
- AO configured as 0 – 20 mA, but no current is
80Z790.1
running
- flashing when sensor is in special mode (e.g. when
- Supply voltage out of range
RED flashing: is an indication of alarm due to gas concentration level. The Buzzer & Light behaves identical to the status LED.
x6
x5
Ackn.-/Test button
1
2
3
1
2
3
Rel. 3
(critical)
Rel. 1
(warning)
4
3
x4
2
1
Danfoss
B­MODBUS A+
­24 V AC/D +
Ackn. / Test button / DI_01:
TEST: The button must be pressed for 8 sec.
Tool
JP3
x3
JP2 JP1
not used
- Critical and warning alarm is simulated and AO goes to
ACKN: If pressed during critical alarm, as default* the relays and Buzzer go out of alarm condition and back on after 5
minutes if the alarm situation is still active.
* the duration and whether to include the relay status with this function or not is user defined.
Sensor 1
DI_01 (terminals 1 and 2) is a dry-contact (potential-free) behaving identically to the Ackn./Test button.
Remove potential burrs and secure flat surfaces. Install the cable gland according to the enclosed guide.
changing parameters with the Service Tool)
max. (10 V/20 mA), stops on release.
Note: For what concern the power supply, please refer to chapter 3.10 Power Con- ditions and Shielding Conceptions in the User Guide (BC291049702513en-000201).
A Class II power supply is recommended
Fig. 3
2 | AN284527372096en-000301
DC supply for external Strobe&Horn
Whether the DGS is powered by 24 V DC or 24 V AC, a 24 V DC power supply (max. 50 mA) is available between terminals 1 and 5 on connector x1.
Jumpers
* JP4 open 19200 Baud JP4 closed 38400 Baud (default)
* JP5 open AO 0 – 20 mA JP5 closed AO 0 – 10 V (default)
Note: the DGS must be power cycled before any change to JP4 takes effect.
Analog Output:
If the analog output AO_01 is used (terminals 4 and 5) then you need the same ground potential for the AO and the connected device.
Note: JP1, JP2 and JP3 are not used.
© Danfoss | Climate Solutions | 2022.01
DGS installation instructions
The DGS is available with one or two sensors and B&L (Buzzer and Light) as option (see fig. 1). For sensors that can be poisoned by e.g. silicones like all semiconductor and catalytic bead sensors, it is imperative to only remove the protective cap after all silicones are dry, and then energize the device. The sensor protection cap must be removed before taking the DGS into operation
Mounting and wiring
To wall mount the DGS, unscrew the lid by releasing the four plastic screws in each corner and remove the lid. Mount the DGS base to the wall by fitting screws through the holes which the lid screws were fastened by. Complete the mounting by re-applying the lid and fastening the screws. The sensor head must always be mounted so that it points downwards. The DGS-IR sensor head is sensitive to shock – special attention should be paid to protect the sensor head from shocks during installation and operation. Observe the recommended placing of the sensor head as stated on page 1. Extra cable glands are added by following the instruction in fig. 2. The exact position of the terminals for the sensors, alarm relays, digital input and analogue output is shown in the connection diagrams (see fig. 3). The technical requirements and regulations for wiring, electrical security, as well as project specific and environmental requirements and regulations must be met.
Configuration
For convenient commissioning, the DGS is pre-configured and parameterized with factory-set defaults. See Menu Survey on page 5. Jumpers are used to change the analogue output type and the MODBUS baud rate. See fig. 3. For DGS with Buzzer & Light, alarm actions are given according to following table below.
System integration
To integrate the DGS with a Danfoss system manager or general BMS system, set the MODBUS address using the DGS Service Tool, using password "1234" when prompted. See the DGS User Guide for details on operating the DGS Service Tool. The Baud Rate is adjusted by jumper JP4. As default, the setting is 38.4k Baud. For integration with AK-SM 720/350 change the setting to 19.2k Baud. For more information about data communication see Danfoss document RC8AC--
Sensor replacement
The sensor is connected to the DGS via a plug connection enabling simple sensor exchange instead of an on-site calibration. The internal replacement routine recognizes the exchanging process and the exchanged sensor and re-starts the measurement mode automatically. The internal replacement routine also examines the sensor for actual type of gas and actual measuring range. If the data does not match the existing configuration, the built-in status LED indicates an error. If everything is OK the LED will light up green.
As an alternative, the on-site calibration via the DGS Service Tool can be performed with the integrated, user friendly calibration routine.
See the DGS User Guide for details on operating the DGS Service Tool.
Action Reaction
Loss of power to DGS OFF OFF X (closed) Gas signal < warning alarm threshold OFF GREEN Gas signal > warning alarm threshold OFF RED Slow flashing X (closed) Gas signal > critical alarm threshold ON RED Fast flashing X (closed) X (closed) Gas signal ≥ critical alarm threshold, but ackn. button pressed No alarm, no fault OFF GREEN No fault, but maintenance due OFF GREEN Slow flashing Sensor communication error OFF YELLOW DGS in special mode OFF YELLOW flashing
Alarm thresholds can have the same value, therefore both the relays and the Buzzer and Light can be triggered simultaneously. The alarm thresholds have a hysteresis of app. 5% * whether to include the relay status with the acknowledge function or not is user
defined.
** If the DGS has two sensors and the "Room Mode" is configured to "2 rooms",
then relay 1 ac ts as a critical relay for sensor 1 and relay 3 acts as a critical relay for sensor 2. Both relays are SPDT NC. The Buzzer and Light operation is independent of the "Room Mode" setting.
Buzzer
OFF (ON after delay)
Reaction Light
RED Fast flashing X (closed)* (open)*
Warning relay 1** SPDT NO (Normally Open)
Critical relay 3** SPDT NC (Normally closed)
© Danfoss | Climate Solutions | 2022.01
AN284527372096en-000301 | 3
DGS installation test
As DGS is a digital device with self-monitoring, all internal errors are visible via the LED and MODBUS alarm messages. All other error sources often have their origins in other parts of the installation. For fast and comfortable installation test we recommend proceeding as follows.
Optical Check
Right cable type used. Correct mounting height according to definition in the section about mounting. LED status – see DGS trouble shooting.
Functional test (for initial operation and maintenance)
Functional test is done by pressing the test button for more than 8 seconds and observing that all connected outputs (Buzzer, LED, Relay connected devices) are working properly. After deactivation all outputs must automatically return to their initial position.
Zero-point test (if prescribed by local regulations)
Zero-point test with fresh outdoor air. A potential zero offset can be read out by use of the Service Tool.
Trip test with reference gas (if prescribed by local regulations)
The sensor is gassed with reference gas (for this you need a gas bottle with pressure regulator and a calibration adapter). In doing so, the set alarm thresholds are exceeded, and all output functions are activated. It is necessary to check if the connected output functions are working correctly (e.g. the horn sounds, the fan switches on, devices shut down). By pressing the push-button on the horn, the horn acknowledgement must be checked. After removal of the reference gas, all outputs must automatically return to their initial position. Other than the trip testing, it is also possible to perform a functional test by means of calibration. For further information, please refer to the User Guide.
Comparing sensor gas type with DGS specification
The replacement sensor specification must match the DGS specification. The DGS software automatically reads the specification of the connected sensor and compares with the DGS specification. This feature increases the user and operating security. New sensors are always delivered factory-calibrated by Danfoss. This is documented by the calibration label indicating date and calibration gas. A re-calibration is not necessary during commissioning if the device is still in its original packaging (including air-tight protection by the red protective cap) and if the calibration certificate has not expired.
4 | AN284527372096en-000301
© Danfoss | Climate Solutions | 2022.01
Menu Survey
Function Min. Max. Factory Unit AKM name
Gas level
Sensor 1 Actual gas level in % of range 0.0 100.0 - % Gas level %
Sensor 1 Actual gas level in ppm 0 FS1 - ppm Gas level ppm
Sensor 2 Actual gas level in % of range 0.0 100.0 - % 2: Gas level %
Sensor 2 Actual gas level in ppm 0 FS1 - ppm 2: Gas level ppm
Alarms Alarm settings
Indication of critical alarm (critical alarm of Gas1 or Gas2 active) 0: No active alarm(s) 1: Alarm(s) active
Common indication of both critical and warning alarm as well as internal and maintenance alarms 0: No active alarm(s), warning(s) or errors 1: Alarm(s) or warning(s)) active
Gas 1 Critical limit in %. Critical limit in % (0-100)
Gas 1 Critical limit in ppm Critical limit in ppm; 0: Warning Signal deactivated
Gas 1 Warning limit in % (0-100) 0 100.0 HFC: 25
Gas 1 Warning limit ppm 0: Warning Signal deactivated 0.0 FS1 HFC: 500
High (critical and warning) alarm delay in seconds, if set to 0: no delay 0 600 0 sec. Alarm delay s
When set to 1, the Buzzer is reset (and the relays if defined: Relay rest enable) to no alarm indication. When the alarm is reset or the time-out duration is exceeded, the value is reset to 0. Note: The alarm condition is not reset-only the output indication is reset. 0: Alarm outputs not reset 1: Alarm outputs reset – Buzzer muted and relays reset if configured
Duration of alarm reset before automatic re-enable of alarm outputs. A setting of 0 disables the ability to reset alarm.
Relay reset enables: Relay reset with alarm acknowledge function 1= (default) Relays wil be reset if the alarm acknowledge function is activated 0: Relays remain active until the alarm condition clears
Gas 2 Critical limit in %. Critical limit in % (0-100)
Gas 2 Critical limit in ppm Critical limit in ppm; 0: Warning Signal deactivated
Gas 2. Warning limit in % (0-100) 0 100.0 CO2: 25 % 2: Warn. limit %
0 1 - - GD alarm
0 1 - - Common errors
0.0 100.0 HFC: 25 CO2: 25 R290: 16
0 FS1 HFC: 500
CO2: 5000 R290: 800
CO2: 25 R290: 16
CO2: 5000 R290: 800
0 1 0 - Reset alarm
0 9999 300 sec. Reset alarm time
0 1 1 - Relay rst enable
0.0 100.0 CO2: 25 % 2: Crit. limit %
0 FS1 CO2: 5000 ppm 2: Crit. limit ppm
% Crit. limit %
ppm Crit. limit ppm
% Warn. limit %
ppm Warn. limit ppm
SW 1.1x
Gas 2. Warning limit ppm 0: Warning Signal deactivated 0.0 FS1 CO2: 5000 ppm 2: Warn. limit ppm
High (critical and warning) alarm delay in seconds, if set to 0: no delay 0 600 0 sec. 2: Alarm delay s
Configuration of relays for one or two rooms’ application mode. 1: One room with two sensors sharing the same warning relay and critical relay 2: Two rooms with one sensor in each, and each sensor having a critical alarm relay. In this mode, warning alarms activate as normal on the LED indicator, hand-held Service Tool and on MODBUS.
Service
Status of the sensor's warm-up period: 0: Ready 1: Warming up one or more sensors
1
 The max. alarm limit for CO2 is 16000 ppm / 80% of full scale. All other values equal the full scale range of the specific product.
© Danfoss | Climate Solutions | 2022.01
1 2 1 - 1:1 room (default)
2:2 rooms
0 1 - - DGS Warm-up
AN284527372096en-000301 | 5
Readout the attached gas sensor type.
1 5 N - Sensor type
1: HFC grp 1
R1234ze, R454C, R1234yf R1234yf, R454A, R455A, R452A R454B, R513A
2: HFC grp 2
R407F, R416A, R417A R407A, R422A, R427A R449A, R437A, R134A R438A, R422D
3: HFC grp 3
R448A, R125 R404A, R32 R507A, R434A R410A, R452B R407C, R143b
2
4: CO 5: Propane (R290)
Full scale range 0 32000 HFC: 2000
ppm Full scale ppm CO2: 20000 R290: 5000
Gas 1 Days until next calibration 0 32000 HFC: 365
days Days till calib CO2: 1825 R290: 182
Gas 1 Estimates how many days remaining for sensor 1 0 32000 - days Rem.life time
Status of the Critical Alarm Relay
0 1 - - Critical Relay 1: ON = no alarm signal, coil under power - normal 0: OFF = alarm signal, coil depowered, alarm situation
Status of the Warning Relay:
0 1 - - Warning Relay 0: OFF= inactive, no warning active 1: ON = active warning, coil under power
Status of the Buzzer:
0 1 - - Buzzer 0: inactive 1: active
Gas 2 Days until next calibration 0 32000 HFC: 365
days 2: Days til calib CO2: 1825 R290: 182
Gas 2 Estimates how many days remaining for sensor 2 0 32000 - days 2: Rem.life time
Activates a mode which simulates an alarm. Buzzer, LED and relays all
0 1 0 - Test Mode activate. 1:-> Test function - no alarm generation possible now Automatically falls back to Off after 15 min. 0: back to normal mode
Analogue output max. scaling 0: zero to full scale (e.g sensor 0-2000 ppm) 0-2000 ppm will give 0-10 V)
0 1 HFC: 1
CO: 1 R290: 0
- AOmax = half FS
1: zero to half scale (e.g sensor 0-2000 ppm) 0-1000 ppm will give 0-10 V)
Analogue output min. value
0 1 0 - AOmin = 2V/4 mA 0: select 0-10 V or 0-20 mA output signal 1: select 2-10 V or 4-20 mA output signal
Alarms
Critical Limit alarm
0 1 - - Critical limit 0: OK 1: Alarm. Gas limit exceeded and delay expired
0: OK
0 1 - - Out of range 1: Fault. Out of range under test – over range or under range
0: OK
0 1 - - Wrong SensorType 1: Fault. Sensor and head failures
0: OK
0 1 - - Sensor removed 1: Fault. Sensor out or removed, or wrong sensor connected
0: OK
0 1 - - Calibrate sensor 1: Warning. Due for calibration
0: OK
0 1 - - Warning limit 1: Warning. Gas level above warning level and delay expired
6 | AN284527372096en-000301
© Danfoss | Climate Solutions | 2022.01
Indication if the normal alarm function is inhibited or in normal
oss
80Z875
operation 0: Normal operation, i.e. alarms are created and cleared 1: Alarms inhibited, i.e. alarm status is not updated, e.g. due to DGS in test mode
Critical Limit alarm 0: OK 1: Alarm. Gas limit exceeded and delay expired
0: OK 1: Fault. Out of range under test – over range or under range
0: OK 1: Fault. Sensor and Head failures
0: OK 1: Fault. Sensor out or removed, or wrong sensor connected
0: OK. Sensor not due for calibration 1: Warning. Due for calibration
0: OK 1: Warning. Gas level above warning level and delay expired
0 1 - - Alarm inhibited
0 1 - - 2: Criti. limit
0 1 - - 2: Out of range
0 1 - - 2: Wrong SensType
0 1 - - 2: Sens.removed
0 1 - - 2: Calibrate sens
0 1 - - 2: Warning limit
DGS troubleshooting
Symptom: Possible cause(s):
LED off • Check power supply. Check wiring.
• DGS MODBUS was possibly damaged in transit. Check by installing another DGS to confirm the fault.
Green flashing • The sensor calibration interval has been exceeded or the sensor has reached the end of life. Carry
out calibration routine or replace with a new factory calibrated sensor.
Yellow • AO configured but not connected (only 0 – 20 mA output). Check wiring.
• Sensor type does not match DGS specification. Check gas type and measuring range.
• Sensor may be disconnected from printed circuit board. Check to see if the sensor is properly connected.
• The sensor has been damaged and needs to be exchanged. Order replacement sensor from Danfoss.
• Supply voltage out of range. Check power supply.
Yellow flashing • The DGS is set to service mode from the hand-held Service Tool. Change setting or await time-out
within 15 minutes.
Alarms in the absence of a leak • If you experience alarms in the absence of a leak, try setting an alarm delay.
• Perform a bump test to ensure proper operation.
The zero-measurement drifts The DGS-SC sensor technology is sensitive to the environment (temperature, moist, cleaning agents,
gases from trucks, etc). All ppm measurements below 75 ppm should be disregarded, i.e. no zero­adjustment made.
Power Conditions and Shielding Conceptions
Standalone DGS without Modbus network communication
DGS with Modbus network communication in combination with other devices powered by the same power supply
© Danfoss | Climate Solutions | 2022.01
Shield/screen is not required for standalone DGS with no connection to a RS-485 communication line. However, it can be done as described in the next paragraph (Fig. 4).
It is strongly recommended to use direct current power supply when:
• more than 5 DGS units are powered by the same power supply
• the bus cable length is longer than 50 m for those powered units
It is moreover recommended to use class 2 power supply (see AK-PS 075)
Make sure to not interrupt the shield when connecting A and B to the DGS (see Fig. 4).
A+B
Fig. 4: Loop trough
Danf
AN284527372096en-000301 | 7
Shield
Busmaster
Busmaster
Danfoss Modbus
device
Shld
A
B
DGS 1 #adr 10 A B Gnd
+
DGS 2 #adr 11 A B Gnd
+
1 KΩ
DGS n #adr xx A B Gnd
+
AK-PS 075 power supply
+
Input 230 V
L
230 V
N
Fig. 5: Wiring diagram for system with one power supply
Ground potential difference between nodes of the RS485 network might affect the communication. It is advised to connect a 1 KΩ 5% ¼ W resistor between the shield and the ground (X4.2) of any unit o r group of units connected to the same power supply (Fig. 5). Please refer to Literature No. AP363940176099.
Danfoss
80Z876
DGS with Modbus network communication in combination with other devices powered by more than one power supply
It is strongly recommended to use direct current power supply when:
• more than 5 DGS units are powered by the same power supply
• the bus cable length is longer than 50 m for those powered units It is moreover recommended to use class 2 power supply (see AK-PS 075)
Make sure to not interrupt the shield when connecting A and B to the DGS (see Fig. 4).
1 KΩ
1 KΩ
Shield
DGS 1 #adr n1 A B Gnd
Shield
DGS 1 #adr n11 A B Gnd
AK-PS 075 power supply
+
+
+
DGS 2 #adr n2 A B Gnd
DGS 2 #adr n12 A B Gnd
+
+
DGS n #adr nx A B Gnd
DGS n #adr ny A B Gnd
+
AK-PS 075 power supply
+
+
L
230 V
N
L
230 V
N
L
230 V
N
Danfoss Modbus
device AK-SM
A
B
Shld
Busslave
L
230 V
N
Danfoss Modbus
device AK-CC
A
B
Shld
Fig. 6: Wiring diagram for system with multiple power supplies
Ground potential difference between nodes of the RS485 network might affect the communication. It is advised to connect a 1 KΩ 5% ¼ W resistor between the shield and the ground (X4.2) of any unit or group of units connected to the same power supply (Fig. 6). Please refer to Literature No. AP363940176099.
Danfoss
80Z878
© Danfoss | Climate Solutions | 2022.01
Power supply and voltage alarm
The DGS device goes into voltage alarm when voltage exceeds certain limits. The lower limit is 16 V. The upper limit is 28 V, if DGS software version is lower than 1.2 or 33.3 V in all other cases. When in the DGS the voltage alarm is active, in the System Manager the “Alarm inhibited” is raised.
AN284527372096en-000301 | 8
Loading...