Danfoss CTI 25M, CTI 45MB Data sheet

Data sheet
Circuit Breakers
Type CTI 25M, CTI 45MB
Circuit breakers for short circuit and overload protection of motor applications cover the current range 0.1 – 45 A (AC-3 rating). The product range is split in two product sizes. The smallest size is CTI 25M. It consists of 14 code numbers and covers the current range 0.1– 32 A. The bigger size is called CTI 45MB. It consists of two code numbers and covers the current range from 23 – 45 A.
The program is very exible and includes add­on accessories such as auxiliary contacts, alarm contacts, voltage and under voltage trips, connection terminals and bus bars.
Features • Indication for magnetic trip (short circuiting)
• Overload protection and short circuit protection of motor installations
• Test function for thermal trip
• Manual reset function
• Indication for thermal trip
• Single phase protection (Dierential trip)
• Temperature compensated (-20 – 60 °C)
• Tripping class 10
© Danfoss | DCS (az) | 2018.02
IC.PD.C00.A9.02 | 1
Data sheet | Circuit Breakers CTI 25M, CTI 45MB
Approvals
Ordering
Approval
institute
UK Germany France
Lloyds
Register
Product type EN 60947 Canada USA
CTI 25M
CTI 45MB
CBA-
CBA S-
CBT-
CBT S-
VTU-
BDH
RDH
BBT-
BBC-
Approved Approvals applied for
of
Shipping
Germanischer
Circuit Breakers / Manual Motor Starters CTI 25M, CTI 45MB
Type
380 - 415 V
[kW]
0.02 0.1 – 0.16 2.1 047B3140
0.06 0.16 – 0.25 3.3 047B3141
0.09 0.25 – 0.40 5.2 047B3142
0.18 0.4 – 0.63 8.2 047B3143
0.25 0.63 – 1.0 13 047B3144
0.55 1.0 – 1.6 21 047B3145
0.75 1.6 – 2.5 33 047B3146
AC-3 Load
CTI 25M
1.5 2.5 – 4.0 52 047B3147
2.2 4.0 – 6.3 82 047B3148
4.0 6.3 – 10 130 047B3149
7.5 10 – 16 208 047B3150 10 14.5 – 20 260 047B3151 11 18 – 25 325 047B3152 13 24 – 29 406 047B3103 15 27 – 32 448 047B3102
CTI 45MB
15 23 – 32 416 047B3164 22 32 – 45 585 047B3165
Note!
For motors with full load currents higher or equal with 19 A, CTI 25M 047B3152 (18 - 25 A) must be selected
Range
Motor Starter
[A]
Electromagnetic
Trip current
[A]
Lloyd
Bureau Veritas
Code no.
© Danfoss | DCS (az) | 2018.02
IC.PD.C00.A9.02 | 2
Data sheet | Circuit Breakers CTI 25M, CTI 45MB
Ordering
CBA -
CBA S­CBT S-
VTU
Anti tamper shield
Auxiliary contacts and Alarm contacts to circuit breakers CTI 25M, CTI 45MB
Type Description Feature Mounting Code no. CBA-10 Auxiliary contact 1 NC (11-12) Front 1) 047B3198 CBA-11 Auxiliary contact 1 NO+1 NC (13-14, 21-22) Front 1) 047B3200 CBA-20 Auxiliary contact 2 NO (13-14, 23-24) Front 1) 047B3201 CBA S-11 Auxiliary contact 1 NO+1 NC (33-34, 41-42) Side 1) 3) 047B3203
CBT S-TM2 Trip alarm + Magnetic alarm contact
1
) Max. one per Circuit breaker
2
) Can also be mounted together with CBA-S
3
 Can also be mounted onto an alarm contact CBT S-
4
 Always direct onto the circuit breaker
Trip alarm: Make, 55-56, Magnetic alarm: Break, 65-66
Side 2) 4 047B3211
Under voltage and voltage trips to circuit breakers CTI 25M, CTI 45MB
Type Remarks Code no. VTU Under voltage trip, 24 V/50 Hz-28 V/60 Hz, D1-D2 047B3214 VTU Under voltage trip, 220-230 V/50 Hz, D1-D2 047B3217 VTU Under voltage trip, 380-400 V/50 Hz, 440-460 V/60 Hz, D1-D2 047B3220
Accessories for circuit breakers CTI 25M, CTI 45MB
Type Remarks Code no. BDH Black door handle for mounting in panel doors IP66 047B3249 RDH Red/yellow door handle for mounting in panel doors IP66 047B3250
Door handle extension rod for CBI 100-BDH 047B3136
BDH RDH
Door handle extension
BBT 25
BBC 25
Connection terminal blocks and bus bars for circuit breakers CTI 25M, CTI 45MB
Type Remarks
BBT 52 Connection terminal block for CTI 25M 047B3259 BBC 25 45-2 Bus bar for CTI 25M 45 2 047B3261 BBC 25 45-3 Bus bar for CTI 25M 45 3 047B3262 BBC 25 45-5 Bus bar for CTI 25M 45 4 047B3263 BBC 25 45-5 Bus bar for CTI 25M 45 5 047B3264 BBC 25 54-2 Bus bar for CTI 25M 54 2 047B3265 BBC 25 54-3 Bus bar for CTI 25M 54 3 047B3266 BBC 25 54-4 Bus bar for CTI 25M 54 4 047B3267 BBC 25 54-5 Bus bar for CTI 25M 54 5 047B3268
Spacing
[mm]
Number of connections Code No.
© Danfoss | DCS (az) | 2018.02
IC.PD.C00.A9.02 | 3
Data sheet | Circuit Breakers CTI 25M, CTI 45MB
Enclosures for the circuit breaker CTI 25M is made of deform-resistant grey ABS thermoplast.
The enclosures are available with black rotary handle on a grey background or with red rotary handle on a yellow background.
Circuit breaker type CTI 25M for overload protection of electric motors from 0.1 – 25 A full load current can be mounted into the enclosure.
Features
Ordering
 Status indication ON-OFF-TRIP  For maintenance purposes locking facility
up to 3 padlocks  Sealed cover  High protection degree IP65  Cable entries top and bottom M20/25  Mounted with DIN-rail  Mounted with earth terminal  Possible installation of auxiliary and trip
contacts  Space for under voltage and voltage trips
Used as:
 Manual motor starter  Mains isolator  Maintenance switch  Emergency switch together with under
voltage trip
Used on:
 Small workshops for drilling machines  Concrete mixer  Air handling units  Water booster systems  Fan systems  Transport belt
Enclosures for CTI 25M
Type Application Rotary handle Cable entries Code no. BMG Motor starter / Main switch Black/grey 4 M20/25 047B3284 BMY Motor starter / Emergency switch Red/grey 4 M20/25 047B3285
© Danfoss | DCS (az) | 2018.02
IC.PD.C00.A9.02 | 4
Data sheet | Circuit Breakers CTI 25M, CTI 45MB
Contact symbols for CTI and accessories
Circuit breakers
Auxiliary contacts for front mounting
Auxiliary contacts for side mounting
Alarm contacts for side mounting
CTI 25M, CTI 45MB
CBA S-11 CBA S-20 CBA S-02
CBA-01CBA-10
CBA-11 CBA-20
CBA-02
Under voltage trip
Voltage trip
CBT S-2TM CBT S-1T-1M CBT S-1M-1T
VTU-
VT-
CBT S-TM2
CBT S-1M-1M
© Danfoss | DCS (az) | 2018.02
IC.PD.C00.A9.02 | 5
Data sheet | Circuit Breakers CTI 25M, CTI 45MB
General specications
Parameters CTI 25M, CTI 45MB
Isolation voltage IEC, SEV, VDE 0660 UL, CSA
Impulse voltage U
/pollution degree 6 kV/3
imp
Rated frequency range 50/60 Hz
Ambient temperature: Storage Operation Temperature compensation
Utilization category
Overload protection Motors Trip class 10 Magnetic trip 13 × (max. value of setting range) Phase failure protection Yes Mechanical operations 100000 Electrical operations 30000 Switching frequency Max 25 operations/hour Resistance to climate change according to IEC 68-2 Site altitude 2000 m N.N Protection class IP20 Resistance to vibration IEC 68-2 Resistance to shock 30 g, 11 ms Life span 0.1 – 25 A Total power loss 6 – 8 W
690 V 600 V
-40 – 80 °C
-25 – 60 °C
-20 – 60 °C As circuit breaker IEC 947-2
As motor starter IEC 947-4-1
Mounting direction
CTI 25M, CTI 45MB
© Danfoss | DCS (az) | 2018.02
IC.PD.C00.A9.02 | 6
Data sheet | Circuit Breakers CTI 25M, CTI 45MB
Max. motor load
Accessories for circuit breakers CTI 25M
Circuit breaker for overload and short circuit protection of motor applications CTI 25M, CTI 45MB
Setting
Type
[A]
0.1 – 0.16 0.02
0.16 – 0.25
0.25 – 0.4 0.09
0.40 – 0.63
0.63 – 1.0 0.12 0.25 0.25 0.37 0.37 0.55
1.0 – 1.6 0.18 0.25 0.37 0.55 0.55 0.75 0.75 1.1
1.6 – 2.5 0.37 0.75 1.1 1.8
CTI 25M
CTI 45MB 32 – 45 11 13 18.5 22 22 30 30 40
2.5 – 4.0 0.55 0.75 1.1 1.5 1.5 2.2 2.2 3
4.0 – 6.3 1.1 1.5 2.2 2.5 3 4
6.3 – 10 2.2 3 4 4 6.3 5.5 7.5 10 – 16 3 4 5.5 7.5 7.5 10 11 13
14.5 – 20 4 5.5 7.5 10 11 15 17 18 – 25 5.5 11 15 18.5 22 24 – 29 7.5 13 18.5 25 27 – 32 7.5 15 20 25
220 – 240 V 380 – 415 V 500 V 690 V
AC-2 AC-3 AC-2 AC-3 AC-2 AC-3 AC-2 AC-3
0.06
0.06 0.09 0.12 0.18 0.18 0.25
Motor operating voltage – Rated output in [kW]
Auxiliary and trip contacts CBA-, CBA S-, CBT S-
Type Description
Auxiliary
CBA-
CBA S-
CBT S-
contacts for front mounting
Auxiliary contacts for side mounting
Trip contacts for side mounting
I
th
60 °C
[A]
24 V
[A]
40 °C
[A]
5 4 4 3 1.5 2 0.5 0.25
10 6 6 5 3 2 0.7 2 0.5 0.25 0.15
10 6 6 5 3 2 0.7 2 0.5 0.25 0.15
AC-15 DC-13
120 V
220 –
380 –
690 V
240 V
415 V
[A]
[A]
[A]
[A]
24 V
[A]
120 V
[A]
240 V
[A]
415 V
[A]
© Danfoss | DCS (az) | 2018.02
Bus bar terminal and Bus bar connection
Max. load
Type Description
BBT 25 Bus bar terminal for CTI 25M 63 BBC 25 Bus bar connection for CTI 25M 63
Ith at 60 °C
[A]
Voltage and under voltage trip VT-, VTU-
Type Description Operating voltage range Coil consumption
VT-
VTU-
Voltage trip 21 V/50 Hz-415 V/50 H z 24 V/60 Hz-480 V/60 Hz (max 300V UL) Endurance 100%
Under voltage trip 21 V/50 Hz-415 V/50 H z 24 V/60 Hz-480 V/60 Hz (max 300V UL) Endurance 100%
Pull-in
0.85-1.1xU Drop-out
0.7-0.35x U Pull-in
0.85-1.1xU Drop-out
0.7-0.35x U
Pull-in:
s
s
s
s
8.5 VA, 6 W Hold: 3 VA, 1.2 W
Pull-in:
8.5 VA, 6 W Hold: 3 VA, 1.2 W
IC.PD.C00.A9.02 | 7
Data sheet | Circuit Breakers CTI 25M, CTI 45MB
Accessories for circuit breaker
Terminals
Recommended
Type Comments
CTI 25M 1 conductor or
2 conductors
CBA- 1 conductor or
2 conductors
CBA S- 1 conductor or
2 conductors
CBT S- 1 conductor or
2 conductors
VTU- 1 conductor or
2 conductors
CBA- 1 conductor or
2 conductors
BBT 25 1 conductor Pozi 2/ blade 3 6 – 25 6 – 25 4 – 16 3 BBT 25 2 conductors Pozi 2/ blade 3 6 – 16 6 – 16 4 – 10 3
screwdriver size
Pozi 2/ blade 3 1.5 – 6 1 – 6 1 – 4 1 – 2.5
Pozi 2/ blade 3 0.75 – 2.5 0.75 – 2.5 0.5 – 2.5 1.5
Pozi 2/ blade 3 0.75 – 2.5 0.75 – 2.5 0.5 – 2.5 1.5
Pozi 2/ blade 3 0.75 – 2.5 0.75 – 2.5 0.5 – 2.5 1.5
Pozi 2/ blade 3 0.75 – 2.5 0.75 – 2.5 0.5 – 2.5 1.5
Pozi 2/ blade 3 0.75 – 2.5 0.75 – 2.5 0.5 – 2.5 1.5
Solid wire
[mm2]
Stranded
wire
[mm2]
Stranded wire with
sleeve [mm2]
Tightening
torque
[Nm]
© Danfoss | DCS (az) | 2018.02
IC.PD.C00.A9.02 | 8
Data sheet | Circuit Breakers CTI 25M, CTI 45MB
Short circuit protection Short circuit coordination is the connection
between the specications of the protection devices, such as fuses, circuit breakers, MCCB and its ability to resist short circuit.
Short circuit coordination type 1 Test demand
O-t-CO O = Breaking a short circuiting CO = Making and breaking a short circuiting t = Dened pause (3 min)
No damage to equipment or personal injury may occur in the event of short circuit. However, contactors and thermal overload relays are not required to remain functional after short circuit. It is typically the maximum short circuit breaking capacity Icu in use when a plant is dimensioned according to coordination type 1.
Terms Remarks
Prospective short circuit current (Icc)
Rated ultimate short circuit breaking capacity (Icu)
Rated service short circuit breaking capacity (Ics)
Ir-current
Iq current
gI fuse
gL fuse Indicates full short circuit protection of wires.
gG fuse
T fuse Description of an English standard fuse. BS 88 British Standard for smeltesikringer
Short circuit coordination type 2 Test demand
O-t-CO-t-CO O = Breaking a short circuiting CO = Making and breaking a short circuiting t = Dened pause (3 min)
No damage to equipment or personal injury may occur in the event of short circuit. However, light contact welding is permissible, provided that contacts can be separated without deformation, using a screwdriver for example. Contactors and thermal overload relays must remain completely functional after short circuit. It is typical the short circuit breaking capacity during operation Ics in use when a plant is dimensioned according to coordination type 2.
The prospective short circuit current is the current that ows during a bolt short circuiting without any short circuit protection device mounted
The ultimate short circuit breaking capacity is the maximum short circuit current specied by the manufacturer that a circuit breaker can handle under circumstances specied in IEC 947-2 and in EN 60947-2
The rated service short circuit breaking capacity is the maximum short circuit current specied by the manufacturer that a circuit breaker can handle under circumstances specied in IEC 947-2 and in EN 60947-2
The Ir-current is a short circuit test current. The size of the Ir- current is determined by the nominal current of the product. (See below)
Iq –current is the maximum prospective short circuiting current stated by the manufacturer and often at the value 50 kA.
Indicates full short circuit protection at voltages 250V, 400V, 500V and 690V
Indicates full short circuit protection at general applications. (Will replace gI- and gL –fuses)
© Danfoss | DCS (az) | 2018.02
Contactor size Prospective short circuit test current
Rated current at AC-3 load Ir in [kA]
0 < Ie < 16 1
16 < Ie < 63 3
63 < Ie < 125 5 125 < Ie < 315 10 315 < Ie < 630 18
630 < Ie < 1000 30
IC.PD.C00.A9.02 | 9
Data sheet | Circuit Breakers CTI 25M, CTI 45MB
Back-up fuses type gG, gL and Icc > I
cu
Circuit breaker for motor applications
Type
CTI 25M
CTI 45MB 32 – 45 125 125 125 100
– = No fuse required
Type
CTI 25M
CTI 45MB 32 – 45 585 100 100 65 50 50 50 50 50 10 6
Setting
[A]
0.1 – 0.16
0.16 – 0.25
0.25 – 0.4
0.4 – 0.63
0.63 – 1.0
1.0 – 1.6 16
1.6 – 2.5 20
2.5 – 4.0 35
4.0 – 6.3 50
6.3 – 10 63 80 50 10 – 16 80 63 80 63
14.5 – 20 100 100 80 80 63 18 – 25 100 100 80 80 63 24 – 29 125 125 100 100 80 27 – 32 125 125 100 100 80
Thermal
setting
range
[A]
0.1 – 0.16 2.1 100 100 100 100 100 100 100 100 100 100
0.16 –
0.25
0.25 –
0.40
0.40 –
0.63
0.63 – 1.0 13 100 100 100 100 100 100 100 100 100 100
1.0 – 1.6 21 100 100 100 100 100 100 100 100 8 8
1.6 – 2.5 33 100 100 100 100 100 100 100 100 8 8
2.5 – 4.0 52 100 100 100 100 100 100 100 100 8 8
4.0 – 6.3 82 100 100 100 100 100 100 100 100 4 4
6.3 – 10 130 100 100 100 100 50 50 50 50 4 4 10 – 16 208 100 100 65 50 10 6 10 6 3 3
14.5 – 20 260 65 50 50 15 6 6 6 6 3 3 18 – 25 325 65 50 15 15 6 6 6 6 3 3 24 – 29 406 50 25 15 15 6 6 6 6 3 3 27 – 32 448 50 25 15 15 6 6 6 6 3 3
220-240 V
[A]
Magnetic
Trip
current
[A]
3.3 100 100 100 100 100 100 100 100 100 100
5.2 100 100 100 100 100 100 100 100 100 100
8.2 100 100 100 100 100 100 100 100 100 100
220 – 240 V 380 – 415 V 440 – 460 V 500 V 690 V
I
cuIcsIcuIcsIcuIcsIcuIcs IcuIcs
380-415 V
[A]
440-460 V
[A]
Breaking capacity in kA
500 V
[A]
690 V
[A]
© Danfoss | DCS (az) | 2018.02
IC.PD.C00.A9.02 | 10
Data sheet | Circuit Breakers CTI 25M, CTI 45MB
UL/CSA specications
Terminals
Auxiliary contacts and alarm contacts CBA-, CBA S-, CBT-, CBT S-
Max back up
Type Description AC DC
CBA- Auxiliary contacts for front mounting B300 Q300 0A CBA S- Auxiliary contacts for side mounting B600 Q600 0A CBT S- Alarm contacts for side mounting B600 Q600 0A
Stranded
wire
with sleeve
AWG
Type Comments
CTI 25M
1 conductor or
2 conductors
Recommended
screwdriver
size
Solid
wire
AWG
Stranded
wire
AWG
Pozi 2/ blade 3 No. 16-8 No. 16-8 No. 16-12 8.9-22
CTI 45MB 1 conductor Pozi 2/ blade 4 No. 14-6 No. 14-6 No. 14-8 13-31 CTI 45MB 2 conductors Pozi 2/ blade 4 No. 14-4 No. 14-4 No. 14-6 13-31
CBA-
CBA S-
CBT S-
VTU-
CBA-
1 conductor or
2 conductors
1 conductor or
2 conductors
1 conductor or
2 conductors
1 conductor or
2 conductors
1 conductor or
2 conductors
Pozi 2/ blade 3 No. 14-6 No. 14-6 No. 14-8 13.3
Pozi 2/ blade 3 No. 18-14 No. 18-14 No. 18-14 13.3
Pozi 2/ blade 3 No. 18-14 No. 18-14 No. 18-14 13.3
Pozi 2/ blade 3 No. 18-14 No. 18-14 No. 18-14 13.3
Pozi 2/ blade 3 No. 18-14 No. 18-14 No. 18-14 13.3
BBT 25 1 conductor Pozi 2/ blade 3 No. 18-14 No. 18-14 No. 18-14 27 BBT 25 2 conductors Pozi 2/ blade 3 No. 14-6 No. 14-6 No. 14-8 27
fuse
type gG, gL
Tightening
torque
[Ib-in]
UL/CSA specications
Circuit breaker for overload- and short circuit protection of motor applications
Range
Type
[A]
1-phase run 3-phase run
115 V 230 V 230 V 460 V 575 V 480 V 600 V
0.1 – 0.16 65 47
0.16 – 0.25 65 47
0.25 – 0.4 65 47
0.4 – 0.63 65 47
0.63 – 1.0
1
10
1
6
1
3
1
2 3 5 65 30
CTI 25M
1.0 – 1.6
1.6 – 2.5
2.5 – 4.0
4.0 – 6.3
6.3 – 10 10 – 16
1
8
1
4
1
2 1 3 5 7 ½ 65 30
3
4 2 5 10 10 30 30
14.5 – 20 1 3 5 15 10 10 18 – 25 1 ½ 7 ½ 15 20 10 5 24 – 29 10 20 25 10 – 27 – 32 10 25 30 10
CTI 45MB 32 – 45 3 15 30 40 65 18
Motor rating in hp
Prospective
short circuit current
[kA]
1
3
1
2 1 1 ½ 65 30
3
4 2 3 65 25
4
2 65 47
3
4 65 47
© Danfoss | DCS (az) | 2018.02
IC.PD.C00.A9.02 | 11
Data sheet | Circuit Breakers CTI 25M, CTI 45MB
Let-through curves for circuit breakers CTI 25M
Max let-through current for circuit breakers CTI 25M
A: Max let-through current ID [kA] B: The prospective short circuit current at 415 V I
Max let-through energy for circuit breakers CTI 25M
cc
[kA]
© Danfoss | DCS (az) | 2018.02
A: Max let-through energy I2t [kA2s] B: The prospective short circuit current at 415 V I
cc
[kA]
IC.PD.C00.A9.02 | 12
Data sheet | Circuit Breakers CTI 25M, CTI 45MB
Let-through curves for circuit breakers CTI 45MB
Max let-through current for circuit breakers CTI 45MB
A: Max let-through current ID [kA] B: The prospective short circuit current at 415 V I
Max let-through energy for circuit breakers CTI 45MB
cc
[kA]
© Danfoss | DCS (az) | 2018.02
A: Max let-through current I2t [kA2s] B: The prospective short circuit current at 415 V I
cc
[kA]
IC.PD.C00.A9.02 | 13
Data sheet | Circuit Breakers CTI 25M, CTI 45MB
Overload protection of motors
Tripping characteristic for CTI 25M
A: Trip time in sec. B: Times the adjustable current I
ef
1) Thermal trip
The adjustable bimetals ensure a reliable
overload protection of motors. The curve is mean value curve at 20°C ambient temperature from cold state. It also ensures protection of motors by phase failure (dierential trip).
All three bimetals must be connected in series
by overload protection of 1-phase motors.
2) Magnetic trip
The electromagnetic trips react at a xed
response current. The size of the xed response current correspond typically to 13 times of the maximum range of the circuit breakers CTI 25M, CTI 45MB.
© Danfoss | DCS (az) | 2018.02
IC.PD.C00.A9.02 | 14
Data sheet | Circuit Breakers CTI 25M, CTI 45MB
Coordination without fuse
Circuit breakers and contactors
Max. prospective short circuit-current Iq = 50 kA Voltage 380-415 V/50 Hz Overload protection CTI 25M, CTI 45MB Short-circuit protection CTI 25M, CTI 45MB Short-circuit coordination T1 and T2
Coordination type 1 Coordination type 2
Contactor
Ir 1) and Iq = 50 kA Ir 1) and I
CTI 25M CTI 45MB CTI 25M CTI 45MB
= 50 kA
q
Max. CTI range [A]
CI 5-2, CI 5, CI 5-9, CI 5-12 25 45 2.5 2.5 CI 6, CI 9 25 45 2.5 2.5 CI 12, CI 15 25 45 4.0 4.0 CI 16 25 45 6.3 20 CI 20, CI 25 25 45 6.3 25 CI 30 25 45 10 25 CI 32 45 32 CI 37, CI 45, CI 50 90 45 CI 61, CI 73, CI 86 90
1
) Short-circuit current according to EN 60947-4 (see page 16)
Circuit breakers, contactors and thermal overload relays
Max. prospective short-circuit current Iq = 50 kA Voltage 380-415 V/50 Hz Overload protection Thermal overload relay type TI 9C, TI 16C, TI 25C, TI 30C, TI 80 Short-circuit protection CTI 25M, CTI 45MB Short-circuit coordination T1
Contactor
Thermal overload relay
range
Coordination type T1
Test current I
r
Max. CTI range
[A]
CI 5-9, CI 6, CI 9 0.13 – 0.20 45 CI 5-9, CI 6, CI 9 0.19 – 0.29 45 CI 5-9, CI 6, CI 9 0.27 – 0.42 45 CI 5-9, CI 6, CI 9 0.4 – 0.62 45 CI 5-9, CI 6, CI 9 0.6 – 0.92 45 CI 5-9, CI 6, CI 9 0.85 – 1.3 45 CI 5-9, CI 6, CI 9 1.2 – 1.9 63 CI 5-9, CI 6, CI 9 1.8 – 2.8 63 CI 5-9, CI 6, CI 9 2.7 – 4.2 63 CI 5-9, CI 6, CI 9 4 – 6.2 63 CI 9 6 – 9.2 63 CI 12, CI 15 8 – 12 63 CI 15, CI 16 11 – 16 90 CI 16, CI 20 15 – 20 90 CI 25 19 – 25 90 CI 30 24 – 32 90 CI 32 22 – 32 90 CI 37, CI 45 30 – 45 90 CI 50, CI 61 42 – 63 90 CI 73 60 – 80 90 CI 86 74 – 85 90
1
) Short-circuit current according to EN 60947-4 (see page 16)
1
) and I
[A]
= 50 kA
q
© Danfoss | DCS (az) | 2018.02
IC.PD.C00.A9.02 | 15
Data sheet | Circuit Breakers CTI 25M, CTI 45MB
Coordination with fuse Contactors
Max. prospective short-circuit current Iq = 50 kA Voltage 380-415 V/50 Hz Overload/short-circuit protection gG and T (BS88) Short-circuit coordination T1 and T2
Contactor
CI 5-2, CI 5-9, CI 5-12 25 32 16 20 16 20 CI 6, CI 9, CI 12, CI 15 50 63 25 32 25 32 CI 16 80 80 25 32 25 32 CI 20, CI 25 80 08 25 32 25 32 CI 30 80 80 35 40 25 32 CI 32 125 125 50 63 35 40 CI 37, CI 45, CI 50 125 125 80 80 80 80 CI 61, CI 73, CI 86 250 160 CI 141 315 250 CI 180 355 315 CI 210 EI, CI 250 EI 500 400
1
) Short-circuit current according to EN 60947-4 (see page 16)
Short-circuit coordination
T1 T2
Test current
Ir 1) and Iq = 50 kA Ir 1) and Iq = 10 kA Ir 1) and I
gG [A]
[A]
T
gG [A]
[A]
T
gG [A]
= 50 kA
q
T
[A]
Contactors and thermal overload relays
Max. prospective short-circuit current Iq= 50 kA Voltage 380-415 V/50 Hz Overload/short-circuit protection gG and T (BS88) Short-circuit coordination T1 and T2
Thermal overload
relay
Contactor
Ir 1) and Iq = 50 kA Ir 1) and Iq = 10 kA Ir 1) and I
gG
[A]
[A]
CI 5-9, CI 6, CI 9 0.13 – 0.20 25 32 2 2 CI 5-9, CI 6, CI 9 0.19 – 0.29 25 32 2 2 2 CI 5-9, CI 6, CI 9 0.27 – 0.42 25 32 2 2 2 2 CI 5-9, CI 6, CI 9 0.4 – 0.62 25 32 4 4 4 4 CI 5-9, CI 6, CI 9 0.6 – 0.92 25 32 4 6 4 6 CI 5-9, CI 6, CI 9 0.85 – 1.3 25 32 4 6 4 6 CI 5-9, CI 6, CI 9 1.2 – 1.9 25 32 6 10 6 10 CI 5-9, CI 6, CI 9 1.8 – 2.8 25 32 6 10 6 10 CI 5-9, CI 6, CI 9 2.7 – 4.2 25 32 16 20 16 20 CI 5-9, CI 6, CI 9 4 – 6.2 35 40 20 25 20 25 CI 5-9, CI 6, CI 9 6 – 9.2 50 50 20 25 20 25 CI 12 8 – 12 63 63 25 32 25 32 CI 15, CI 16 11– 16 80 80 25 32 25 32 CI 20, CI 25 15 – 20 80 80 35 40 35 40 CI 25 19 – 25 80 80 35 40 35 40 CI 30 24 – 32 80 80 35 40 35 40 CI 32 16 – 23 125 125 50 63 35 40 CI 32 22 – 32 125 125 63 63 35 40 CI 37, CI 45 30 – 45 125 125 80 80 63 63 CI 50 42 – 63 125 125 80 80 63 63 CI 61 42 – 63 160 80 CI 73 60 – 80 160 125 CI 86 74 – 85 160 160 CI 98 20 – 180 250 200 CI 141 20 – 180 315 250 CI 180 20 – 180 355 315 CI 210 EI, CI 250 EI 160 – 630 500 400 CI 300 EI, CI 420 El 160 – 630 630 500
1
) Short-circuit current according to EN 60947-4 (see page 16)
Short-circuit coordination
T1 T2
Test current
T
[A]
gG [A]
T
[A]
gG [A]
q
= 50 kA
T
[A]
© Danfoss | DCS (az) | 2018.02
IC.PD.C00.A9.02 | 16
Data sheet | Circuit Breakers CTI 25M, CTI 45MB
Dimensions
Circuit breakers CTI 25M
Circuit breakers CTI 45MB
© Danfoss | DCS (az) | 2018.02
IC.PD.C00.A9.02 | 17
Dimensions Enclosures BMG and BMY
for circuit breakers CTI 25M
© Danfoss | DCS (az) | 2018.02
IC.PD.C00.A9.02 | 18