Danfoss DEVIreg Multi Installation guide

DEVIreg™ Multi
EN
Installation and User Guide
DEVIreg™ Multi
7 channel DIN-rail programmable controller
Intelligent solutions with lasting effect
Visit devi.com
Table of content
1 Introduction .......................................................................4
2 Safety Instructions .................................................................5
3 Mounting Instructions .............................................................5
4 User Manual .......................................................................6
4.1 Control modes overview ....................................................6
4.2 Terms and abbreviations ....................................................7
4.3 General use .............................................................. 10
4.4 Control modes, special functions, special statuses and settings .............15
4.4.1 Active and Not Active Channel status ..................................... 15
4.4.2 Relay status RO/RC – special setting for status ‘Heating On’ ................. 17
4.4.3 1S or Single Sensor mode and Sensor Type set up .........................17
4.4.3.1 1S mode ................................................................. 17
4.4.3.2 Sensor Type set up .......................................................20
4.4.4 PR or Power Regulation mode ............................................ 21
4.4.5 MOn and MOf – Manually heating On and Manually heating Of mode ...... 23
4.4.6 CableOK? – special channel function ...................................... 24
4.4.7 Channel ON/OFF – special function ....................................... 26
4.4.8 Device ON/OFF – special function and switch .............................. 27
4.4.9 Relay Test 5/30– special function .......................................... 29
4.4.10 Alarms, alarm data and alarm relay ........................................ 29
4.4.11 Relay Counters view and reset ............................................ 31
4.4.12 Language setting ......................................................... 32
4.4.13 Date and Time settings ................................................... 32
4.4.14 BMS settings ............................................................. 32
5 Connection diagram ............................................................. 33
6 Technical Specifications .......................................................... 34
6.1 Technical data ............................................................ 34
6.2 Dimensions .............................................................. 35
7 Disposal Instruction .............................................................. 36
Appendix A. BMS and RS-485 interface .............................................37
A1. Communication settings ......................................................37
A2. RS-485 specifications .......................................................... 37
A3. Modbus parameters and variables ............................................. 37
Warranty ............................................................................46
FEC | Produced by Danfoss © 3
1 Introduction
DEVIreg™ Multi is 7 channel electronic programmable controller to be installed on
DIN-rail and supposed to be used for controlling electrical heating and cooling systems. Every channel can be individually set up with three control modes –temperature sensor, time proportional power regulation without sensor and manually on/off with time period.
Universal analog channels’ inputs can be selected via software between 8 types of temperature sensors including NTC 15 kOhm at 25 °C. Controller has graphic LCD display, Modbus RS-485 opto-insulated serial interface and 110/230 V AC power supply.
DEVIreg™ Multi has 8 control relays – 2 sets of max. 10 A and 6 sets of max. 6 A; and among them 4 sets NO and 4 sets NC/NO contacts. Relay control functions can be set up for heating or cooling systems. Additionally, relay contacts are not connected to a voltage source inside the controller, and can be used for control systems with any voltage up to 250 V AC.
In addition to 3 control modes, DEVIreg™ Multi has some special functions which can be programmed for every channel: relay status – opened or closed for ‘Heating On’ mode, channel activation or deactivation, sensor failure alarm, min. and max. temperature alarms, cable failure monitoring, relay test, channel on/off, relay cycles’ calculator, etc.
Hardware of DEVIreg™ Multi is based on the Danfoss controller type MCX08M2, art. no. 080G0307, but is customized with special software.
The product complies with the EN/IEC Standard “Automatic electrical controls for house­hold and similar use”:
EN/IEC 60730-1 (general)
EN/IEC 60730-2-9 (thermostat)
More information on this product can also be found at: devi.com
NB: All relevant abbreviations and words in bold are terms used in DEVIreg™ Multi screen texts with exact the same spelling.
FEC | Produced by Danfoss ©4
2 Safety Instructions
Make sure the mains supply to the controller is turned off before installation.
Please also note the following:
The installation of the controller must be done by an authorized and qualified installer according to local regulations.
The controller must be connected to a power supply via an all-pole disconnection switch.
Always connect the controller to continuous power supply.
Do not expose the controller to moisture, water, dust and excessive heat.
IMPORTANT: When the controller is used for controlling a floor heating element/cable in connection with a wooden floor or similar material, always use a floor sensor and never set the maximum floor temperature to more than 35°C.
Note: Product is designed for Over Voltage Category II. When used in fixed installation, installation must be equipped with transient protection.
3 Mounting Instructions
Please observe the following placement guidelines:
Install the thermostat in an electric cabinet with DIN rail attachment or a separate DIN attachment according to local regulation on IP classes.
Do not place the thermostat in a way that it will be exposed to direct sunlight.
Follow the steps below to mount the thermostat:
1. Click the thermostat on the DIN rail attachment.
2. Connect the thermostat according to the connection diagram and chosen system mode(-s)
3. The screen of the heating cable must be connected to the earth conductor of the power supply cable by using a separate connector.
4. Turn on the power supply.
Note: Always install the floor sensor in a conduit in the floor construction or similar. The bending radius of the conduit must be min. 50 mm.
FEC | Produced by Danfoss © 5
4 User Manual
4.1 Control modes overview
The DEVIreg™ Multi is 7 channels controller and every channel can be individually set up with one from three control modes:
1. Single sensor control with temperature sensor - ‘1 Sensor’ mode or ‘1S’.
2. Time proportional power regulation – ‘Power Regulation’ mode or ‘PR’.
3. Manually On/Off control with time period – ‘MOn’/’MOf’ mode.
1S mode or Single sensor control
1S mode is control with temperature sensor and adjustable hysteresis. 1S control typically
can be used for Pipe heating, Ground Ice & Snow melting, Cold rooms’ protection, Comfort Floor heating, Total heating and other applications with temperature control. This control mode is similar to well-known DEVIreg™ 316 thermostat.
Universal analog channel’s inputs (AI) can be selected via software between 8 types of temperature sensors including NTC 15 kOhm at 25°C.
This mode can be set up with special function to control Alarm min. and max. temperatures. Additionally, it can be set up with so called Cable OK? function which uses channel digital input (DI) with connected Current Monitoring Relay (CMR) to control availability of elec­tricity passing through a heating cable or similar.
PR mode or Power Regulation control
PR mode is time proportional power regulation with a simple duty cycle generator. Time
for status ‘Heating On’ during the chosen mode cycle can be set up by installer. PR control typically can be used where one wants to dissipate a subjective amount of power.
This mode is also not connected to a temperature sensor and is therefore very suitable for installation where it is impossible to install temperature sensor. This control mode is similar to well-known DEVIreg™ 527 controller.
This mode can be set up with so called Cable OK? function which uses channel digital input (DI) with connected Current Monitoring Relay (CMR) to control power consumption or similar.
FEC | Produced by Danfoss ©6
Manually On/Of mode
Manually On/Of mode (on the screen – MOn or MOf) is control with setting time period during which relay status ‘Heating On’ or ‘Heating Of’ will operate.
NB: This mode can be used only on the base of 1S or PR modes and upon its completion controller returns to the same mode from which it started.
4.2 Terms and abbreviations
NB: Terms and abbreviations in the bold are special DEVIreg™ Multi words used for screen texts, menu lines, etc.
Special terms and abbreviations
Term in English
#1, #2, …, #7 Channel number from 1 to 7.
1S Single Sensor or ‘1 Sensor’ control mode.
PR Power Regulation control mode.
MOn
MOf
Heating On
Heating Of
On
Of
RO RC
The mode with temperature sensor and adjustable hysteresis.
The time proportional power regulation with a simple duty cycle generator with time set when heating is turned on during the chosen period/cycle time.
Manually On/Of control mode. The mode with relay setting either for state ‘Heating On’ or ‘Heating Of’ and time setting during which this mode will be performed.
The state when control algorithm decides to start heating or to stop heating.
Special abbreviation used for state ‘Heating On’ or ‘Heating Of’. It’s a logical state not corresponding to relay status with closed or trol algorithm activates heating, it appears be either with an opened circuit state or with a closed-circuit condition which are determined by the setting Relay status RO/RC – Relay Opened (RO) or Relay Closed (RC).
NB: These abbreviations – On or Of – should be used with 1st capital and 2nd small letters, and contain 2 letters only.
Relay status RO/RC for state Heating On – Relay Opened (RO) or Relay Closed (RC). For the heating mode on, the corresponding state of the relay contacts can be selected – open or closed. This relay status allows to implement both heating and cooling control, as well as electric and water heating systems.
Explanation
opened contacts. When con-
on the screen as On. For this case relay contacts can
FEC | Produced by Danfoss © 7
Term in English
ON
OFF
# The symbol “Hash sign” indicates when Channel is OFF or Device is OFF. This status can be
## These 2 hash symbols appear when Device is OFF. This status can be set up by ‘mechanical’
En
Dis
Active Possible status for every Channel. When Active = Yes – Channel’s algorithm works according
Yes No
CableOK?
! This symbol appears in Alarm conditions with some Channel(-s).
!!! These 3 symbols appear in Alarm conditions with Device by any reason.
Main Screen The Main Screen displays the main data of controller and the status of all Channels at the
AI1-AI8 Analog inputs, used for connection of temperature sensors.
DI1-DI8 Digital inputs, voltage free contacts. DI1-DI7 are used for connection of special devices for
DO1-DO8 Digital outputs connected to relay contacts. DO1-DO7 are used for loads, DO8 – for Alarm.
Used for setting Channels or Device with status ON or OFF. When Channel or Device is set up with OFF – it means that the appropriate control algo­rithm(-s) is stopped. It is similar to power supply off, but device/channels are still powered, and display shows some data and settings. When the Channel is OFF – symbol hash – ‘#” appears in the Channel’s line on the Main Screen. When the Device is OFF – one or two symbols hash – ‘#’ or ‘##’, appear on the top-left position of a Main Screen.
NB: The abbreviations ON and OFF should to be used with capital letters only. It emphasizes the difference in relation to abbreviations On and Of used for Heating status.
set up via Main Menu.
switch on input DI8 when contacts are closed.
En means Enabled and Dis – Disabled, are used to allow of forbid some special functions or statuses.
to the settings and data is displayed on the screen(-s). When it’s not Active or Active = No – Channel does not work at all and “empty” line appears on the Main Screen.
Status of some settings. For example, Channel can be Active or not Active – it means Ye s or No respectively for settings Activate #1-7.
Special abbreviation used for function checking the proper functioning of the heating cable by con­dition on digital inputs DI1-DI7. For this purpose, additional device can be recommended – Current Monitoring Relay (CMR) or so on. For OK and not OK are used terms Yes and No respectively.
same time. This screen is constantly visible on the display during everyday work.
function Cable OK?, DI8 is used for connection of ‘mechanical’ switcher for Device ON/OFF function.
Explanation
FEC | Produced by Danfoss ©8
Common terms and abbreviations
Term Explanation
Sensor In this content, always a temperature sensor – NTC, PT1000, etc..
NTC NTC temperature sensor. NTC stands for “Negative Temperature Coefficient”. NTC sensor is
PT1000
RTC Real Time Clock
BMS A building management system (BMS), is a computer-based control system installed in build-
RS-485 RS-485 or RS485, also known as TIA-485(-A) or EIA-485, is a standard defining the electrical
RCD Residual-current device
CMR Current Monitoring Relay
NO
NC Normally Close relay. Has an initial closed-circuit state when no current is applied to its inter-
MCX Danfoss Programmable Controller. DEVIreg™ Multi is based on MCX08M2 controller
resistor with a negative temperature coefficient, which means that the resistance decreases with increasing temperature.
Temperature sensor. PT refers to that the sensor is made from Platinum (Pt). 1000 refers to that at 0°C sensor has a resistance of 1000 Ohms (Ω). Sensor has Positive Temperature Coefficient (PTC).
ings that controls and monitors the building’s mechanical and electrical equipment such as ventilation, lighting, power systems, fire systems, and security systems.
characteristics of drivers and receivers for use in serial communications systems.
Normally Open relay. Has an initial opened circuit state when no current is applied to its coil so basically the internal switch disconnects the power to the load in the inactive state.
nal coil therefore the internal switch connects the power to the load. When voltage is applied to the coil of the NC relay the internal switch goes to the open position and disconnects the power from the load.
FEC | Produced by Danfoss © 9
4.3 General use
The DEVIreg™ Multi is operated via 4 buttons out of 6. Display with an alpha numeric style with information in various languages.
Buttons
The functions of the 4 operated buttons are:
Up, Down
Escape Escape to upper level of menu / show Alarm screen
Enter Confirm / select / go to the Main menu
Besides the normal function of the buttons, some special combinations are important to the user:
For quick changing of any values, e.g. temperature – hold button Up or Down.
Return to Main Screen – press several times Escape or do not press any button during some minutes.
Display
The DEVIreg™ Multi can simultaneously control up to 7 different systems with 3 different modes. These 7 systems are referred as Channel #1, Channel #2, … and Channel #7.
The DEVIreg™ Multi provides the user with an opportunity to view the current status of the all systems / channals. This status can be shown in different ways.
Next menu entry / next line / next setting parameter / shows additional screens
control
FEC | Produced by Danfoss ©10
Main Screen view (default)
The Main Screen is the main window appearing when the controller is powered. This screen displays the main data of controller and the status of all Channels at the same time. The main controller’s data is visible on the 1st display line and the Channel #1 – #7 data are visible on the lines from 2 to 8.
This view gives the user an example of all Channels on one screen.
Main sub-screens view
These screens give to user quick and more detailed information about settings and status of each Channel.
Just press button Down on the Main Screen of controller and Channel data #1 will appear, press Down again – and you’ll see Channel data #2, and so on.
To exit from Main sub-screens view and return to the Main Screen – press Escape 2 times.
FEC | Produced by Danfoss © 11
Relay On cycles view
By pressing button Up in the Main Screen of controller, it gives information about how many times relays were switched to status Heating On. This screen is named
Relay On cycles.
Alarms view
By pressing Escape button from Main Screen – screen(-s) with Alarm appears.
If more than 1 Alarm is happened – use navigation by going Up/Down. Pressing
Escape button again leads from Alarm to Main Screen.
Menu system
By pressing Enter from the Main Screen– screen with Main Menu appears.
The menu system is navigated from Main
Screen by the following sequence: EN: Enter – Down/Up – Enter – Down/
Up – Enter – … .
EN: Enter – Down/Up – Enter – Down/
Up – Enter – … .
Pressing Escape button mostly leads to a transition to upper level.
FEC | Produced by Danfoss ©12
By scrolling the Down button you’ll get to the bottom part of Main Menu.
Menu windows above display the root directory of the menu tree or so-called Main Menu.
Activating any line by Enter button leads to a transition to a lower level of menu, opening a list of settings, parameters, special functions or so on. For example:
FEC | Produced by Danfoss © 13
Lines with data for
Active Channels #1-#7
Line with mode
Manually Of
over mode PR with the remaining time in 57 min.
Line with mode
Manually On
over mode 1S with the remaining time in 133 min.
Line with mode PR with set up cycle time 180 min. and Heating On status during 120 min. The real time after begining of the cycle is 113 minutes
Channel OFF
Channel
with Alarm
Sensor fault – open
or short circuit,
or not connected
Device
Time
Degrees
in Celsius
Device
Alarm
Sofware
version
Regulation
type
Real Temp.
on the
sensor for
1S mode
Heating
status
Set up Temp.
Main Screen view – explanation
The screen below is visible close to the maximum different information which can be presented on display.
The following Main Screen texts, abbreviations, icons have a special meaning:
FEC | Produced by Danfoss ©14
4.4 Control modes, special functions, special statuses and settings
Each of 7 Channels has possibility to be individually set up with one of three control modes – 1S (1 Sensor), PR (Power Regulation) and MOn/MOf (Manually On/Of).
The controller configurations for these 3 modes are the following:
1. Single sensor control with temperature sensor or 1S: one temperature sensor input, one relay output;
2. Power regulation control or time proportional power regulation or PR: no sensor input, one relay output;
3. Heating control Manually On and Manually Off with setting time period or MOn and MOf: no sensor input, one relay output;
Together with any control mode could be set up or enabled/disabled some special functions and statuses: “Relay status RO/RC”, “ CableOK?”, “ Relay test 5/30”, “ Channel ON/OFF” and Device ON/OFF”. Special functions and statuses are specified in chapters below.
Additionally, any Channel can be set up with status ‘not Active’ or Active = No. It means
Channel does not work at all and “empty” line appears on the Main Screen.
4.4.1 Active and Not Active Channel status
Not Active status can be used for applications there is no need to use full channel set of 7. And view/line for the Channel which is not used is simply deleted from the screen.
By the way, standard factory setting for DEVIreg™ Multi supposes 1 active Channel #2. The Main Screen with the only one Active Channel #2 is as on the picture below:
FEC | Produced by Danfoss © 15
Activation or deactivation can be done by the following menu sequence:
EN: Main Screen – Enter to Main Menu – Channels settings – Activate channels –
Activate #X1) – { Enter – Up/Down (YES/NO) – Enter }
1)
– here and further #X means any Channel number in diapason from #1 to #7.
2)
– here and further brackets indicate more detailed sequence.
2)
EN: Main Screen – Enter to Main Menu – Channels settings – Activate channels –
Activate #X1) – { Enter – Up/Down (YES/NO) – Enter }
Example of the base screens for the sequence above:
FEC | Produced by Danfoss ©16
4.4.2 Relay status RO/RC – special setting for status ‘Heating On’
Heating On is a logical status for systems with temperature sensor. It means that real
sensor temperature is below set up level and controller should provide a special signal to the system – either close or open relay contacts.
Heating On is a logical status that corresponds to heating system type. And some heating systems, for example electrical, mostly need relay that closes contacts when the heating is on. But another heating systems, for example water based, sometimes need relay that opens contacts when the heating is on. For this purpose, DEVIreg™ Multi has possibility to set up relay status for heating – ‘open’ or ‘close’.
Additionally, this relay status allows to implement both heating and cooling control, because cooling is system having opposite algorithm to heating system.
The special setting for logical status Heating On is named Relay status RO/RC – Relay Opened (RO) or Relay Closed (RC) each Channel Relay can be separately set up to status.
Factory setting – RC for relays or relays contacts which are normally opened (NO).
NB: This setting mostly works only when controller is powered!
Setting Relay status RO/RC can be done by the following menu sequence: EN: Main Screen – Enter to Main Menu – Channels settings – Channel #X –
Relay status RO/RC – { Enter – Up/Down (RO/RC) – Enter }
EN: Main Screen – Enter to Main Menu – Channels settings – Channel #X – Relay
status RO/RC – { Enter – Up/Down (RO/RC) – Enter }
4.4.3 1S or Single Sensor mode and Sensor Type set up
4.4.3.1 1S mode
Single sensor control (1S) is mode with one temperature sensor. And can be individually set up for any Channel.
The mode logic algorithm is the following: if sensor temperature is below set up value then heating is turned on, and if sensor temperature is above set up value then heating is turned off.
FEC | Produced by Danfoss © 17
Setting 1S mode can be done by the following menu sequence: EN: Main Menu – Channels settings – Channel #X – Regulation Type –
{ Enter – Up/Down (1S/PR) – Enter }
EN: Main Menu – Channels settings – Channel #X – Regulation Type – { Enter – Up/
Down (1S/PR) – Enter }
Common Channel diagram for 1S mode is shown on the picture below:
AI 1
COM
Channel #1
DI 1
C 1
NO 1
Some control parameters can be set up: mandatory – control temperature, optionally – hysteresis and control alarm temperature diapason.
Temperature. 1S mode has temp. setting with max. diapason from -50°C degree to 200°C. Default: 5°C.
NB: Each type of sensor has its own temperature range, which may differ from the maximum given above.
Hysteresis.1S mode has hysteresis setting with diapason from 0,2 degree to 9 degree. Default: 0,4°C.
NB: Hysteresis is used as the plus or minus value to the set temperature. For example, if set temp. = 5°C and hysteresis = 0,4°C, then heating will turn off at the temperature of 5 + 0,4 = 5,4°C and accordingly turn on at the temperature of 5 – 0,4 = 4,6°C.
FEC | Produced by Danfoss ©18
Setting Temperature and Hysteresis can be done by the following menu sequence:
EN: Main Screen – Enter to Main Menu – Channels settings – Channel #X –
Temp & Hysteresis – #X Set temperature – { Down – #X Set +-Hysteresis }
EN: Main Screen – Enter to Main Menu – Channels settings – Channel #X – Temp &
Hysteresis – #X Set temperature – { Down – #X Set +-Hysteresis }
Temperatures Alarm. 1S mode has Temp Alarm settings with 3 parameters – alarm Enabled
or Disabled, alarm minimal temperature and alarm maximum temperature. Alarm temperatures have unchangeable hysteresis 0,2°C. Default – Temp Alarm is Disabled, Alarm min Temp = 0°C, Alarm max Temp = 60°C.
NB: It is the full responsibility of the installer/user to set correct alarm values that correspond to the sensor type and for the specific application to avoid overheating of the cable, building materials and so on.
Example of data for Temp Alarm settings and temperature Alarm Status is presented on the screen below (lines 2-4):
Data on the picture above means the following: Temp Alarm is disabled for Channel #2 (Dis) and Software does not control alarm temperature, alarm range set up with values from 0 °C to 60 °C, actual temperature of the sensor out of the range – Alarm Status = Yes.
Setting Alarm Temperatures and Alarm Enabling can be done by the following menu sequence:
EN: Main Screen – Enter to Main Menu – Channels settings – Channel #X –
Alarm Temps & En/Dis – ( #X Alarm Temp En/Dis – Down – #X Alarm min Temp – Down – #X Alarm max Temp }
EN: Main Screen – Enter to Main Menu – Channels settings – Channel #X – Alarm
Temps & En/Dis – ( #X Alarm Temp En/Dis – Down – #X Alarm min Temp – Down – #X Alarm max Temp }
FEC | Produced by Danfoss © 19
Channel number
Real sensor
Temp.
Heating
status: On or Of
Set up Temp.
Line of the Main screen with 1S mode data for one Channel is shown on the picture below:
4.4.3.2 Sensor Type set up
1S control mode can be set up with different 8 types of temperature sensors.
Sensor unit can be selected via software connected to Channel’s analog inputs AI1-AI7 between: NTC15k (15 kOhm @ 25 °C), NTC10k (10 kOhm @ 25 °C), NTC5k (5 kOhm @ 25 °C), NTC2k (2 kOhm @ 25 °C), NTC100 (100 kOhm @ 25 °C), NTC16k (16,7 kOhm @ 100 °C), PT1000 (1000 Ohm @ 0 °C), Ni100 (100 Ohm @ 0 °C).
Setting of Sensor type can be done by the following menu sequence:
EN: Main Screen – Enter to Main Menu – Channels settings – Channel #X – Sensor
type –
{Enter – Up/Down ( PT1000/ NTC10k/ NTC100/ Ni100/ NTC2K/ NTC16k/
NTC5k/ NTC15k) }
EN:
Main Screen – Enter to Main Menu – Channels settings – Channel #X – Sensor type –
{Enter – Up/Down ( PT1000/ NTC10k/ NTC100/ Ni100/ NTC2K/ NTC16k/
NTC5k/ NTC15k) }
NB: Setting is possible/visible for Active Channels only.
Chosen Sensor type can be found in the Channel Data screens with the following menu sequence:
EN: Main Screen – Down.
EN: Main Screen – Down.
FEC | Produced by Danfoss ©20
Screen example:
Another possibility to see Sensor Type is to use the following sequence:
EN: Main Screen – Enter to Main Menu – Channels data – Channel #X
EN: Main Screen – Enter to Main Menu – Channels data – Channel #X
4.4.4 PR or Power Regulation mode
Power regulation is time proportional power regulation mode with a simple duty cycle generator with time set up during which heating is turned on within the period.
This mode can be individually set up for any Channel.
The PR logic algorithm is the following: if time counter is below set up cycle time when heating should be on (On time) then heating is turned on, and if time counter is above set up time then heating is turned off just up to the end of mode period.
FEC | Produced by Danfoss © 21
Setting PR mode can be done by the following menu sequence: EN: Main Screen – Enter to Main Menu – Channels settings – Channel #X –
Regulation Type – { Enter – Up/Down (1S/PR) – Enter }
EN: Main Screen – Enter to Main Menu – Channels settings – Channel #X – Regula-
tion Type – { Enter – Up/Down (1S/PR) – Enter }
PR mode logic diagram is shown on the picture below:
Period (1-900, min.)
On Time
Heating On Heating On
Heating O Heating O Heating O
Period Period
Heating On
Common Channel scheme for PR mode is shown on the picture below:
AI 1
COM
Channel #1
DI 1
C 1
NO 1
Two control parameters can be set up: Heating On time and period of PR mode.
Period. Control mode time cycle. Can be set up from 1 to 900 minutes. Default – 30 min.
On time. Time from the beginning of the Period during which heating is turned on. Default – 15 min.
NB: It is the full responsibility of the installer/user to set correct time values corresponding to the specific application to avoid overheating of the cable, building materials and so on.
FEC | Produced by Danfoss ©22
Time from
the beginning
of the Period (min.)
Heating status:
On or Of
On Time
(min.)
Period
(min.)
Parameters setting for PR mode can be done by the following menu sequence: EN: Main Screen – Enter to Main Menu – Channels settings – Channel #X – On Time
& Period – { Enter – #X Set On Time – Down – #X Set PR Period }
EN: Main Screen – Enter to Main Menu – Channels settings – Channel #X – On Time
& Period – { Enter – #X Set On Time – Down – #X Set PR Period }
Line of the Main screen with PR mode data for one Channel is shown on the picture below:
4.4.5 MOn and MOf – Manually heating On and Manually heating Of mode
Manually On/Of mode (on the screen – MOn or MOf) is control with setting time period
during which heating will be turned on or turned off. This mode can be started only on the base of 1S or PR mode and after Manually On/Of mode is finished, controller returns to the same initial mode – 1S or PR.
This mode can be individually set up for any Channel.
Three control parameters can be set up: time period, heating state – On or Of, and Start or Stop mode state.
Time Period. Setting Period of time for MOn or MOf mode. Default – 1 min.
Heating status. Setting state Heating On or Heating Of. Default – Of.
Start or Stop. Starting or Stopping control mode. After finishing of MOn or MOf mode
controller goes to Stop state automatically and disappears from the screen automatically too. Default – Stop.
NB: It is the full responsibility of the installer/user to use this mode and to set up correct states that correspond to the specific application to avoid overheating of the cable, building materials and so on.
FEC | Produced by Danfoss © 23
Data
of base mode
Heating status:
On or Of
The remaining
mode time (min.)
Setting MOn or MOf mode and mode parameters can be done by the following menu sequence: EN: Main Screen – Enter to Main Menu – Channels settings – Channel #X – Manually
On/Of – { Enter – #X Manually On/Of Time – Down – Status On or Of – Down – Manually On/Of Start or Stop }
EN: Main Screen – Enter to Main Menu – Channels settings – Channel #X – Manually
On/Of – { Enter – #X Manually On/Of Time – Down – Status On or Of – Down – Manually On/Of Start or Stop }
Main screen with MOn mode data for one Channel is shown on the picture below (here MOn started over 1S mode):
4.4.6 CableOK? – special channel function
CableOK? special function function can be used for checking the proper functioning
of the heating cable or other electrical equipment using a current flow control. In other words, the current in the heater is controlled when the heating is turned on. Channel
Alarm appears as the result of state ‘not OK’ for this function (indication – symbol ‘!’ in Channel line on the Main Screen).
For CableOK? function should be used additional device – for example Current Monitoring Relay (CMR) or similar. CMR should be connected to the digital inputs DI1-DI7 corresponding to Channel number. The main logic of CMR is the following – if current is not going through device then 2 contacts/outputs are closed, and if current is going through device then 2 contacts/outputs are opened. This logic may also be in the opposite contacts’ state.
NB: This function works the only when Channel has state ‘Heating On’! In other words – if heating is turned off (‘Heating Of’) cable or another heater does not consume any current and accordingly there’s nothing to control.
FEC | Produced by Danfoss ©24
This mode can be individually set up for any Channel. By default – function is Disabled for all Channels.
Common Channel diagram with connected CMR is shown on the picture below:
AI 1
COM
Channel #1
COM
DI 1-4
DI 1
C 1
NO 1
<I
CMR #1
For the state CableOK? = OK is used term Yes , and for the state CableOK? = not OK is used term No respectively.
For CableOK? function can be set up two control parameters: Enable or Disable, and digital input (DI) state for OK status – Normally Opened (NO) or Normally Closed (NC) on the COM DI input.
Enabled or Disabled. Function can be Enabled (En) or Disabled (Dis) for any Channel. By default – Disabled.
CableOK? NO/NC. Setting for state of digital input (DI) when CableOK? function is OK. It means if chosen NO for CableOK? = OK then digital input is not connected to the controller input COM DI or there is an open circuit between DI and COM DI. And vice versa, if chosen NC for CableOK? = OK then digital input connected to controller input COM DI or there is a short circuit between DI and COM DI. Default – NO or Normally Opened (this setting and proper CMR is shown on the picture above).
Settings CableOK? function can be done by the following menu sequence:
EN: Main Screen – Enter to Main Menu – Channels settings – Channel #X – Ca-
bleOK?– { Enter – #X CableOK? En/Dis – Down – #X CableOK? = NO/NC }
EN: Main Screen – Enter to Main Menu – Channels settings – Channel #X – Ca-
bleOK?– { Enter – #X CableOK? En/Dis – Down – #X CableOK? = NO/NC }
FEC | Produced by Danfoss © 25
Data for CableOK? function is presented on =Channel data #X screen, for example as on the screen below in 3 bottom lines:
Relevant data on the picture above means the following:
- CableOK? function is disabled for Channel #2 – ‘Dis’ on the screen, and software does not control state of the input DI2;
- input DI2 has setting ‘NO’ (Normally Open) or, in other words, when current flows through the cable/heater the input DI2 should not be closed on input COM DI;
- actual status for CableOK? function is OK or displayed ‘Ye s’ in the last line.
4.4.7 Channel ON/OFF – special function
Each Active Channel can be set up with status OFF or ON. OFF means that there is no need to carry out Channel control algorithm due to, for example, a malfunction of the cable or sensor, heating system installation and so on. In other words, Channel does not perform algorithm and does not perform any Alarms. At the same time the Channel saves all settings and for 1S mode active Channels show real sensors’ temperature and for PR mode – shows real mode time. Additionally, it is possible to do/change any settings.
Settings Channel ON/OFF function can be done by the following menu sequence:
EN: Main Screen – Enter to Main Menu – Channels settings – Channel #X – Channel
ON/OFF – {Enter – #X Channel ON/OFF }
EN: Main Screen – Enter to Main Menu – Channels settings – Channel #X – Channel
ON/OFF – {Enter – #X Channel ON/OFF }
When Channel is OFF hash sign/symbol – ‘#’ – is presented on the 2nd position of Main Screen line, for example:
FEC | Produced by Danfoss ©26
4.4.8 Device ON/OFF – special function and switch
DEVIreg™ Multi controller can be set up by Menu with status OFF. This means that there
is no need to carry out any regulation for all 7 Channels. At the same time all Channels save all settings and for 1S mode active Channels show real sensor temperature and for PR mode – show real time. Additionally, it is possible to do/change any settings.
Settings Device ON/OFF function can be done by the following menu sequence:
EN: Main Screen – Enter to Main Menu – Device ON/OFF – {Enter – Turn device ON –
Down – Turn device OFF/ON }
EN: Main Screen – Enter to Main Menu – Device ON/OFF – {Enter – Turn device ON –
Down – Turn device OFF }
When Device is OFF by special function a hash sign/symbol – ‘#’ – is visible in the left corner of Main Screen, for example like on the screen below:
FEC | Produced by Danfoss © 27
Additionally, DEVIreg™ Multi controller can be set up with status OFF by ‘mechanical’ switch connected to DI8:
Alarm
C 8
NO 8
COM
DI 5-8
Dev ice
OFF ON
DI 8
NC 8
NB: When no switch is used – it means Device is always ON.
When Device is OFF by 'mechanical' switch two hash sign/symbols – ‘##’ – are visible in the left corner of Main Screen, for example:
FEC | Produced by Danfoss ©28
4.4.9 Relay Test 5/30– special function
Each Active Channel Relay can be tested by this function. When function is started, the corresponding Channel relay switches On and Of every 5 sec. within 30 seconds.
Start of special test function Relay Test 5/30 can be done by the following menu sequence:
EN: Main Screen – Enter to Main Menu – Channels settings – Channel #X –
Relay Test 5/30 sec – {Enter – STOP/START }
EN: Main Screen – Enter to Main Menu – Channels settings – Channel #X – Relay Test
5/30 sec – {Enter – STOP/START }
NB: When this function is started nothing new appears on the screen(-s). Only the switching sound of the corresponding relay is heard.
4.4.10 Alarms, alarm data and alarm relay
DEVIreg™ Multi controller has Alarm relay with both types of contacts – NO and NC. For Alarm used controller contacts which have number 8 – NC8, C8 and NO8. Connection
diagram is shown on the picture below:
Alarm
NC 8
DI 8
C 8
NO 8
FEC | Produced by Danfoss © 29
Information about any Alarm happening to any Channel appears in the Channel line with exclamation symbol – ‘!’. For example, like on the picture below, when Alarm information has appeared due to the temperature sensor failure:
NB: Any Alarm type – e.g. sensor failure or CableOK?= No, has the same exclamation symbol on the screen.
Additionally, any Alarm happening in the controller appears on the Main Screen like device Alarm with three exclamation symbols – ‘!!!’ – on the 1st line of the Main Screen. Example is shown on the picture below:
NB: if Channel or Device is turned OFF any corresponded Alarm does not appear on the screen.
Detailed information about all Alarms can be found on special Alarm screens by pressing Escape button on the Main Screen.
Example of Alarm detailed information is shown on the picture below:
If more than one Alarm occurs, it is possible to flip the screens by Up and Down buttons.
FEC | Produced by Danfoss ©30
4.4.11 Relay Counters view and reset
DEVIreg™ Multi controller is collecting information about number of times the Channel
relay is turned on.
Relay counters information can be found in two ways.
The simplest way to see ‘Relay On cycles’ in total can be done by sequence:
EN: Main Screen – Up.
EN: Main Screen – Up.
For example, the screen view can be as below:
The second way to see list of service information can be done by the following menu sequence:
EN: Main Screen – Enter to Main Menu – Channels data – Channels data #X –
{ Down – Down }.
EN: Main Screen – Enter to Main Menu – Channels data – Channels data #X – { Down
– Down }.
For example:
FEC | Produced by Danfoss © 31
4.4.12 Language setting
Language settings can be done by the following menu sequence:
EN: Main Screen – Enter to Main Menu – Language – { Enter – English/Polish/
Russian/Ukrainian/… }
EN: Main Screen – Enter to Main Menu – Language – { Enter – English/Polish/Rus-
sian/Ukrainian/… }
NB: Different software versions can be with different set of languages.
4.4.13 Date and Time settings
DEVIreg™ Multi controller has RTC (Real Time Clock) for fixing time of data logging
information, for example Alarms.
Date and Time settings can be done by the following menu sequence:
EN: Main Screen – Enter to Main Menu – Device settings – Date & Time setup –
{ Enter – Right/Left – Enter – YYYY – MM – DD – WD – hh – mm – ss }
EN: Main Screen – Enter to Main Menu – Device settings – Date & Time setup – {
Enter – Right/Left – Enter – YYYY – MM – DD – WD – hh – mm – ss }
NB: Battery back-up time is min. 48 hours.
4.4.14 BMS settings
DEVIreg™ Multi controller has Modbus RS-485 opto-insulated serial interface.
Modbus RS-485 settings can be done by the following menu sequence:
EN: Main Screen – Enter to Main Menu – Device settings – BMS settings – { Enter –
Serial address – Down – Serial baud rate – Down – Serial settings }
EN: Main Screen – Enter to Main Menu – Device settings – BMS settings – { Enter –
Serial address – Down – Serial baud rate – Down – Serial settings }
More detailed information is contained in the Appendix A.
FEC | Produced by Danfoss ©32
CMR - Current Monitoring Relay
MCX08M2 - TOP
80G8036.04
5 Connection diagram
Connection scheme DEVIreg™ Multi
Power
110/230 V AC
AI 1
COM
AI 2
COM
AI 3
COM
AI 3-4
AI 4
COM
AI 5-8
Channel #1 Channel #2 Channel #3 Channel #4 Channel #5 Channel #6 Channel #7 Alarm RS485
COM
DI 1-4
DI 1
C 1
NO 1
DI 2
C 2
NO 2
DI 3
NC 3
C 3
NO 3
DI 4
NC 4
C 4
NO 4
DI 5
C 5
<I <I <I <I <I <I <I
CMR #1 CMR #2 CMR #3 CMR #4 CMR #5 CMR #6 CMR #7
S - temperature Sensor;
General MCX08M2 controller connection diagram
To the AI
PWM-PPM
0/10 Vdc
optoinsulated
Not
used
0/10 V
To the AI
(100 mA max)
(120 mA max)
RS485
(Modbus)
D -
AI 5
NO 5
AI 6
DI 6
C 6
NO 6
AI 7
DI 7
NC 7
C 7
NO 7
NC 8
DI 8
C 8
Dev ice
OFF ON
D +
GND
NO 8
COM
DI 5-8
Danfoss
NTC, 0/1 V, 0/5 V,
0/10 V, PT1000
FEC | Produced by Danfoss © 33
MCX08M2 - BOTTOM
6 Technical Specifications
6.1 Technical data
Type Value
Nominal voltage 110/230 V AC, 50–60 Hz Power consumption, max. 20 V A Relay resistive (inductive, cos(phi) = 0,6) load:
Total current load limit C1-NO1, C2-NO2 C5-NO5, C6-NO6 C3-NO3-NC3, C4-NO4-NC4 C7-NO7-NC7, C8-NO8-NC8
Sensor inputs Analog inputs AI1-AI8 Sensing unit Temperature sensors separately selectable via
software at analog inputs AI1-AI7 between:
Sensor failure monitoring Disconnected or short-circuited sensor Digital inputs DI1-DI8, voltage free contacts, on/off inputs Connection specification Grouped screws plug-in connectors, pitch 5 mm Cable specification for connectors terminals 0,2-2,5 mm² Battery back-up time, min. 48 hours Ball pressure test 125 °C according to IEC 60730-1 Pollution degree 2 (domestic use) Controller type 1 C Operating temperatures and conditions CE: -20T60 / UL: 0T55, 90% RH non-condensing Storage temperature and conditions -30Т85, 90% RH non-condensing IP class IP40 only on the front cover Protection class Class II ­Immunity against voltage surges Designed for Over Voltage Category II Dimensions (H/W/D), DIN dimension : 110(122) х 138 х 70 mm, 8 DIN modules Mounting method DIN-rail, complying with EN 60715 Weight, net 511 g Menu languages: v01.7: EN, PL, RU, UA Base controller Danfoss MCX08M2, item no. 080G0307 Software class A
10 (3,5) A (100 000 cycles)
6 (4) A (100 000 cycles) 6 (4) A (100 000 cycles) 6 (4) A (100 000 cycles)
NTC15k (15 kOhm @ 25 °C) NTC10k (10 kOhm @ 25 °C)
NTC5k (5 kOhm @ 25 °C) NTC2k (2 kOhm @ 25 °C)
NTC100 (100 kOhm @ 25 °C)
NTC16k (16,7 kOhm @ 100 °C)
PT1000 (1000 Ohm @ 0 °C)
Ni100 (100 Ohm @ 0 °C)
32 A
FEC | Produced by Danfoss ©34
110
6.2 Dimensions
140 6063
FEC | Produced by Danfoss © 35
7 Disposal Instruction
FEC | Produced by Danfoss ©36
Appendix A. BMS and RS-485 interface
The controller has a built-in Modbus data transmission system and can be connected to the BMS central unit.
A1. Communication settings
Default communication settings:
Serial address: 1.
Serial baud rate (Transmission speed): 19200.
Serial setting: 8N1.
A2. RS-485 specifications
MCX hardware network specifications (wiring, topology, etc.) can be found in Danfoss document:
User manual. Meet any HVAC requirement with the reliability of MCX network.
This document provides general indications for the setup of RS-485 networks.
A3. Modbus parameters and variables
Modbus parameters and variables for DEVIreg™ Multi controller.
LABEL DESCRIPTION MIN MAX. VALUE/TYPE UNIT RW ADU
PARAMETERS & STATUS VARIABLES
Q10 Activate channels > Activate #1 P16 Activate #1 0 1 0 – NO Enum 2 RW 3001
W10 Activate channels > Activate #2
O16 Activate #2 0 1 1 – YES Enum 2 RW 3002 R10 Activate channels > Activate #3
I16 Activate #3 0 1 0 – NO Enum 2 RW 3003 G10 Activate channels > Activate #4 U16 Activate #4 0 1 0 – NO Enum 2 RW 3004 H10 Activate channels > Activate #5 Y16 Activate #5 0 1 0 – NO Enum 2 RW 3005 Z10 Activate channels > Activate #6
T16 Activate #6 0 1 0 – NO Enum 2 RW 3006 X10 Activate channels > Activate #7 V16 Activate #7 0 1 0 – NO Enum 2 RW 3007
FEC | Produced by Danfoss © 37
Q1 Channel #1 > Regulation Type P1 #1 Regulation Type: 1S – Single Sensor,
PR – Power Regulation Q2 Channel #1 > Temp & Hysteresis P2 #1 Set Temperature -50 200 5 °C RW 3009 P3 #1 Set +-Hysteresis 0.2 6 0.4 °C RW 3010 Q3 Channel #1 > On Time & Period P4 #1 Set On Time 1 0 15 min. RW 3011 P5 #1 Set PR Period (max. 900 minutes) 0 900 30 min. RW 3012 Q4 Channel #1 > Alarm Temps & En/Dis P6 #1 Alarm Temp En/Dis 0 1 0 – Dis Enum 5 RW 3013 P7 #1 Alarm min. Temp -50 0 0 °C RW 3014 P8 #1 Alarm max. Temp 0 200 60 °C RW 3015 Q5 Channel #1 > CableOK? P9 #1 CableOK? En/Dis - Enable or Disable the
function of current monitoring in the load
P10 #1 CableOK? = NO/NC. Set up DI1 status
Normally Opened (NO) or Normally Closed (NC)
when cable is OK
Q75 Power calculator > Channel Power #1 P11 #1 Channel Power (max. 32000) 0 32000 0 W RW 3018
Q8 Channel #1 > Manually On/Of
P12 #1 Manually On/Of Time – Set up period of time
for MOn or MOf status (max. 900 minutes)
P13 #1 Status On or Of for mode Heating Manually 0 1 0 – Of Enum 11 RW 3020 P14 #1 Manually On/Of Start or Stop control mode.
Caution: this mode may cause overheating and
damage! Q9 Channel #1 > Channel ON/OFF
P15 #1 Channel ON/OFF If OFF – symbol # in the
line, algorithm is stopped, but real Temp. is
being shown
Q11 Channel #1 > Sensor type P17 #1 Sensor type 0 7 1 – PT1000 Enum 9 RW 3023 Q12 Channel #1 > Relay Status RO/RC P18 #1 Relay status - Set up Relay Opened (RO) or
Relay Closed (RC) for status ‘Heating On’
Q13 Channel #1 > Relay Test 5/30 sec. P19
#1 Relay Test 5/30 - Every 5 sec. switching for 30 sec.
W1 Channel #2 > Regulation Type
O1 #2 Regulation Type: 1S – Single Sensor,
PR – Power Regulation
W2 Channel #2 > Temp & Hysteresis
O2 #2 Set Temperature -50 200 5 °C RW 3027 O3 #2 Set +-Hysteresis 0.2 6 0.4 °C RW 3028
W3 Channel #2 > On Time & Period
0 1 1 – 1S Enum 1 RW 3008
0 1 0 – Dis Enum 5 RW 3016
0 1 1 – NO Enum 8 RW 3017
1 900 1 min. RW 3019
0 1 0 – STOP Enum 6 RW 3021
0 1 0 – OFF Enum 7 RW 3022
0 1 0 – RC Enum 10 RW 3024
0 1 0 – STOP Enum 6 RW 3025
0 1 1 – 1S Enum 1 RW 3026
FEC | Produced by Danfoss ©38
O4 #2 Set On Time 1 0 15 min. RW 3029 O5 #2 Set PR Period (max. 900 minutes) 0 900 30 min. RW 3030
W4 Channel #2 > Alarm Temps & En/Dis
O6 #2 Alarm Temp En/Dis 0 1 0 – Dis Enum 5 RW 3031 O7 #2 Alarm min. Temp -50 0 0 °C RW 3032 O8 #2 Alarm max. Temp 0 200 60 °C RW 3033
W5 Channel #2 > CableOK?
O9 #2 CableOK? En/Dis - Enable or Disable the
function of current monitoring in the load
O10 #2 CableOK? = NO/NC. Set up DI2 status
Normally Opened (NO) or Normally Closed (NC)
when cable is OK
W75 Power calculator > Channel Power #2
O11 #2 Channel Power (max. 32000) 0 32000 0 W RW 3036
W8 Channel #2 > Manually On/Of
O12 #2 Manually On/Of Time – Set up period of time
for MOn or MOf status (max. 900 minutes)
O13 #2 Status On or Of for mode Heating Manually 0 1 0 – Of Enum 11 RW 3038 O14 #2 Manually On/Of Start or Stop control mode.
Caution: this mode may cause overheating and
damage!
W9 Channel #2 > Channel ON/OFF
O15 #2 Channel ON/OFF If OFF – symbol # in the
line, algorithm is stopped, but real Temp. is
being shown
W11 Channel #2 > Sensor type
O17 #2 Sensor type 0 7 1 – PT1000 Enum 9 RW 3041
W12 Channel #2 > Relay Status RO/RC
O18 #2 Relay status - Set up Relay Opened (RO) or
Relay Closed (RC) for status ‘Heating On’
W13 Channel #2 > Relay Test 5/30 sec.
O19
#2 Relay Test 5/30 - Every 5 sec. switching for 30 sec. R1 Channel #3 > Regulation Type
I1 #3 Regulation Type: 1S – Single Sensor,
PR – Power Regulation R2 Channel #3 > Temp & Hysteresis
I2 #3 Set Temperature -50 200 5 °C RW 3045 I3 #3 Set +-Hysteresis 0.2 6 0.4 °C RW 3046
R3 Channel #3 > On Time & Period
I4 #3 Set On Time 1 0 15 min. RW 3047 I5 #3 Set PR Period (max. 900 minutes) 0 900 30 min. RW 3048
R4 Channel #3 > Alarm Temps & En/Dis
I6 #3 Alarm Temp En/Dis 0 1 0 – Dis Enum 5 RW 3049 I7 #3 Alarm min. Temp -50 0 0 RW 3050 I8 #3 Alarm max. Temp 0 200 60 RW 3051
0 1 0 – Dis Enum 5 RW 3034
0 1 1 – NO Enum 8 RW 3035
1 900 1 min. RW 3037
0 1 0 – STOP Enum 6 RW 3039
0 1 0 – OFF Enum 7 RW 3040
0 1 0 – RC Enum 10 RW 3042
0 1 0 – STOP Enum 6 RW 3043
0 1 1 – 1S Enum 1 RW 3044
FEC | Produced by Danfoss © 39
R5 Channel #3 > CableOK?
I9 #3 CableOK? En/Dis - Enable or Disable the
function of current monitoring in the load I10 #3 CableOK? = NO/NC. Set up DI3 status
Normally Opened (NO) or Normally Closed (NC)
when cable is OK
R75 Power calculator > Channel Power #3
I11 #3 Channel Power (max. 32000) 0 32000 0 W RW 3054 R8 Channel #3 > Manually On/Of I12 #3 Manually On/Of Time – Set up period of time
for MOn or MOf status (max. 900 minutes) I13 #3 Status On or Of for mode Heating Manually 0 1 0 – Of Enum 11 RW 3056 I14 #3 Manually On/Of Start or Stop control mode.
Caution: this mode may cause overheating and
damage! R9 Channel #3 > Channel ON/OFF I15 #3 Channel ON/OFF If OFF – symbol # in the
line, algorithm is stopped, but real Temp. is
being shown
R11 Channel #3 > Sensor type
I17 #3 Sensor type 0 7 1 – PT1000 Enum 9 RW 3059
R12 Channel #3 > Relay Status RO/RC
I18 #3 Relay status - Set up Relay Opened (RO) or
Relay Closed (RC) for status ‘Heating On’
R13 Channel #3 > Relay Test 5/30 sec.
I19
#3 Relay Test 5/30 - Every 5 sec. switching for 30 sec. G1 Channel #4 > Regulation Type U1 #4 Regulation Type: 1S – Single Sensor, PR –
Power Regulation G2 Channel #4 > Temp & Hysteresis U2 #4 S et Temperature -50 200 5 °C RW 3063 U3 #4 Set +-Hysteresis 0.2 6 0.4 °C RW 3064 G3 Channel #4 > On Time & Period U4 #4 Set On Time 1 0 15 min. RW 3065 U5 #4 Set PR Period (max. 900 minutes) 0 900 30 min. RW 3066 G4 Channel #4 > Alarm Temps & En/Dis U6 #4 Alarm Temp En/Dis 0 1 0 – Dis Enum 5 RW 3067 U7 #4 Alarm min. Temp -50 0 0 °C RW 3068 U8 #4 Alarm max. Temp 0 200 60 °C RW 3069 G5 Channel #4 > CableOK? U9 #4 CableOK? En/Dis - Enable or Disable the
function of current monitoring in the load
U10 #4 CableOK? = NO/NC. Set up DI4 status
Normally Opened (NO) or Normally Closed (NC)
when cable is OK
G75 Power calculator > Channel Power #4
0 1 0 – Dis Enum 5 RW 3052
0 1 1 – NO Enum 8 RW 3053
1 900 1 min. RW 3055
0 1 0 – STOP Enum 6 RW 3057
0 1 0 – OFF Enum 7 RW 3058
0 1 0 – RC Enum 10 RW 3060
0 1 0 – STOP Enum 6 RW 3061
0 1 1 – 1S Enum 1 RW 3062
0 1 0 – Dis Enum 5 RW 3070
0 1 1 – NO Enum 8 RW 3071
FEC | Produced by Danfoss ©40
U11 #4 Channel Power (max. 32000) 0 32000 0 W RW 3072
G8 Channel #4 > Manually On/Of
U12 #4 Manually On/Of Time – Set up period of time
for MOn or MOf status (max. 900 minutes)
U13 #4 Status On or Of for mode Heating Manually 0 1 0 – Of Enum 11 RW 3074 U14 #4 Manually On/Of Start or Stop control mode.
Caution: this mode may cause overheating and
damage! G9 Channel #4 > Channel ON/OFF
U15 #4 Channel ON/OFF If OFF – symbol # in the
line, algorithm is stopped, but real Temp. is
being shown
G11 Channel #4 > Sensor type U17 #4 Sensor type 0 7 1 – PT1000 Enum 9 RW 3077 G12 Channel #4 > Relay Status RO/RC U18 #4 Relay status - Set up Relay Opened (RO) or
Relay Closed (RC) for status ‘Heating On’
G13 Channel #4 > Relay Test 5/30 sec. U19
#4 Relay Test 5/30 - Every 5 sec. switching for 30 sec. H1 Channel #5 > Regulation Type Y1 #5 Regulation Type: 1S – Single Sensor,
PR – Power Regulation H2 Channel #5 > Temp & Hysteresis Y2 #5 Set Temperature -50 200 5 °C RW 3081 Y3 #5 Set +-Hysteresis 0.2 6 0.4 °C RW 3082 H3 Channel #5 > On Time & Period Y4 #5 Set On Time 1 0 15 min. RW 3083 Y5 #5 Set PR Period (max. 900 minutes) 0 900 30 min. RW 3084 H4 Channel #5 > Alarm Temps & En/Dis Y6 #5 Alarm Temp En/Dis 0 1 0 – Dis Enum 5 RW 3085 Y7 #5 Alarm min. Temp -50 0 0 °C RW 3086 Y8 #5 Alarm max. Temp 0 200 60 °C RW 3087 H5 Channel #5 > CableOK? Y9 #5 CableOK? En/Dis - Enable or Disable the
function of current monitoring in the load
Y10 #5 CableOK? = NO/NC. Set up DI5 status
Normally Opened (NO) or Normally Closed (NC)
when cable is OK
H75 Power calculator > Channel Power #5 Y11 #5 Channel Power (max. 32000) 0 32000 0 W RW 3090
H8 Channel #5 > Manually On/Of
Y12 #5 Manually On/Of Time – Set up period of time
for MOn or MOf status (max. 900 minutes)
Y13 #5 Status On or Of for mode Heating Manually 0 1 0 – Of Enum 11 RW 3092
1 900 1 min. RW 3073
0 1 0 – STOP Enum 6 RW 3075
0 1 0 – OFF Enum 7 RW 3076
0 1 0 – RC Enum 10 RW 3078
0 1 0 – STOP Enum 6 RW 3079
0 1 1 – 1S Enum 1 RW 3080
0 1 0 – Dis Enum 5 RW 3088
0 1 1 – NO Enum 8 RW 3089
1 900 1 min. RW 3091
FEC | Produced by Danfoss © 41
Y14 #5 Manually On/Of Start or Stop control mode.
Caution: this mode may cause overheating and
damage! H9 Channel #5 > Channel ON/OFF
Y15 #5 Channel ON/OFF If OFF – symbol # in the
line, algorithm is stopped, but real Temp. is
being shown
H11 Channel #5 > Sensor type Y17 #5 Sensor type 0 7 1 – PT1000 Enum 9 RW 3095 H12 Channel #5 > Relay Status RO/RC Y18 #5 Relay status - Set up Relay Opened (RO) or
Relay Closed (RC) for status ‘Heating On’
H13 Channel #5 > Relay Test 5/30 sec. Y19
#5 Relay Test 5/30 - Every 5 sec. switching for 30 sec. Z1 Channel #6 > Regulation Type T1 #6 Regulation Type: 1S – Single Sensor,
PR – Power Regulation Z2 Channel #6 > Temp & Hysteresis T2 #6 Set Temperature -50 200 5 °C RW 3099 T3 #6 Set +-Hysteresis 0.2 6 0.4 °C RW 3100 Z3 Channel #6 > On Time & Period T4 #6 Set On Time 1 0 15 min. RW 3101 T5 #6 Set PR Period (max. 900 minutes) 0 900 30 min. RW 3102 Z4 Channel #6 > Alarm Temps & En/Dis T6 #6 Alarm Temp En/Dis 0 1 0 – Dis Enum 5 RW 3103 T7 #6 Alarm min. Temp -50 0 0 °C RW 3104 T8 #6 Alarm max. Temp 0 200 60 °C RW 3105 Z5 Channel #6 > CableOK? T9 #6 CableOK? En/Dis - Enable or Disable the
function of current monitoring in the load
T10 #6 CableOK? = NO/NC. Set up DI6 status
Normally Opened (NO) or Normally Closed (NC)
when cable is OK
Z75 Power calculator > Channel Power #6
T11 #6 Channel Power (max. 32000) 0 32000 0 W RW 3108
Z8 Channel #6 > Manually On/Of
T12 #6 Manually On/Of Time – Set up period of time
for MOn or MOf status (max. 900 minutes)
T13 #6 Status On or Of for mode Heating Manually 0 1 0 – Of Enum 11 RW 3110 T14 #6 Manually On/Of Start or Stop control mode.
Caution: this mode may cause overheating and
damage! Z9 Channel #6 > Channel ON/OFF
T15 #6 Channel ON/OFF If OFF – symbol # in the
line, algorithm is stopped, but real Temp. is
being shown
0 1 0 – STOP Enum 6 RW 3093
0 1 0 – OFF Enum 7 RW 3094
0 1 0 – RC Enum 10 RW 3096
0 1 0 – STOP Enum 6 RW 3097
0 1 1 – 1S Enum 1 RW 3098
0 1 0 – Dis Enum 5 RW 3106
0 1 1 – NO Enum 8 RW 3107
1 900 1 min. RW 3109
0 1 0 – STOP Enum 6 RW 3111
0 1 0 – OFF Enum 7 RW 3112
FEC | Produced by Danfoss ©42
Z11 Channel #6 > Sensor type
T17 #6 Sensor type 0 7 1 – PT1000 Enum 9 RW 3113
Z12 Channel #6 > Relay Status RO/RC
T18 #6 Relay status - Set up Relay Opened (RO) or
Relay Closed (RC) for status ‘Heating On’
Z13 Channel #6 > Relay Test 5/30 sec.
T19
#6 Relay Test 5/30 - Every 5 sec. switching for 30 sec. X1 Channel #7 > Regulation Type V1 #7 Regulation Type: 1S – Single Sensor,
PR – Power Regulation X2 Channel #7 > Temp & Hysteresis V2 #7 Set Temperature -50 200 5 °C RW 3117 V3 #7 Set +-Hysteresis 0.2 6 0.4 °C RW 3118 X3 Channel #7 > On Time & Period V4 #7 Set On Time 1 0 15 min. RW 3119 V5 #7 Set PR Period (max. 900 minutes) 0 900 30 min. RW 3120 X4 Channel #7 > Alarm Temps & En/Dis V6 #7 Alarm Temp En/Dis 0 1 0 – Dis Enum 5 RW 3121 V7 #7 Alarm min. Temp -50 0 0 °C RW 3122 V8 #7 Alarm max. Temp 0 200 60 °C RW 3123 X5 Channel #7 > CableOK? V9 #7 CableOK? En/Dis - Enable or Disable the
function of current monitoring in the load
V10 #7 CableOK? = NO/NC. Set up DI7 status
Normally Opened (NO) or Normally Closed (NC)
when cable is OK
X75 Power calculator > Channel Power #7 V11 #7 Channel Power (max. 32000) 0 32000 0 W RW 3126
X8 Channel #7 > Manually On/Of
V12 #7 Manually On/Of Time – Set up period of time
for MOn or MOf status (max. 900 minutes)
V13 #7 Status On or Of for mode Heating Manually 0 1 0 – Of Enum 11 RW 3128 V14 #7 Manually On/Of Start or Stop control mode.
Caution: this mode may cause overheating and
damage! X9 Channel #7 > Channel ON/OFF
V15 #7 Channel ON/OFF If OFF symbol # on the
main screen, algorithm is stopped, but real
Temp. is shown
X11 Channel #7 > Sensor type V17 #7 Sensor type 0 7 1 – PT1000 Enum 9 RW 3131 X12 Channel #7 > Relay Status RO/RC V18 #7 Relay status - Set up Relay Opened (RO) or
Relay Closed (RC) for status ‘Heating On’
X13 Channel #7 > Relay Test 5/30 sec. V19
#7 Relay Test 5/30 - Every 5 sec. switching for 30 sec.
0 1 0 – RC Enum 10 RW 3114
0 1 0 – STOP Enum 6 RW 3115
0 1 1 – 1S Enum 1 RW 3116
0 1 0 – Dis Enum 5 RW 3124
0 1 1 – NO Enum 8 RW 3125
1 900 1 min. RW 3127
0 1 0 – STOP Enum 6 RW 3129
0 1 0 – OFF Enum 7 RW 3130
0 1 0 – RC Enum 10 RW 3132
0 1 0 – STOP Enum 6 RW 3133
FEC | Produced by Danfoss © 43
ALC Alarms settings > Alarm configuration BUZ Buzzer active time 0 15 1 min. RW 3137 AdL Alarm relay activation delay 0 999 2 s RW 3138 AOF Alarm relay active if unit in OFF 0 1 0 – NO Enum 2 RW 3139
StU Device settings > Device setup y01 ON/OFF 0 1 1 - YES Enum 2 RW 3143 y02 Sensor filter 0 3 3 RW 3144 y99 FirstTimeStart 0 1 1 RW 3145 FSe Device settings > Factory Reset y07 Restore default parameters 0 1 0 - NO Enum 2 RW 3146
ALARMS
LABEL DESCRIPTION MIN. MAX. RESET IN OFF
A01 Device is logically tuned off by either switcher
on DI8 (##) or menu Device ON/OFF (#)
E01 Alarm Sensor #1 0 1 AUTO ACTIVE Read 1901 .09 E02 Alarm Sensor #2 0 1 AUTO ACTIVE Read 1901 .10 E03 Alarm Sensor #3 0 1 AUTO ACTIVE Read 1901 .11 E04 Alarm Sensor #4 0 1 AUTO ACTIVE Read 1901 .12 E05 Alarm Sensor #5 0 1 AUTO ACTIVE Read 1901 .13 E06 Alarm Sensor #6 0 1 AUTO ACTIVE Read 1901 .14 E07 Alarm Sensor #7 0 1 AUTO ACTIVE Read 1901 .15 E09 Alarm CableOK? #1 0 1 AUTO ACTIVE Read 1901 .00 E10 Alarm CableOK? #2 0 1 AUTO ACTIVE Read 1901 .01 E11 Alarm CableOK? #3 0 1 AUTO ACTIVE Read 1901 .02 E12 Alarm CableOK? #4 0 1 AUTO ACTIVE Read 1901 .03 E13 Alarm CableOK? #5 0 1 AUTO ACTIVE Read 1901 .04 E14 Alarm CableOK? #6 0 1 AUTO ACTIVE Read 1901 .05 E15 Alarm CableOK? #7 0 1 AUTO ACTIVE Read 1901 .06 E17 Alarm max. Temp #1 0 1 AUTO ACTIVE Read 1901 .07 E18 Alarm max. Temp #2 0 1 AUTO ACTIVE Read 1902 .08 E19 Alarm max. Temp #3 0 1 AUTO ACTIVE Read 1902 .09 E20 Alarm max. Temp #4 0 1 AUTO ACTIVE Read 1902 .10 E21 Alarm max. Temp #5 0 1 AUTO ACTIVE Read 1902 .11 E22 Alarm max. Temp #6 0 1 AUTO ACTIVE Read 1902 .12 E23 Alarm max. Temp #7 0 1 AUTO ACTIVE Read 1902 .13 E24 Alarm min. Temp #1 0 1 AUTO ACTIVE Read 1902 .14 E25 Alarm min. Temp #2 0 1 AUTO ACTIVE Read 1902 .15 E26 Alarm min. Temp #3 0 1 AUTO ACTIVE Read 1902 .00 E27 Alarm min. Temp #4 0 1 AUTO ACTIVE Read 1902 .01 E28 Alarm min. Temp #5 0 1 AUTO ACTIVE Read 1902 .02 E29 Alarm min. Temp #6 0 1 AUTO ACTIVE Read 1902 .03 E30 Alarm min. Temp #7 0 1 AUTO ACTIVE Read 1902 .04 E31 Memory is full 0 1 AUTO ACTIVE Read 1902 .05
0 1 AUTO ACTIVE Read 1901 .08
FEC | Produced by Danfoss ©44
I/O CONFIGURATION
AI ANALOG INPUTS
1 Temperature1 -50.0 200.0 PT1000 Read 18502 2 Temperature2 -50.0 200.0 PT1000 Read 18503 3 Temperature3 -50.0 200.0 PT1000 Read 18504 4 Temperature4 -50.0 200.0 PT1000 Read 18505 5 Temperature5 -50.0 200.0 PT1000 Read 18506 6 Temperature6 -50.0 200.0 PT1000 Read 18507 7 Temperature7 -50.0 200.0 PT1000 Read 18508 8
DI DIGITAL INPUTS
1 Cable1 0 1 N.O. Read 17504 2 Cable2 0 1 N.O. Read 17505 3 Cable3 0 1 N.O. Read 17506 4 Cable4 0 1 N.O. Read 17507 5 Cable5 0 1 N.O. Read 17508 6 Cable6 0 1 N.O. Read 17509 7 Cable7 0 1 N.O. Read 17510 8 On/Off 0 1 N.C. Read 17502
DO DIGITAL OUTPUTS
1 Heat1 0 1 N.O. Read 18003 2 Heat2 0 1 N.O. Read 18004 3 Heat3 0 1 N.O. Read 18005 4 Heat4 0 1 N.O. Read 18006 5 Heat5 0 1 N.O. Read 18007 6 Heat6 0 1 N.O. Read 18008 7 Heat7 0 1 N.O. Read 18009 8 Alarm 0 1 N.O. Read 18002
FEC | Produced by Danfoss © 45
Warranty
At DEVI, we find it of great importance to deliver high quality products with long lasting effects. DEVIwarranty™ is a series of 4 individual, best-in-market warranties to give you full peace of mind while using DEVI products in electric heating systems. For all DEVI products, we maintain the following warranties:
A 20-year full service warranty is valid for:
• heating cables incl. DEVIflex™ / DEVIsafe™ / DEVIsnow™ / DEVIasphalt™ / DEVIaqua™/ DEVIbasic™ / DEVIcomfort™ / DEVIsport™ (DSM3) / DEVImulti™ / DEVIinline™;
• heating mats incl. DEVImat™ / DEVIcomfort™ / DEVIheat™ / DEVIsnow™ / DEVIasphalt™ / DTCE;
Not only does this warranty include costs of reparation or replacement, but also installation and floor materials, such as damage to brickwork and tiles. For more details, read DEVIwarranty™ terms and conditions below.
A 10-year product warranty is valid for:
• DEVIcell™ plates, DEVIpipeguard™ LSZH self-limiting heating cables;
A 5-year product warranty is valid for DEVI thermostats, floor heating systems, self-limiting heating cables, and accessories:
• DEVIreg™ Smart thermostat;
• DEVIreg™ Touch thermostat;
• DEVIdry™ floor heating element under carpet, laminate and wooden floor (not including the DEVIdry™ thermostats and control sets);
• DEVIiceguard™, DEVIpipeheat™, DEVIpipeguard™ and DEVIhotwatt™ self-limiting heating cables;
• All related accessories;
A 2-year product warranty is valid for:
• DEVIreg™ 130–132 / 233 / 316 /330 / 527 / 528 / 530–535 / 610 thermostats;
• DEVIreg™ Multi, DEVIreg™ 850 controllers;
• DEVIlink™ wireless control system;
• DEVIdry™ thermostats and control sets;
• DEVIreg™ Therm Control;
• DEVIfoil™ heating foils;
• DEVIrail™ towel heaters;
• DEVItemp™ industrial heaters;
• DEVItronic™ anti-condensation heaters;
• Radiant heaters;
• Power supply units for thermostats;
• All related accessories, including heating cables, and heating mats accessories.
Should you, against all expectations, experience a problem your DEVI product, you will find that DEVI offers DEVIwarranty™ from the date of purchase on the following conditions: During the warranty period DEVI shall offer a new comparable product or repair the product in case the product is found to be faulty by reason of defective design, materials or workmanship. The repair or replacement shall be carried out free of charge
with
providing that the warranty claim is valid. The decision to either repair or replace will be solely at the discretion of DEVI. DEVI shall not be liable for any consequential or incidental damages including, but not limited to, damages to property or extra utility expenses. An extension of the warranty period following repairs undertaken cannot be granted. The warranty shall be valid only if the WARRANTY CERTIFICATE is completed correctly and in accordance with the instructions, and provided the fault is submitted to the installer or the seller without undue delay and proof of purchase is provided. Please note that the WARRANTY CERTIFICATE must be completed in English or local language. DEVIwarranty™ shall not cover any damage caused by incorrect conditions of use, incorrect installation or if installation has been carried out by non-authorized electricians. All work will be invoiced in full if DEVI is required to inspect or repair faults that have arisen as a result of any of the above. The DEVIwarranty™ shall not extend to products which have not been paid in full. DEVI will, at all times, provide a rapid and effective response to all complaints and inquiries from our customers. The warranty explicitly excludes all claims exceeding the above conditions.
Attention: The Warranty Certificate must be completed correctly for the Warranty to be valid.
FEC | Produced by Danfoss ©46
Warranty Certificate
The DEVIwarranty™ is granted to:
Name:
Address:
Postal code: Phone:
Please observe!
In order to obtain the DEVIwarranty™, the following must be
carefully filled in. See other conditions on previous page.
Electrical Installation by:
Installation date:
Type of thermostat:
Production code:
Suppliers Stamp:
FEC | Produced by Danfoss © 47
Danfoss A/S
Nordborgvej 81 6430 Nordborg, Syddanmark Denmark
08097125 & AN335045092882en-000104 Produced by Danfoss © 06/2020
Loading...