Danfoss DEVIreg Multi Data sheet

Data Sheet
DEVIreg™ Multi
DEVIreg™ Multi is 7 channel electronic programmable controller to be installed on DIN rail. Every channel can be individually set up with three control modes – with temperature sensor, time proportional power regulation without sensor and manually on/off with time limitation. Сhannels inputs can be selected via software between 8 types of temperature sensors including NTC 15 kOhm at 25°C. Modbus RS485 opto-insulated serial interface gives possibility for BMS control.
DEVIreg™ Multi has some special functions which can be programmed for every channel: relay status - opened or closed correspondently to ‘Heating On’ mode, channel activation or deactivation, sensor failure alarm, min and max temperatures alarm, cable failure monitoring, relay test, channel on/off, relay cycles calculator, etc.
Benefits:
• 7 independent channels
• 3 control modes:
– with temperature sensor – time proportional regulation – manually on/off
• Heating or cooling control
• Compatible with 8 sensors types
• Accurate temperature control
• Alarm functions
• Cable failure monitoring
• Multilanguage menu
• Graphic LCD display
• BMS control
• Dimensions 8 DIN modules
Standard compliance:
• Low Voltage Directive 2014/35/EU
• EMC Directive 2014/30/EU
• EN/IEC 60730-1 + EN/IEC 60730-2-9
Certificates:
Type
Nominal voltage 110/230 V AC, 50–60 Hz Power consumption, max. 20 V A Relay resistive (inductive, cos(phi) = 0,6) load:
Total current load limit C1-NO1, C2-NO2 C5-NO5, C6-NO6 C3-NO3-NC3, C4-NO4-NC4 C7-NO7-NC7, C8-NO8-NC8
Sensor inputs Analog inputs AI1-AI8 Sensing unit Temperature sensors separately selectable via
Sensor failure monitoring Disconnected or short-circuited sensor Digital inputs DI1-DI8, voltage free contacts, on/off inputs Connection specification Grouped screws plug-in connectors, pitch 5 mm Cable specification for connectors terminals Section cable 0,2-2,5 mm² Battery back-up time, min. 48 hours Ball pressure test 125 °C according to IEC 60730-1 Pollution degree 2 (domestic use) Controller type 1 C Operating temperatures and conditions CE: -20...+60 °C / UL: 0...55 °C,
Storage temperature and conditions -30...+85 °C, 90% RH non-condensing IP class IP40 only on the front cover Protection class Class II ­Immunity against voltage surges Designed for Over Voltage Category II Dimensions (H/W/D), DIN dimension : 110(122) х 138 х 70 mm, 8 DIN modules Mounting method DIN rail, complying with EN 60715 Weight, net 511 g Menu languages: 2.0 en, bg, cs, da, de, es, et, fi, fr, hr, hu, lt, no, pl,
Base controller Danfoss MCX08M2, item no. 080G0307 Software class A
Value
32 A
10 (3,5) A (100 000 cycles)
6 (4) A (100 000 cycles) 6 (4) A (100 000 cycles) 6 (4) A (100 000 cycles)
software at analog inputs AI1-AI7 between:
NTC15k (15 kOhm @ 25 °C) NTC10k (10 kOhm @ 25 °C)
NTC5k (5 kOhm @ 25 °C) NTC2k (2 kOhm @ 25 °C)
NTC100 (100 kOhm @ 25 °C)
NTC16k (16,7 kOhm @ 100 °C)
PT1000 (1000 Ohm @ 0 °C)
Ni100 (100 Ohm @ 0 °C)
90% RH non-condensing
ro, ru, sk, sl, sv, tr, uk
Types: set DEVIreg™ Multi + 1 sensor NTC 15kOhm
Item no. Product name Type EAN no.
140F1139 DEVIreg™ Multi Programmable controller with Wire sensor NTC 15 kOhm at 25 °C, 3 m 5703466248560
Produced by Danfoss © AI33434718 4693e n-010106
Accessories
Item no. Product name Description EAN no.
140F1095 Room sensor, 426-frame 85 x 85 x 30 mm, NTC 15 kOhm at 25 °C, IP 20 5703466209684
140F1096 Outdoor sensor IP44 80 х 50 х 35 mm, NTC 15 kOhm at 25 °C, IP 44 5703466209691
140F1091
140F1098
19121445
Sensor 3 m, 15 kOhm, Santropene
Temperature Sensor 10 m NTC 15k
Santropene
Sensor cable 40 m, 15 kOhm, Santropene
140F1092 Outdoor sensor 2,5 m, 15 kOhm, PVC
140F1097
084N3209
084N3210
084N1221
084Z6039
080G0180
Silicon sensor for DEVIreg™ 330
(60-160°C), NTC 16,1 kOhm @ 100°C
Sensor EKS 221 NTC 10K 8,5m cable
Sensor EKS 221 NTС 10K 3,5m cable
Sensor EKS 211 NTC 5000 Wire sensor, 3,5 m cable, NTC 5 kOhm at 25 °C, Ø8x30 mm, IP 67
Sensor MBT 153-2200-0350 Wire sensor, 3,5 m cable, PT 1000 kOhm at 0 °C, Ø5,7x40 mm, IP 67
ACCCNX Connectors MCX-08M Screws plug-in connectors set for MCX-08M
Wire sensor, 2x0,75 mm², NTC 15 kOhm at 25 °C, Ø5x18 mm,
black Santropene (TPV), IP 67
Wire sensor, 2x0,75 mm², NTC 15 kOhm at 25 °C, Ø8 mm,
white PVC outer sheath, IP 67
Wire silicon sensor, 2,5 m, 2x0,75 mm²,
NTC 16,1 kOhm at 100 °C, IP 65
Wire sensor, NTC 10 kOhm at 25 °C, Ø6x15 mm, IP 67
5703466209301
5703466210734
5703466115015
5703466209318
5703466209707
5702428171960
5702428171960
5702428099431
5702423151431
5702423284696
Connection scheme
Power
110/230 V AC
AI 1
COM
AI 2
COM
COM
AI 3-4
Channel #1 Channel #2 Channel #3 Channel #4 Channel #5 Channel #6 Channel #7 Alarm RS485
DI 1
C 1
NO 1
DI 2
C 2
NO 2
DI 3
NC 3
COM
DI 1-4
CMR #1 CMR #2 CMR #3 CMR #4 CMR #5 CMR #6 CMR #7
S - temperature Sensor; CMR - Current Monitoring Relay
<I <I <I <I <I <I <I
C 3
General MCX08M2 controller connection scheme
AI 3
NO 3
RS485
(Modbus)
D -
AI 4
DI 4
NC 4
C 4
NO 4
DI 5
AI 5
COM
AI 5-8
C 5
NO 5
DI 6
AI 6
C 6
NO 6
DI 7
NC 7
AI 7
C 7
NO 7
NC 8
DI 8
C 8
NO 8
Dev ice
OFF ON
D +
GND
COM
DI 5-8
To the AI
PWM-PPM
0/10 Vdc
optoinsulated
Not
used
0/10 V
To the AI
(100 mA max)
(120 mA max)
NTC, 0/1 V, 0/5 V,
0/10 V, PT1000
MCX08M2 - TOP
Produced by Danfoss © AI33434718 4693e n-010106
Danfoss
80G8036.04
MCX08M2 - BOTTOM
Loading...