1 Introduction
DEVIreg™ 316 is an electronic thermostat to be installed in
electric cabinets with DIN rail attachment. The thermostat
must be installed via an all-pole disconnection switch.
DEVIreg™ 316 applies to the control of room temperature,
floor temperature, ventilation, cooling or to the control of
snow melting in gutters and similar installations.
For measuring purposes either a wire sensor or an external
air sensor is used.
1.1 Technical Specifications ..... 4
1.2 Safety Instructions ........ 5
3.1 Hysteresis ............. 8
3.2 Minimum Temperature Limiter 9
3.3 Temperature Set-back ...... 10
Installation Guide 3
DEVIreg™ 316
The thermostat has a button to adjust the temperature setting with a scale from -10°C to +50°C . An LED indicator
shows standby periods (green light) and heating periods
(red light).
More information on this product can also be found at:
devireg.devi.com
1.1 Technical Specifications
Operation voltage 220-240V~, 50Hz
Standby power consumption Max 0.25W
Relay:
Resistive load
Inductive load
Sensing units NTC 15kOhm at 25°C
Sensing values:
0°C
25°C
50°C
Hysteresis 0 to 6°C
Ambient temperature 10°C to +45°C
Lowering in economy periods 0 to 8°C
Temperature range -10°C to +50°C
Max 16A / 3680W @ 230V
cos φ= 0.3 max1A
42kOhm
15kOhm
6kOhm
4 Installation Guide