Data Sheet
Her
metic filter drier
Type DFL
For unio
w liquid line
ELIMINATOR® CB driers has compact bead.
iers contain 80% molecular sieve with
DFL dr
20% activated Alumina.
ELIMINATOR® CB DFL driers are designed for
applications requiring high ltration and
moisture capacity.
Available with solder copper, solder steel and
are connections.
For other connections please contact your
Danfoss Sales Representative.
AI374042233537en-000201

Hermetic lt
er drier, type DFL
Features
he compact bead type DFL
T
• 80% Molecular Sieve with 20% activated alumina
• Recommended for use with Applicable to R22, R134a, R404A, R32,R410A, R407C, R23, R600, R600a,R1234yf,
R1234z
The Shell
• PED approved for PS 45 bar
• Available with Solder Copper, Solder Steel and ar
• Corrosion resistant powder-painted nish
• Allows installation with any orientation provided the arrow is in the ow direction
• Available in sizes 3 – 30 cubic inches
The Filter
• Provides 20 microns ltr
e, R407f, R290, R452A,R444B, R449A, R448A and R450A refrigerants
e connections
ation with minimal pressure drop
© Danfoss | Climate Solutions | 2021.11 AI374042233537en-00020
1 | 2

Danfoss
23Z9035
EVR
SGP
AKS
ERC
TCAE
GBC GBCDFL
Hermetic lt
er drier, type DFL
Applications
Intro-diagram
ELIMINA
TOR® CB Hermetic lter driers protect refrigeration and air-conditioning systems from moisture, acids, and
solid particles.
With these contaminants eliminated, systems are safer from harmful chemical reactions and from abrasive
impurities.
Figure 1: Application
© Danfoss | Climate Solutions | 2021.11 AI374042233537en-00020
1 | 3

Filter drier volume (shell volume)[l]
Filter drier volume (net volume)[l]
Drying capacity of refrigerant(Kg)
Hermetic lt
er drier, type DFL
Product specication
Technical data
Table 1: Technical data
Table 2: Volume
Table 3: Acid capacity
(1)
(1)
Adsorption capacity of oleic acid at 0.05 TAN (Total Acid Number).
Adsorption capacity of oleic acid at 0.05 TAN (Total Acid Number).
emperature range:
Temperature range:
T
-30 – 70 °C
-30 – 70 °C
Maximum working pressure:
Maximum working pressure:
PS 45 bar
PS 45 bar
Capacity
Table 4: Capacity table for moisture and o
w
© Danfoss | Climate Solutions | 2021.11 AI374042233537en-00020
1 | 4

Drying capacity of refrigerant(Kg)
80% Molecular Sieve / 20% activated alumina
Connection (lt
er connection in
1
⁄8 of an inch incre-
ments)
Hermetic lt
er drier, type DFL
Given in accordance with ARI 710-2004 for:
e = -15 °C
–t
–tc = 30 °C
–Δp = 0.07 bar
Conversions
Drops of water =
See ARI standard 710-86 for recommended initial and nal PP
[1 kg of refrigerant× (Initial PPM of water−
50
Identication
Table 5: Iden
tication
Final PPM of water)]
M values for dierent refrigerants.
Example for type codes
© Danfoss | Climate Solutions | 2021.11 AI374042233537en-00020
1 | 5