Danfoss Decoupling Plate H6 Installation guide

Installation Guide

Decoupling Plate H6

VLT® Compressor Drive CDS 803

1 Introduction

1.1 Code Number for Item Supplied

Table 1: Code Number

Item

Enclosure size

Code number

 

 

 

Decoupling plate

H6

120Z0837

 

 

 

1.2 Safety Precautions

For important information about safety precautions for installation, refer to the VLT® Compressor Drive CDS 803 Operating Guide.

W A R N I N G

DISCHARGE TIME

The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be present even when the warning indicator lights are off.

Failure to wait the specified time after power has been removed before performing service or repair work could result in death or serious injury.

-Stop the motor.

-Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and DC-link connections to other drives.

-Wait for the capacitors to discharge fully. The minimum waiting time is specified in the table Discharge time and is also visible on the nameplate on the top of the drive.

-Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors are fully discharged.

Table 2: Discharge Time

Voltage [V]

Power range [kW (hp)]

Minimum waiting time (minutes)

 

 

 

3x200

6.0–10 (8.0–15)

15

 

 

 

3x400

6.0–7.5 (8.0–10)

4

 

 

 

3x400

10–30 (15–40)

15

 

 

 

Danfoss A/S © 2021.05

AN365937499532en-000201 / 130R0986 | 1

Danfoss Decoupling Plate H6 Installation guide

Decoupling Plate H6

Installation Guide

Installation

 

 

2 Installation

2.1 Mounting the Decoupling Plate

Procedure

1.Remove the brackets.

<![if ! IE]>

<![endif]>e30bb910.11

2.Mount the metal plate on the drive and fasten it with the 2 screws provided. Tightening torque: 2 Nm (17.7 in-lb).

<![if ! IE]>

<![endif]>e30bb911.11

2 | Danfoss A/S © 2021.05

AN365937499532en-000201 / 130R0986

Loading...
+ 2 hidden pages