Danfoss DEVIreg Hotwater Installation guide

DEVIreg™ Hotwater
EN
Installation and User Guide
DEVIreg™ Hotwater
DIN-rail programmable controller for hotwater maintenance
Intelligent solutions with lasting effect
Visit devi.com
Table of content
1 Introduction .......................................................................4
2 Safety Instructions .................................................................5
3 Mounting Instructions .............................................................5
4 User Manual .......................................................................6
4.1 General use ...................................................................6
Buttons ..................................................................................6
Display ...................................................................................6
Main Screen view (default) ................................................................7
Heater sub-screen view ...................................................................7
Setup wizard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
First start-up ..............................................................................9
Sub-menu Alarm ........................................................................10
Sub-menu Service .......................................................................10
Function Setup Wizard ...................................................................11
Sub-menu (H1-H4) .......................................................................12
Sub-menu Disinfection schedule .........................................................14
Alarms view .............................................................................15
Main menu ..............................................................................15
4.2 Language setting ........................................................... 16
4.3 Date and Time settings ......................................................16
4.4 BMS settings ................................................................ 16
5 Connection diagram ............................................................. 17
Connection scheme DEVIreg™ Hotwater .................................................17
6 Technical Specifications .......................................................... 18
6.1 Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.2 Dimensions ................................................................. 19
7 Disposal Instruction .............................................................. 20
FEC | Produced by Danfoss © 3
1 Introduction
DEVIreg™ Hotwater is a 4 channel electronic programmable controller. 3 additional chan-
cels are not used in this constellation. The device is DIN-rail mountable and is used for control of Devi Hotwatt cables. Every channel (4) can be individually set up, this will allow for 4 different temperatures and disinfection schedules.
Universal analog channels’ inputs can be selected via software between 7 types of temperature sensors including NTC 15 kOhm at 25 °C. The controller has a LCD display, Modbus RS-485 serial interface and 110/230 V AC power supply. Voltage to sensors is SELV.
DEVIreg™ Hotwater has 8 control relays – 2 sets of max. 10 A and 6 sets of max. 6 A; For this specific application 2, 10A and 2, 6A relays are used. Relay control functions can be set to Hot-water maintenance and legionella control of a hot-water system by use of applicable heating cables. Additionally, relay contacts are not connected to a voltage source inside the controller, and can be used for control systems with any voltage up to 250 V AC.
Hardware of DEVIreg™ Hotwater is based on the Danfoss controller type MCX08M2, art. no. 080G0307, but is customized with special software.
The product complies with the EN/IEC Standard “Automatic electrical controls for house­hold and similar use”:
EN/IEC 60730-1 (general)
EN/IEC 60730-2-9 (thermostat)
More information on this product can also be found at: devi.com
Connection scheme DEVIreg™ Hotwater
Power
110/230 V AC
COM
DI 1-4
DI 1
S - temperature Sensor; H - Heating element.
AI 1
COM
C 1
NO 1
H1 H2 H3 H4
AI 2
COM
DI 2
C 2
NO 2
DI 3
for H2 for H3for H1
AI 3
COM
AI 3-4
NC 3
C 3
NO 3
AI 4
DI 4
NC 4
C 4
NO 4
AI 5
COM
AI 5-8
DI 5
C 5
NO 5
AI 6
DI 6
C 6
NO 6
DI 7
for H4
AI 7
NC 7
C 7
NO 7
NC 8
DI 8
RS485
(Modbus)
D -
D +
AI 8
C 8
NO 8
GND
RS485
COM
DI 5-8
FEC | Produced by Danfoss ©4
2 Safety Instructions
Make sure the mains supply to the controller is turned off before installation.
Please also note the following:
The installation of the controller must be done by an authorized and qualified installer according to local regulations.
The controller must be connected to a power supply via an all-pole disconnection switch.
Always connect the controller to continuous power supply.
Do not expose the controller to moisture, water, dust and excessive heat.
Note: Product is designed for Over Voltage Category II. When used, installation must be equipped with transient protection.
3 Mounting Instructions
Please observe the following placement guidelines:
Install the thermostat in an electric cabinet with DIN rail attachment or a separate DIN attachment according to local regulation on IP classes.
Do not place the thermostat in a way that will expose the controller to direct sunlight.
Follow the steps below to mount the thermostat:
1. Click the thermostat on the DIN rail attachment.
2. Connect the thermostat according to the connection diagram, see page 4.
3. The screen of the heating cable must be connected to the earth conductor of the power supply cable by using a separate connector.
4. Turn on the power supply.
Note: Always install the sensors at assumed hottest and coldest locations on the respec­tive pipe, and in direct contact with the pipe (2 sensors pr. heating circuit)
FEC | Produced by Danfoss © 5
4 User Manual
4.1 General use
The DEVIreg™ Hotwater is operated via 6 physical buttons to the right of the LCD-display.
Buttons
The functions of the 4 operated buttons are:
Up, Down
Left, Right
Escape
Enter Confirm / select / go to the Main menu
Display
The DEVIreg™ Hotwater can simultaneously control up to 4 different systems are referred as H1, H2, H3 and H4 (short for Heater).
The DEVIreg™ Hotwater provides the user with an opportunity to view the current status of the all systems. This status is allways shown on the main screen.
Next menu entry / next line / next setting parameter
Shows additional information
Escape return to previous level of menu / show Alarm screen
. These 4 systems
FEC | Produced by Danfoss ©6
Main Screen view (default)
The Main Screen is the main window appearing when the controller is powered. This screen displays an overview of data from the
different heaters. (H1-H4) by pressing the and more detailed information can be ob-
tained from the respective heaters sub screen.
This view provides the user with an overview of all systems, however with limited information.
Heater sub-screen view
These screens give to user quick and more detailed information about settings and status of each heater.
Just press button on the Main Screen of con­troller and H1 data will appear, press again
- and you'll see H2 data, and so on. To progress
reversly through this menu please use .
To exit from sub-screens view and return to the Main Screen - press 1 time.
FEC | Produced by Danfoss © 7
Setup wizard
On the first power on of the device, the device will ask to run the wizard to do this press
Press once more to proceed into the setup.
The device will ask for the amount heaters use
to select and to accept.
The device will now ask for the details of each heater in the following pattern
- Pipe material
- Sensor type
- Temperature setpoint
- Enable disinfection
All mentioned can be selected with and accepted by .
FEC | Produced by Danfoss ©8
If multiple heaters are entered, this exact pro­cedure will repeat till all information is filled for all heaters.
The final step in the wizard is the RTC (Real Time Clock) press
Navigate with or select with
Manipulate with accept with or return with
Once time and date are set confirm with
First start-up
Ensure everything is correctly connected and securely fixed.
Please check this now.
Once verified press and hold (approx. 3-5 sec.) to turn on the device.
T
he device will now commence normal operation.
FEC | Produced by Danfoss © 9
Sub-menu Alarm
The structure in this Sub-menu is navigated like the main menu.
Active alarms: display of the currently active alarms and is to navigate like Alarm view. Having an active alarm will activate alarm relay. Alarms will be retained till reset has been performed.
Reset Alarms: Reset all alarms by pressing
Log history: display previous alarms in a list
with date and timestamp. This is navigated like Alarm view.
Clear log history: clears the log history perma­nently by pressing
Sub-menu Service
The structure in this Sub-menu is navigated like the main menu.
System: contains a system submenu for profes­sional users containing (Yxx) parameters.
Additionally this menu should under normal circumstances not be used.
This menu will change according to the user level password entered in Login.
Relay counters: Displays the number of relay ON/OFF switching’s performed by each relay.
Software info: Displays the installed software version.
Device info: Displays serial number, product code and BIOS version
FEC | Produced by Danfoss ©10
RTC setup: Setup of the real time clock, this is to navigate like explained in setup wizard step RTC.
Login: Enables a password to be input and is to be navigated with and select with
Configuration: Contains buzzer activation time, delay for alarm activation and alarm state when device is OFF.
Serial settings: Contains Modbus/CAN serial address, Modbus serial baudrate and Modbus serial set­tings
Language: The structure in this Sub-menu is navigated like the main menu.
Contains the different language variants.
Function Setup Wizard
This function will reset the device into the Setup Wizard.
Yes with or NO with
FEC | Produced by Danfoss © 11
Sub-menu (H1-H4)
The structure in this Sub-menu is navigated like the main menu.
Sensor type:
to select correct type and to confirm.
Be aware that 2 sensors must be used for each heater circuit (H1-H4) and that these must be the same type.
-PT1000
-NTC16K (NTC16.8K)
-NTC100 (NTC100K)
-NTC2K
-NTC5K
-NTC10K
-NTC15K (Std. DEVI sensor)
Has no default value as this must be set in setup wizard. Please refer to the sensors maximum and minimum temperatures to ensure safe operation of the system.
Setpoint: Settable with to select and to confirm.
Settable temperature setpoint (desired maintained temperature) between 20.0-80.0°C (20-60.0°C on plastic pipe).
Has no default value as this must be set in setup wizard.
Hysteresis: Settable with to select and to confirm.
Settable between 1.0-10.0K
Defaults to 2.0K
High temperature:
Settable with to select and to confirm.
Settable between 20.0-90.0K
Defaults to Setpoint+Hysteresis+5K
Not settable below setpoint
FEC | Produced by Danfoss ©12
Alarm delay:
Settable with to select and to confirm.
Temperature alarm delay
Settable between 10-240s
Defaults to 10s
Sensor weighting: Settable with to select and to confirm.
Weighting the impact of the 2 sensors on the heater regulation.
0% means that the regulation is made on basis of sensor A only 100% meaning sensor B only, thus 50% is the mean between sensor A and B.
Settable between 0-100%
Defaults to 50%
Disinfection temp:
Settable with to select and to confirm.
Settable between 55-80.0°C
Defaults to 55°C
Pipe material:
Settable with to select and to confirm.
This parameter will have impact on the maximum settable temperatures.
Can be set to metal or plastic.
Has no default value as this must be set in setup wizard
Disinfection alarm temperature:
Settable with to select and to confirm.
This parameter will have impact on the alarm temperature for disinfection temperatures.
Defaults to 65°C
FEC | Produced by Danfoss © 13
Maximum rising time:
Settable with to select and to confirm.
This parameter will have impact on when the alarm will be triggered due to, too low temperature (setpoint not reached).
Defaults to 120 minutes.
Sub-menu Disinfection schedule
The structure in this Sub-menu is navigated like the main menu.
(H1-H4) Schedule:
Press to go to next parameter and to cancel.
Settable with to select and to confirm.
Defaults to Sunday at 02:00.
(H1-H4) Manual start:
Starts the Disinfection procedure manually by pressing
FEC | Produced by Danfoss ©14
Temperature time table:
Temperature of
disinfection [C°]
55 2h 00 minutes 56 1h 20 minutes 57 1h 00 minutes 58 0h 50 minutes 59 0h 45minutes 60 0h 40 minutes 61 0h 35 minutes 62 0h 30minutes 63 0h 28 minutes 64 0h 27 minutes 65 0h 26minutes
Disinfection time
Temperature of
disinfection [C°]
66 0h 25 minutes 67 0h 25 minutes 68 0h 22 minutes 69 0h 21 minutes 70 0h 20 minutes 71 0h 18minutes 72 0h 14 minutes 73 0h 12 minutes 74 0h 10 minutes 75 0h 10 minutes
Alarms view
By pressing button from Main Screen – screen(-s) with Alarm appears. If more than 1 Alarm is happened – use naviga-
tion by going . Pressing button again leads from Alarm to Main Screen. Having an active alarm will activate alarm relay. Alarms will be retained till reset has been performed.
Main menu
Disinfection time
By pressing from the Main Screen– screen Main Menu appears.
The menu system is navigated from Main Screen by the following sequence:
The main menu is navigated by and . Pressing the the selected sub-menu will be shown. Pressing button you will be taken
back to the previous menu step.
FEC | Produced by Danfoss © 15
4.2 Language setting
DEVIreg™ Hotwater controller has different programmed languages located in Sub-menu Service under languages.
4.3 Date and Time settings
DEVIreg™ Hotwater controller has RTC (Real Time Clock) for fixing time of data logging information, for example Alarms.
NB: Battery back-up time is min. 48 hours.
4.4 BMS(Building Management System) settings
DEVIreg™ Hotwater controller has Modbus RS-485 opto-insulated serial interface.
Modbus RS-485 settings can be done by the following menu sequence:
EN: Main Screen – Enter to Main Menu – Enter to Service – Enter to
Serial settings
EN: Main Screen – Enter to Main Menu – Device settings – BMS settings – { Enter –
Serial address – Down – Serial baud rate – Down – Serial settings }
More detailed information is contained in the Appendix A.
FEC | Produced by Danfoss ©16
110/230 V AC
5 Connection diagram
Connection scheme DEVIreg™ Hotwater
Power
DI 1
COM
DI 1-4
S - temperature Sensor; H - Heating element.
for H2 for H3for H1
AI 1
COM
C 1
NO 1
AI 2
COM
DI 2
C 2
NO 2
AI 3
COM
AI 3-4
DI 3
NC 3
C 3
NO 3
DI 4
H1 H2 H3 H4
for H4
RS485
(Modbus)
D -
AI 4
AI 5
COM
AI 5-8
AI 6
AI 7
D +
AI 8
GND
RS485
NC 4
C 4
NO 4
DI 5
C 5
NO 5
DI 6
C 6
NO 6
DI 7
NC 7
C 7
NO 7
NC 8
DI 8
C 8
NO 8
COM
DI 5-8
FEC | Produced by Danfoss © 17
6 Technical Specifications
6.1 Technical data
Type Value
Nominal voltage 110/230 V~ AC, 50–60 Hz Power consumption, max. 20 V A Relay load:
Resistive (inductive, cos(phi sign) = 0,6) Total current load limit C1-NO1, C2-NO2 C3-NO3-NC3, C4-NO4-NC4 C8-NO8-NC8
Sensor inputs Analog inputs AI1-AI8 Compatible sensors NTC15k (15 kOhm @ 25 °C) (standard) (max 90 °C)
Digital inputs DI1-DI8, voltage free contacts, on/off inputs Connection specification Grouped screws plug-in connectors Cable specification for connectors terminals 0,2-2,5 mm² Battery back-up time, min. 48 hours Ball pressure test 125 °C Pollution degree 2 (domestic use) Controller type 1 C Operating temperatures and conditions CE: -20T60 / UL: 0T55, 90% RH non-condensing Storage temperature and conditions -30Т85, 90% RH non-condensing IP class IP40 only on the front cover Protection class Class II ­Immunity against voltage surges Over Voltage Category II Dimensions (H/W/D), DIN dimension : 110(122) х 138 х 70 mm, 8 DIN modules Mounting method DIN rail, complying with EN 60715 Weight, net 511 g Menu languages: EN Base controller Danfoss MCX08M2, item no. 080G0307 Software class A
10 (3,5) A (100 000 cycles), cos(phi) = 0.5
6 (4) A (100 000 cycles), cos(phi) = 0.6 6 (4) A (100 000 cycles), cos(phi) = 0.6
NTC10k (10 kOhm @ 25 °C)
NTC5k (5 kOhm @ 25 °C) NTC2k (2 kOhm @ 25 °C)
NTC100 (100 kOhm @ 25 °C)
NTC16k (16,7 kOhm @ 100 °C)
PT1000 (1000 Ohm @ 0 °C)
32 A
FEC | Produced by Danfoss ©18
110
6.2 Dimensions
140 6063
FEC | Produced by Danfoss © 19
7 Disposal Instruction
FEC | Produced by Danfoss ©20
Appendix A. BMS and RS-485 interface
The controller has a built-in Modbus data transmission system and can be connected to the BMS central unit.
A1. Communication settings
Default communication settings:
Serial address: 1.
Serial baud rate (Transmission speed): 19200.
Serial setting: 8N1.
A2. RS-485 specifications
MCX hardware network specifications (wiring, topology, etc.) can be found in Danfoss document:
User manual. Meet any HVAC requirement with the reliability of MCX network.
This document provides general indications for the setup of RS-485 networks.
A3. Modbus parameters and variables
Modbus parameters and variables for DEVIreg™ Hotwater controller.
LABEL DESCRIPTION MIN MAX.
PARAMETERS & STATUS VARIABLES
SYS Main Menu > System variables
S1 MaxH1_0dec 0 100 80 RW 3001 S2 MaxH1_1dec 0.0 100.0 80.0 RW 3002 S3 MaxH2_0dec 0 100 80 RW 3003 S4 MaxH2_1dec 0.0 100.0 80.0 RW 3004 S5 MaxH3_0dec 0 100 80 RW 3005 S6 MaxH3_1dec 0.0 100.0 80.0 RW 3006 S7 MaxH4_0dec 0 100 80 RW 3007 S8 MaxH4_1dec 0.0 100.0 80.0 RW 3008
S9 AlarmH1 0.0 90.0 90.0 RW 3009 S10 AlarmH2 0.0 90.0 90.0 RW 3010 S11 AlarmH3 0.0 90.0 90.0 RW 3011 S12 AlarmH4 0.0 90.0 90.0 RW 3012 S13 InitConfigured 0 1 0 RW 3013 S14 Dis_warn 0 1 0 RW 3014
StU Service > System
FEC | Produced by Danfoss © 21
VALUE/
TYPE
UNIT RW ADU
y01 Main switch 0 1 0 - OFF Enum 1 RW 3015 y02 Heaters used 0 4 0 RW 3016 y03 Maximum plastic temp 0.0 80.0 60.0 °C RW 3017 y04 Reset counters 0 4 0 - NO Enum 7 RW 3018 y07 Restore default parameters 0 1 0 - NO Enum 2 RW 3019
ALA Service > Configuration
BUZ Buzzer activation time 0 15 1 min RW 3023 AdL Alarm relay activation delay 0 999 0 s RW 3024 AOF Alarm relay active if unit in OFF 0 1 1 - YES Enum 2 RW 3025
SEr Service > Serial settings
SEr Serial address (Modbus and CAN) 1 100 1 RW 3026
bAU Serial baudrate (Modbus) 0 7 5 - 192 Enum 3 RW 3027
COM Serial settings (Modbus) 0 2 0 - 8N1 Enum 4 RW 3028
HE1 Main Menu > H1 Settings
H00 Sensor type 0 6 6 - PT1000 Enum 5 RW 3029 H01 Setpoint 20.0 S2 40.0 °C RW 3030 H02 Hysteresis 1.0 10.0 2.0 K RW 3031 H03 High temperature H01 S9 55.0 °C RW 3032 H04 Alarm delay 10 240 10 s RW 3033 H05 Sensor weighting (0 = 100% sensor A) 0 100 50 % RW 3034 H06 Disinfection temp 55 S1 55 °C RW 3035 H07 Pipe material 0 1 0 - Metal Enum 6 RW 3036 H08 Disinfection alarm temp H06 90.0 65.0 °C RW 3037 H09 Max rising time 1 240 120 min RW 3038
HE2 Main Menu > H2 Settings
H10 Sensor type 0 6 6 - PT1000 Enum 5 RW 3039 H11
Setpoint H12 Hysteresis 1.0 10.0 2.0 K RW 3041 H13 High temperature H11 S10 55.0 °C RW 3042 H14 Alarm delay 10 240 10 s RW 3043 H15 Sensor weighting (0 = 100% sensor A) 0 100 50 % RW 3044 H16 Disinfection temp 55 S3 55 °C RW 3045 H17 Pipe material 0 1 0 - Metal Enum 6 RW 3046 H18 Disinfection alarm temp H16 90.0 65.0 °C RW 3047 H19 Max rising time 1 240 120 min RW 3048
HE3 Main Menu > H3 Settings
H20 Sensor type 0 6 6 - PT1000 Enum 5 RW 3049 H21 Setpoint 20.0 S6 40.0 °C RW 3050 H22 Hysteresis 1.0 10.0 2.0 K RW 3051 H23 High temperature H21 S11 55.0 °C RW 3052 H24 Alarm delay 10 240 10 s RW 3053 H25 Sensor weighting (0 = 100% sensor A) 0 100 50 % RW 3054 H26 Disinfection temp 55 S5 55 °C RW 3055 H27 Pipe material 0 1 0 - Metal Enum 6 RW 3056
20.0 S4 40.0 °C RW 3040
FEC | Produced by Danfoss ©22
H28 Disinfection alarm temp H26 90.0 65.0 °C RW 3057 H29 Max rising time 1 240 120 min RW 3058
HE4 Main Menu > H4 Settings
H30 Sensor type 0 6 6 - PT1000 Enum 5 RW 3059 H31 Setpoint 20.0 S8 40.0 °C RW 3060 H32 Hysteresis 1.0 10.0 2.0 K RW 3061 H33 High temperature H31 S12 55.0 °C RW 3062 H34 Alarm delay 10 240 10 s RW 3063 H35 Sensor weighting (0 = 100% sensor A) 0 100 50 % RW 3064 H36 Disinfection temp 55 S7 55 °C RW 3065 H37 Pipe material 0 1 0 - Metal Enum 6 RW 3066 H38
Disinfection alarm temp H39 Max rising time 1 240 120 min RW 3068
LOG Status var > MCX Design Hotspots
V01 SystemOnOff 0 1 0 - OFF Enum 1 Read 8101 C01 Reset Alarms 0 2 RW 1859 V11 H1_highTemp 0 1 0 - NO Enum 2 Read 8102 V09 H1_controlTemp -50.0 120.0 0.0 °C Read 8103 V11 H1_reference 0.0 100.0 0.0 °C Read 8104 V12 H1 pullDown 0 1 0 - NO Enum 2 Read 8105 V13 H1 manualDis 0 1 0 RW 9901 V14 H2 manualDis 0 1 0 RW 9902 V15 H3 manualDis 0 1 0 RW 9903 V16 H4 manualDis 0 1 0 RW 9904 V16 H1 sensorA error 0 1 0 - NO Enum 2 Read 8106 V17 H1 sensorB error 0 1 0 - NO Enum 2 Read 8107 V16 H1_sensorA -50.0 120.0 0.0 °C Read 8108 V17 H1_sensorB -50.0 120.0 0.0 °C Read 8109 V15 H1_heater 0 1 0 - OFF Enum 1 Read 8110 V16 H1_state 0 6 0 Read 8111 V17 H1_DisinfectionTimer 0 50000 0 s Read 8112 V18 H2 sensorA -50.0 120.0 0.0 °C Read 8113 V19 H2 sensorB -50.0 120.0 0.0 °C Read 8114 V20 H2 sensorA error 0 1 0 - NO Enum 2 Read 8115 V21 H2 sensorB error 0 1 0 - NO Enum 2 Read 8116 V22 H2 controlTemp -50.0 120.0 0.0 °C Read 8117 V23 H2 reference -50.0 120.0 0.0 °C Read 8118 V24 H2 heater 0 1 0 - NO Enum 2 Read 8119 V25 H2 pullDown 0 1 0 - NO Enum 2 Read 8120 V26 H2 highTemp 0 1 0 - NO Enum 2 Read 8121 V27
H2 DisinfectionTimer V28 H2 state 0 6 0 Read 8123 V29 H3_sensorA -50.0 120.0 0.0 °C Read 8124 V30 H3_sensorB -50.0 120.0 0.0 °C Read 8125
H36 90.0 65.0 °C RW 3067
0 50000 0 s Read 8122
FEC | Produced by Danfoss © 23
V31 H3_controlTemp -50.0 120.0 0.0 °C Read 8126 V32 H3_reference -50.0 120.0 0.0 °C Read 8127 V33 H3 heater 0 1 0 - NO Enum 2 Read 8128 V34 H3 state 0 6 0 Read 8129 V35 H3 sensorA error 0 1 0 - NO Enum 2 Read 8130 V36 H3 sensorB error 0 1 0 - NO Enum 2 Read 8131 V37 H3 DisinfectionTimer 0 50000 0 s Read 8132 V38 H3 highTemp 0 1 0 - NO Enum 2 Read 8133 V39 H3 pullDown 0 1 0 - NO Enum 2 Read 8134 V40 H4 sensorA -50.0 120.0 0.0 °C Read 8135 V41 H4 sensorB -50.0 120.0 0.0 °C Read 8136 V42 H4 sensorA error 0 1 0 - NO Enum 2 Read 8137 V43 H4 sensorB error 0 1 0 - NO Enum 2 Read 8138 V44 H4 controlTemp -50.0 120.0 0.0 °C Read 8139 V45 H4 reference -50.0 120.0 0.0 °C Read 8140 V46 H4 heater 0 1 0 - NO Enum 2 Read 8141 V47 H4 state 0 6 0 Read 8142 V48 H4 DisinfectionTimer 0 50000 0 s Read 8143 V49 H4 highTemp 0 1 0 - NO Enum 2 Read 8144 V50 H4 pullDown 0 1 0 - NO Enum 2 Read 8145 V51 H1 Duty 0 100 0 % Read 8146 V52 H2 Duty 0 100 0 % Read 8147 V53 H3 Duty 0 100 0 % Read 8148 V54 H4 Duty 0 100 0 % Read 8149 V56 H1 counter 0 2147483647 0 Read 8150 V57
H2 counter
V58 H3 counter 0 2147483647 0 Read 8154 V59 H4 counter 0 2147483647 0 Read 8156
ALARMS
LABEL DESCRIPTION MIN MAX RESET IN OFF
E01 Sensor1 A error 0 1 AUTO ACTIVE Read 1901 .08 E02 Sensor1 B error 0 1 AUTO ACTIVE Read 1901 .09 E03 Sensor2 A error 0 1 AUTO ACTIVE Read 1901 .10 E04 Sensor2 B error 0 1 AUTO ACTIVE Read 1901 .11 E05 Sensor3 A error 0 1 AUTO ACTIVE Read 1901 .12 E06 Sensor3 B error 0 1 AUTO ACTIVE Read 1901 .13 E07 Sensor4 A error 0 1 AUTO ACTIVE Read 1901 .14
E08 Sensor4 B error 0 1 AUTO ACTIVE Read 1901 .15 A01 Heater1 high temp 0 1 AUTO INACTIVE Read 1901 .00 A02 Heater2 high temp 0 1 AUTO INACTIVE Read 1901 .01 A03 Heater3 high temp 0 1 AUTO INACTIVE Read 1901 .02 A04 Heater4 high temp 0 1 AUTO INACTIVE Read 1901 .03 A05 Heater1 disinfection fail 0 1 MANUAL INACTIVE Read 1901 .04 A06 Heater2 disinfection fail 0 1 MANUAL INACTIVE Read 1901 .05
0 2147483647 0 Read 8152
FEC | Produced by Danfoss ©24
A07 Heater3 disinfection fail 0 1 MANUAL INACTIVE Read 1901 .06 A08 Heater4 disinfection fail 0 1 MANUAL INACTIVE Read 1901 .07 A09 Heater1 rising fail 0 1 MANUAL INACTIVE Read 1902 .08 A10 Heater2 rising fail 0 1 MANUAL INACTIVE Read 1902 .09 A11 Heater3 rising fail 0 1 MANUAL INACTIVE Read 1902 .10 A12 Heater4 rising fail 0 1 MANUAL INACTIVE Read 1902 .11 A13 Heater1 high disinfection 0 1 MANUAL INACTIVE Read 1902 .12 A14 Heater2 high disinfection 0 1 MANUAL INACTIVE Read 1902 .13 A15 Heater3 high disinfection 0 1 MANUAL INACTIVE Read 1902 .14 A16 Heater4 high disinfection 0 1 MANUAL INACTIVE Read 1902 .15
AI ANALOG INPUTS
1 Sensor 1A -30.0 170.0 PT1000 Read 18502 2 Sensor 1B -30.0 170.0 PT1000 Read 18503 3 Sensor 2A -30.0 170.0 PT1000 Read 18504 4 Sensor 2B -30.0 170.0 PT1000 Read 18505 5 Sensor 3A -30.0 170.0 PT1000 Read 18506 6 Sensor 3B -30.0 170.0 PT1000 Read 18507 7 Sensor 4A -30.0 170.0 PT1000 Read 18508 8 Sensor 4B -30.0 170.0 PT1000 Read 18509
DI DIGITAL INPUTS
AO ANALOG OUTPUTS
DO DIGITAL OUTPUTS
1 Heater 1 0 1 N.O. Read 18003 2 Heater 2 0 1 N.O. Read 18004 3 Heater 3 0 1 N.O. Read 18005 4 Heater 4 0 1 N.O. Read 18006 8 Alarm 0 1 N.O. Read 18002
I/O CONFIGURATION
FEC | Produced by Danfoss © 25
Warranty
At DEVI, we find it of great importance to deliver high quality products with long lasting effects. DEVIwarranty™ is a series of 4 individual, best-in-market warranties to give you full peace of mind while using DEVI products in electric heating systems. For all DEVI products, we maintain the following warranties:
A 20-year full service warranty is valid for:
• heating cables incl. DEVIflex™ / DEVIsafe™ / DEVIsnow™ / DEVIasphalt™ / DEVIaqua™/ DEVIbasic™ / DEVIcomfort™ / DEVIsport™ (DSM3) / DEVImulti™ / DEVIinline™;
• heating mats incl. DEVImat™ / DEVIcomfort™ / DEVIheat™ / DEVIsnow™ / DEVIasphalt™ / DTCE;
Not only does this warranty include costs of reparation or replacement, but also installation and floor materials, such as damage to brickwork and tiles. For more details, read DEVIwarranty™ terms and conditions below.
A 10-year product warranty is valid for:
• DEVIcell™ plates, DEVIpipeguard™ LSZH self-limiting heating cables;
A 5-year product warranty is valid for DEVI thermostats, floor heating systems, self-limiting heating cables, and accessories:
• DEVIreg™ Smart thermostat;
• DEVIreg™ Touch thermostat;
• DEVIdry™ floor heating element under carpet, laminate and wooden floor (not including the DEVIdry™ thermostats and control sets);
• DEVIiceguard™, DEVIpipeheat™, DEVIpipeguard™ and DEVIhotwatt™ self-limiting heating cables;
• All related accessories;
A 2-year product warranty is valid for:
• DEVIreg™ 130–132 / 233 / 316 /330 / 527 / 528 / 530–535 / 610 thermostats;
• DEVIreg™ Hotwater, DEVIreg™ 850 controllers;
• DEVIlink™ wireless control system;
• DEVIdry™ thermostats and control sets;
• DEVIreg™ Therm Control;
• DEVIfoil™ heating foils;
• DEVIrail™ towel heaters;
• DEVItemp™ industrial heaters;
• DEVItronic™ anti-condensation heaters;
• Radiant heaters;
• Power supply units for thermostats;
• All related accessories, including heating cables, and heating mats accessories.
Should you, against all expectations, experience a problem the date of purchase on the following conditions: During the warranty period DEVI shall offer a new comparable product or repair the product in case the product is found to be faulty by reason of defective design, materials or workmanship. The repair or replacement shall be carried out free of charge providing that the warranty claim is valid. The decision to either repair or replace will be solely at the discretion of DEVI. DEVI shall not be liable for any consequential or incidental damages including, but not limited to, damages to property or extra utility expenses. An extension of the warranty period following repairs undertaken cannot be granted. The warranty shall be valid only if the WARRANTY CERTIFICATE is completed correctly and in accordance with the instructions, and provided the fault is submitted to the installer or the seller without undue delay and proof of purchase is provided. Please note that the WARRANTY CERTIFICATE must be completed in English or local language. DEVIwarranty™ shall not cover any damage caused by incorrect conditions of use, incorrect installation or if installation has been carried out by non-authorized electricians. All work will be invoiced in full if DEVI is required to inspect or repair faults that have arisen as a result of any of the above. The DEVIwarranty™ shall not extend to products which have not been paid in full. DEVI will, at all times, provide a rapid and effective response to all complaints and inquiries from our customers. The warranty explicitly excludes all claims exceeding the above conditions.
Attention: The Warranty Certificate must be completed correctly for the Warranty to be valid.
with your DEVI product, you will find that DEVI offers DEVIwarranty™ from
FEC | Produced by Danfoss ©26
Warranty Certificate
The DEVIwarranty™ is granted to:
Name:
Address:
Postal code: Phone:
Please observe!
In order to obtain the DEVIwarranty™, the following must be
carefully filled in. See other conditions on previous page.
Electrical Installation by:
Installation date:
Type of thermostat:
Production code:
Suppliers Stamp:
FEC | Produced by Danfoss © 27
Danfoss A/S
Nordborgvej 81 6430 Nordborg, Syddanmark Denmark
08097137 & AN377831097153en-000101 Produced by Danfoss © 06/2021
Loading...